System Settings 

When HMI is powered up and displays image, 
click the system setting button. 
(Default System Password: 111111) 
It is necessary to connect the HMI to   
your network through a RJ-45 cable. 

EasyBuilder Pro Software Settings 

Launch EasyBuilder Pro software, select your 
project file, press F7 shortcut key to open 
the download dialog box:   

Select Ethernet > IP tab > Enter your HMI IP 

> Click Download to download this project

file to HMI.

Communication Connections 

COM1 [RS232] 9 Pin, Male, D-sub 

  COM2

 / 

COM3 [RS485] 9 Pin, Female, D-sub 

DIP SW Settings 

CAUTION

NN

Limited Warranty 

This product is limited warranted against defects in design and manufacture. 

The proven defective product will either be repaired or replaced, at 

SENECA

’s 

discretion. This warranty shall not cover any product which is  

(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.

NOTE:   

Make sure that all local and national electrical standards are met when installing 
the unit. Contact your local authorities to determine which codes apply. 

PIN# 

Symbol 

COM1 [RS232] 

Not used 

RxD 

Received Data 

TxD 

Transmitted Data 

Not used 

GND 

Ground 

Not used 

RTS 

Ready to send output 

CTS 

Clear to send input 

Not used 

 

PIN# 

Symbol 

Com2 
[RS485]2w 

Com2 
[RS485]4w 

Com3 
[RS485] 

Rx- 

Data- 

Rx- 

Rx+ 

Data+ 

Rx+ 

Tx- 

Tx- 

Tx+ 

Tx+ 

GND 

Ground

 

Data- 

Data- 

Not used 

Not used 

Data+ 

Data+ 

SW1 

SW2 

SW3 

SW4 

Mode 

ON 

OFF 

OFF 

OFF

 

Touch Screen Calibration Mode 

OFF 

ON 

OFF 

OFF

 

Hide HMI System Setting Bar 

OFF 

OFF 

ON 

OFF

 

Boot Loader Mode 

OFF 

OFF 

OFF 

ON 

Not supported 

OFF 

OFF 

OFF 

OFF

 

Normal 

NOTE: 

COM2 and COM3 [RS485] 2W support MPI 187.5K, please use one at one time.

 

Go to the Network tab, you may choose 
to auto get DHCP IP, or designate your 
own IP.

 

Power 

The 

HMI

 can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with 

most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a 

switching power supply. The peak starting current can be as high as 2A.

 

Fusing 
Require- 
ments 

If the display does not come on within 5 seconds of power up, remove power. An internal fuse will 

prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections 

and try to power up again. 

High 
Voltage 

An Internal fuse will prevent damage for overcurrent 

condition however it isn’t guaranteed. DC 

voltage sources should provide proper isolation from main AC power and similar hazards. 

Emergency 
Stop 

A Hard-wired EMERGENCY STOP should be fitted in any system using 

HMI

 to comply with ICS 

Safety Recommendations. 

Supply 
Voltage 
Condition 

Do not power the 

HMI

 and inductive DC loads, or input circuitry to the controller, with the same 

power supply. Note: The 24 VDC output from some controllers may not have enough current to 

power the 

HMI.

 

Wire 
Routing 

a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).

b. Please use twisted pair cables for power wire and signal wire and conform to the impedance

matching.

c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.

d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.

e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power 

supply and the frame ground. This provides a path for static and high frequency dissipation.

Typical values to use are 1M Ohm and 4700pF.

CAUTION 

NOTE: 

Make sure that all local and national electrical standards are met when 

installing the unit. Contact your local authorities to determine which codes apply. 

Hardware 
Considerations 

The system designer should be aware that devices in Controller systems could fail and thereby 

create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to 

equipment start-up, which could result in property damage and/or physical injury to the operator. 

If you use any programmable control systems that require an operator, be aware that this potential 

safety hazard exists and take appropriate precautions. Although the specific design steps depend on 

your particular application, the following precautions generally apply to installation of solid-state 

programmable control devices, and conform to the guidelines for installation of Controllers 

recommended in NEMA ICS 3-304 Control Standards.

 

Programming 
Considerations 

To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure 

that all writable registers that control critical parts of plant or machinery have limit checks built into 

the program, with an out-of-limit safe shut down procedure to ensure safety of personnel. 

DANGER 

CAUTION

NN

NOTE:   

Make sure that all local and national electrical standards are met when installing 
the unit. Contact your local authorities to determine which codes apply. 