User Manual
T201DCH50/100/300/600-MU
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
Doc. MI00546-EN
Rev.2
Page 21
6.2.
Creating a Project Configuration
WARNING!
You must set all dip switches to OFF before sending the configuration to the device or the actual
configuration will be overwritten from the dip switches configuration!
The parameters in the “Configuration” section that can be configured are:
Model:
Select between T201DCH50-MU, T201DCH100-MU, T201DCH300-MU, T201DCH300-MU HW2 or
T201DCH600-MU model.
Station Address:
Select The Modbus RTU station address
Baud Rate:
Select the Baud rate from 1200 to 115200 baud
Parity:
Select NONE, ODD or EVEN
Mode:
Select the current measure mode: True RMS or DC Bipolar
Filter:
Select between LOW or HIGH:
FILTER
RMS RESPONSE
TIME
(10%-90% F.S.)
BIPOLAR DC
RESPONSE TIME
(10%-90% F.S.)
LOW
1400 ms
78 ms
HIGH
2900 ms
650 ms