REGISTER
NAME
COMMENT
REGISTE
R TYPE R/W
DEFAUL
T VALUE
OR
START
VALUE
ADDRESS
(4xxxx)
OFFSET
ADDRES
S
THRESHOLD
HIGH
Select the High
Threshold for the Alarm
in [A]
Float32
RW*
According
to the
model
40121 (LSW)
40122 (MSW) 120-121
THRESHOLD
LOW
Select the Low
Threshold for the Alarm
in [A]
Float32
RW*
According
to the
model
40123 (LSW)
40124 (MSW) 122-123
FULL CONFIGURATION WITH EASY SETUP
6.
For configure all the device parameters you must use the RS485 Port and the Easy T201DCH-MU software
included in the Easy Setup Suite.
You can download the Easy Setup software for free from:
6.1.
Easy Setup Menu
Connect
: Use the connect icon for connect the PC to the Device. Note that you need a RS485 to USB
converter like Seneca S117P1 or S107USB for connect the device to a PC.
New:
Load the default parameters in the actual project
Open:
Open a stored project
Save:
Save the actual project
Read:
Read the actual configuration from the device (if the dip switches are not ALL OFF the configuration is
read from dip switches)
WARNING!
If you read a configuration from the device with at least one dip switch to “ON” the software will read
the dip switch configuration because overwrite the flash configuration.
Send:
Send the project configuration (if the dip switches are not ALL OFF the device use the dip switch
configuration and NOT the sent configuration)
Test:
Start a Registers read, you can also reset the MIN/MAX values and start/stop a Datalogger