ENGLISH - 12/21
MI00250 -E
3
TYP_AL3/RLY3
Bit [15:8]
Bit [7:1]
R/W
40009
TYP_AL4/RLY4
R/W
40010
Bit 0
Bit [15:8]
Bit [7:1]
Bit 0
Set the Alarm 3 functioning:
0* = Alarm disabled
1 = Alarm on the minimum threshold
2 = Alarm on the maximum threshold
3 = Retained alarm on the minimum threshold (reset
is not automatic)
4 = Retained alarm on the maximum threshold
(reset is not automatic)
Sets the normal status of relay 3 and alarm 3
type.
Not used
Sets the relay 4 functioning:
0* = normally opened
1 = normally closed
Sets the normal status of relay 4 and alarm 4
type.
Set the Alarm 4 functioning:
0* = Alarm disabled
1 = Alarm on the minimum threshold
2 = Alarm on the maximum threshold
3 = Retained alarm on the minimum threshold (reset
is not automatic)
4 = Retained alarm on the maximum threshold
(reset is not automatic)
Not used
Sets the relay 3 functioning:
0* = normally opened
1 = normally closed
PASSWORD
Enables / disables the password for the
access to the programming menu.
R/W
40011
Bit [15:0]
By setting a value different from
, at the start of
5477
the programming menu the password (always
5477) will be required. Default: 5477.
TYP_OUT/BURN
Sets the behavior in case of Burn Out (PT100
or TC) and output type
R/W
40012
Set the retransmitted output type:
1 = 0..10 V output
2* = 4..20 mA output
3 = 0..20 mA output
Bit [15:8]
Bit 0
Behavior in case of PT100 or Thermocouple Burn
out
:
0* = Full scale indication
1 = Start scale indication.
Bit [7:1]
Not used