MI001458-E
ENGLISH - 10/16
Value of the quantity to transmit (defined via DIP-
switch and phase selected via PHASE_RETR
register, 40017) which gives the maximum value
(100%) of the transmitted output. The value is
expressed in floating point format (most
significative word) and therefore it must be
expressed in the corresponding measurement
unit of the quantity chosen (V for Vrms, mA for
Irms, W for Watt) . Default: 600,0.
Bit [15:0]
ADDR_PARITY
Bit [15:8]
Bit [7:0]
Register for the setting of the module’s
address and parity control.
Set the module’s address. Allowed values from
0x00
0xFF
a
(decimal values in the interval of 0-
255 ). Default: 1.
Set the type of parity control:
00000000* : No parity
( NONE )
00000001 : Even parity
( EVEN )
00000010 : Odd parity
( ODD )
R/W
40025
MAXOUT_FL_MSW
Value of the quantity to transmit which gives
the maximum retransmitted output (floating
point format, most significative word).
40022 R/W
MINOUT_FL_LSW
MAXOUT_FL_LSW
CHECK_FREQ
Value of the quantity to transmit which gives
the minimum retransmitted output (floating
point format, least significative word).
Value of the quantity to transmit which gives
the maximum retransmitted output (floating
point format, least significative word).
Enables measurement errors compensation
of Active Power and Energy caused by
network frequency variations.
40021
40023
40024
R/W
R/W
R/W
Bit [15:1]
Bit 0
Not used
Errors compensation caused by network
frequency variations:
1: If network frequency is not stable at 50 Hz or 60
Hz, or has consistent variations (> 30 mHz), this
register corrects the measurement of Power and
Energy. The measurements of Vrms and Irms are
not influenced by this setting.
BAUDR_ANSDEL
Register for the setting of the Baud rate and
the response delay time in characters.
R/W
40026
Bit [15:8]
Set the serial communication speed value
(Baudrate):