background image

MI00472-3-EN

INSTALLATION MANUAL

3/4

CERTIFICATIONS

https://www.seneca.it/products/r-key-lt/doc/CE_declaration

INSULATION

POWER SUPPLY

Voltage: 11 ÷ 40Vdc; 19 ÷ 28Vac; 50 ÷ 60 Hz, max absorption: 1W

ENVIRONMENTAL

CONDITIONS

Temperature: -25°C ÷ +65°C

Humidity: 30% ÷ 90% non condensing

Storage temperature: -30°C ÷ + 85°C

Protection rating: IP20 (not rated by UL)

ASSEMBLY

DIN rail 35mm IEC EN60715, wall or panel with screws.

CPU

ARM 32 bit

OPERATING SYSTEM

Real time multitasking

CONFIGURATION

Configuration and FW update via webserver;

Via DIP - SWITCH

Via EASY SETUP 2 configuration software

CONNECTIONS

Removable 7-way screw terminals, 5 mm pitch, cable section up to 2.5 mm

2

Removable 2-way screw terminals, 5 mm pitch, cable section up to 2.5 mm

2

RJ45 connector for Ethernet cable

COMMUNICATION

RS232/RS485 on 1-7 terminal; maximum Baud rate 115k

ETHERNET PORTS

1 x 100Mbit Ethernet port with auto switch

TECHNICAL SPECIFICATIONS

CAUTION

DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.

WEB SERVER

To access the maintenance Web Server with the factory IP address above, use the following credentials:

Username:

 admin; 

Password:

 admin

N.B.:

 For the R-KEY-LT-P version it is first necessary to activate webserver mode

The device is normally in Profinet mode; in Profinet mode the device can be configured only through the Easy Setup 2 software. 

In order to access the internal webserver it is necessary to put the device in Webserver mode using the Easy Setup2 or Seneca 

Device Discovery software. It is also possible to change the operating mode by pressing the side button following the procedure:

To force webserver mode:

• 

Keep the “REBOOT / MODE” button pressed until all the LEDs flash quickly

• 

Release the button

• 

The device restarts and the PWR and COM LEDs flash slowly to indicate webserver mode

To force Profinet mode:

• 

Keep the “REBOOT / MODE” button pressed until all the LEDs flash quickly

• 

Release the button

• 

The device restarts and the PWR and COM LEDs stop flashing slowly to indicate Profinet mode

WEB SERVER AND PROFINET MODE (R-KEY-LT-P)

PWR

RS232/485

ETH

1500 V

ac

Отзывы: