Kingfisher Plus+ Hardware Manual
14.4.3 IO-5 Specifications
IO-5 Analogue / Digital Combinational M odule Specifications
Operating Tem perature
-40 to +85 °C
Storage Tem perature
-40 to +85 °C
Hum idit y
5 to 95 % RH (non-condensing)
Output Power
24 V
DC
/ 100 mA max, Isolated
Maxim um W orking
Voltage on an y contact of
the field connector
42.4 V
PEAK
/ 60 V
DC
relative to system (backplane) ground
Hot Swap
Yes. Module can be swapped while RTU is running. Hot swap will
not cause a Warm Start.
ANALOGUE INPUTS
Input Current Ranges
4 - 20 mA or 0 - 20 mA
Input Voltage Ranges *
1 - 5 V or 0 - 5 V *
Inputs per Module
4
Resolution
Unsigned 12 bit
Accurac y
(includes Gain, Linearity
and Offset errors)
± 0.25% @ 25 °C
± 0.50% @ -40 to +85 °C
Update Rate
120 ms
Cross-Channel Rejection
> 115 dB from DC to 1 kHz
Input Im pedance
250 Ω standard
1
MΩ optional *. The internal load resistors can be factory
removed if high impedance voltage inputs are required.
Input Filter
Cutoff Frequenc y
7 Hz @ -3 dB
AC noise attenuation
16 dB @ 50 Hz
18 dB @ 60 Hz
Output Field Power
24 V
DC
/ 80 mA Isolated
Isolation
5 kV Transient
Hardware Manual Version 7.16
http://www.servelec-semaphore.com/
Page 221