Operation 

LED (2) 

AC Overload should normally remain OFF. If the inverter shuts 

down due to too much AC load being drawn from it then LED (2) will come 
ON. The LD550-24 will remain in this condition for 1 minute after the AC 
load has been decreased to a safe level. LED (2) will flash if the inverter shuts 
down due to “time to shutdown”, see page 18 

Five LEDs are provided on the front panel to indicate a number of 
parameters, and allow adjustment of some of these parameters. 
LED (5) tells you what LED (1) – (4) is displaying as indicated on the front 
panel of the LD550-24. Pressing Mode Button (7) will change the information 
being displayed. 

 

If the inverter remains in this condition after one minute, switch (12) 
should be turned OFF and then back ON. 

STATUS indicators LED (5) (green) flashing 

LED (3) 

DC Volts Low / High

 should normally remain OFF. If the inverter 

shuts down because the battery volts are too high then this LED (3) will come 
ON. It will remain ON until normal battery volts are restored. 

When power is first applied LED (1) should flash. 

When LED (5) (green) is OFF, this indicates the LED (1) – (4) is showing the 
inverters STATUS, as per written notation to the right of the LEDs. In this 
mode there are no adjustments to be made. 

 

If the inverter shuts down due to not enough battery volts, then LED (3) 
will flash. 

 

LED (3) will continue to flash until the battery volts have risen 
sufficiently. In this case, charge the battery by starting the vehicle or using 
a battery charger. 

LED (1) Flashing

 indicated the LD550-24 is in Demand Start mode, this 

indicates that no power is being drawn from the inverter so it has gone to 
SLEEP to save power. If no power is used within 12 minutes, the LED (1) 
will flash at a slower rate therefore saving more power. 

 
The low voltage point that the inverter will cut out is adjustable to suit your 
particular battery, see page 12 for details of this adjustment. 

LED (1) Stays ON

, the inverter has been commanded to provide power to the 

load (e.g. a light switch has been turned on) so it has gone from SLEEP mode 
to ON. Once the load has been removed (e.g. the light switch is turned off) the 
inverter will wait 10 seconds and return to SLEEP mode. 

 

LED (4) 

Temperature Overload

 should normally remain OFF. If the inverter 

shuts down due to the heatsink getting too hot, then this LED (4) will come 
ON. If the transformer is too hot then LED (4) will FLASH. The LED will 
remain ON or FLASHING until the temperature has lowered to a safe level; 
the inverter will then come back ON. 

It is good practice to have your LD550-24 in SLEEP mode as often 
as possible. When the LD550-24 is in SLEEP mode it uses 0.05 
amps from the battery, when the inverter is in the ON mode it uses at 
least 0.50 amps from the battery. 

 

If this LED (4) is coming on regularly, either reduce the amount of load 
on the inverter or try to move the inverter to a cooler location. 

 

The amount of power required to go from SLEEP to ON is adjustable and is 
described on page 11. 

LD550-24 Manual 

 

Selectronic Australia

 

LD550-24 Manual 

 

Selectronic Australia

 

Содержание LD550-24

Страница 1: ...o Introduction 1 Warranty Card 1 Installation 1 Batteries and Connections 4 Getting Started Quickly 6 Parts Identification 6 Operation 7 STATUS Indicators 7 Demand Start Setting 9 Low Voltage Shutdown Setting 10 Maintenance 11 Inverter 11 Batteries 11 Handy Hint 12 Radio Frequency Interference 13 Fault Finding 14 Product Warranty Conditions 15 Specifications 16 Selectronic Service Network Back Cov...

Страница 2: ... card please feel free to drop us a line Yes constructive criticism will also be welcome Installation 200mm 200mm 200mm LD550 24 Inverter Front 200mm LD550 24 Inverter A system fuse of at least 25 Amps should be placed before the battery An HRC motor start type is recommended See your system designer for details Warning As a matter of safety Selectronic strongly recommend that all fixed installati...

Страница 3: ... be stored in a battery this figure will generally be stated at a particular hour rate This is how a deep cycle or storage battery would normally be rated Start Battery By incorporating an auxiliary battery in the manner above the starting battery should remain charged for vehicle starting see your auto electrician The LD550 24 has sufficient battery cable length to allow it to sit underneath the ...

Страница 4: ...d on a regular basis the less life you can expect from the battery See you battery specifications for full details If you want to get powered up quickly here are the 11 simple steps 1 Familiarise yourself with the details in the first 6 pages on this manual 2 Unpack the LD550 24 from the packaging 3 Check unit for any damage that may have resulted during transport if any damage is evident report t...

Страница 5: ...y by starting the vehicle or using a battery charger LED 1 Flashing indicated the LD550 24 is in Demand Start mode this indicates that no power is being drawn from the inverter so it has gone to SLEEP to save power If no power is used within 12 minutes the LED 1 will flash at a slower rate therefore saving more power The low voltage point that the inverter will cut out is adjustable to suit your p...

Страница 6: ...econds Hold the Mode button 7 down until LED 5 is FLASHING approximately 2 seconds indicating you are ready to adjust this setting Now press the Mode button 7 until the desired value is sought LEDs 1 4 will return to Status after 20 seconds Low Volts Cut out LED 1 LED 2 LED 3 LED 4 20 0 Volts 20 2 Volts 20 4 Volts 20 6 Volts 20 8 Volts Slow Flash Medium Flash Fast Flash Fastest Flash ON ON ON ON O...

Страница 7: ...e inverter s operation by flashing when the inverter is in SLEEP mode and remaining ON when the inverter is brought ON by a load Batteries 1 Every week carry out a thorough visual inspection of all battery wiring taking particular note of the condition of inter connections between cells This maintenance should be carried out in conjunction with the battery manufacturers recommended maintenance Saf...

Страница 8: ...r be housed at least 15 metres from the home Check again to make sure that there are no appliances left ON the sequentially switch off appliances at the wall and by watching your night light as described in Handy Hint check to see if the LD550 24 returns to pulsing SLEEP mode after a 10 second delay Once you have found the offending appliance increase the sensitivity of the Demand Start see page 1...

Страница 9: ... Outside Australia New Zealand Product purchased for use outside Australia New Zealand must be returned to Selectronic Australia s Service Centre to enable warranty claims to be processed Freight cost to be borne by the customer No charge will be made for the product return LD550 24 Manual Selectronic Australia 16 Inverter Type Microprocessor control circuit with PWM full bridge power stage True s...

Страница 10: ...ay Drive Bayswater Victoria 3153 Australia Ph 03 9762 4822 Fax 03 9762 9646 service selectronic com au Burley TV Service Rainbow Power Company 278 Edmondson Ave 1 Alternative Way Austral Nimbin NSW 2171 NSW 2480 Australia Australia Ph 02 9606 0279 Ph 02 6689 1430 Fax 02 6689 1109 Reid Technology Ltd 3 5 Auburn Street Solar Inverter Services Takapuna 13 Thirteenth Ave North Shore City Sawtell Auckl...

Отзывы: