background image

EN

 I

MPORTANT 

N

OTICE

Attention! Improper installation or operation shall lead to serious accidents and damages! In order to perform proper installation and operation, all and any instructions shall 
absolutely be respected!
Before putting into operation, please read these Installation Manual carefully!
Any installation works, connections and settings, repairs and servicing of electronic commands discussed here shall only be performed by electricians qualified for heating 
techniques under strict respect of safety and security rules in force or detailed here.
The mechanic shall be liable to organise training for the end user (both orally and in writing) about the operation of equipment, on possible sources of risk and on routine checks 
to avoid eventual errors.
It is strictly prohibited to connect and set up electronic equipment under voltage because of risk of electric shock!
Electronic command is highly sensible to humidity, vapours and contaminations, which might even cause lasting malfunctions, too. The command is equipped with rubber stuffing 
boxes of IP 67 protection, which, in case of intended use, prevent intrusion of humidity, vapours or contaminations to the command.
Command panels located in the top and bottom of box are linked to each other by a multicore cable. You shall not leave the box cover hanging on this cable in any case! When 
installing, you shall provide a support to the box cover or have it removed by disconnecting the easily dismantling line terminals!
Improper putting into operation of product might cause a serious, eventually incurable error either in command or in sensors or in other complementary parts or in devices 
operated (radiator, fan etc.). 
The product is particularly ESD sensible (sensible for discharges caused by electro-static charge), for this reason, before touching the product, you shall proceed to electro-static 
discharging in any case.
Acknowledgement operations (deleting error messages of burner or radiator) can only be performed if visibility onto equipment is fully ensured, a workmanlike inspection 
completed professionally, nobody staying near to equipment and by putting the equipment into operation, no personal injury or material or property damage can occur.
Warning! We decline our liability for damages originating from non-respect of safety, installation or other instructions listed in these ’Instructions of Installation’ or of safety and 
security prescriptions actually in force! Non-compliance with these clauses might involve the expiry of guarantee!

The product may not be treated as household waste. Instead it shall be handed over to the applicable collection point. By ensuring of this product is disposed correctly, you
will help prevent potential negative consequences for the environment and human health. Recycling materials helps preserve resources of the earth.

 

T

YPE 

V

ARIANTS

EVO1

 heating controller unit for one zone

▪ FUNCTIONS:

▫ industrial temperature controller unit for several types of burners
▫ controlling of 1 zone
▫ easy to set up & work with via informative LCD and useful keyboard
▫ heating expenses stored for last 4 years in monthly split
▫ several acces levels to avoid unintentional adjustments

▪ INPUTS:

▫ 1 x emergency stop input(NC)
▫ 1 x fan safety relay input(NC)
▫ 1 x remote controller input(customizable)
▫ 2 x inner temperature sensor input(averaged)
▫ 1 x outter temperature sensor input

▪ OUTPUTS:

▫ 1 x fan output
▫ 1 x 2-staged burner output(with reset output & error signal input)
▫ 1 x global error message output

EVO2

 heating controller unit for two zones

▪ FUNCTIONS:

▫ industrial temperature controller unit for several types of burners
▫ controlling of 2 zones
▫ easy to set up & work with via informative LCD and useful keyboard
▫ heating expenses stored for last 4 years in monthly split
▫ several acces levels to avoid unintentional adjustments

▪ INPUTS:

▫ 1 x emergency stop input(NC)
▫ 2 x fan safety relay input(NC)
▫ 2 x remote controller input(customizable)
▫ 2 x inner temperature sensor input
▫ 1 x outter temperature sensor input

▪ OUTPUTS:

▫ 2 x fan output
▫ 2 x 2-staged burner output(with reset output & error signal input)
▫ 1 x global error message output

EVO3

 heating controller unit for three zones

▪ FUNCTIONS:

▫ industrial temperature controller unit for several types of burners
▫ controlling of 3 zones
▫ easy to set up & work with via informative LCD and useful keyboard
▫ heating expenses stored for last 4 years in monthly split
▫ several acces levels to avoid unintentional adjustments

▪ INPUTS:

▫ 1 x emergency stop input(NC)
▫ 3 x fan safety relay input(NC)
▫ 3 x remote controller input(customizable)
▫ 3 x inner temperature sensor input
▫ 1 x outter temperature sensor input

▪ OUTPUTS:

▫ 3 x fan output
▫ 3 x 1-staged burner output(with reset output & error signal input)
▫ 1 x global error message output

EVO4

 heating controller unit for four zones

▪ FUNCTIONS:

▫ industrial temperature controller unit for several types of burners
▫ controlling of 4 zones
▫ easy to set up & work with via informative LCD and useful keyboard
▫ heating expenses stored for last 4 years in monthly split
▫ several acces levels to avoid unintentional adjustments

▪ INPUTS:

▫ 1 x emergency stop input(NC)
▫ 4 x fan safety relay input(NC)
▫ 4 x remote controller input(customizable)
▫ 4 x inner temperature sensor input
▫ 1 x outter temperature sensor input

▪ OUTPUTS:

▫ 4 x fan output
▫ 4 x 1-staged burner output(with reset output & error signal input)
▫ 1 x global error message output

3

Содержание EVO1

Страница 1: ...lation Manual Important Notice 3 Type Variants 3 Frontpanel 4 Control Board 4 Connecting Power Up 5 Software Settings 8 Software Main Screen 8 Software Main Menu 9 Software Zone Menu 12 List of Parameters 15 Technical data 15 Index 16 ...

Страница 2: ...EVO SZUTM_A5B010AEN Fig 1 Fig 2 Fig 3 ...

Страница 3: ...all be handed over to the applicable collection point By ensuring of this product is disposed correctly you will help prevent potential negative consequences for the environment and human health Recycling materials helps preserve resources of the earth TYPE VARIANTS EVO1 heating controller unit for one zone FUNCTIONS industrial temperature controller unit for several types of burners controlling o...

Страница 4: ...connections can easily be performed by using dismantling terminal blocks and terminal block functions marked on panel by pictures if possible You shall not leave the box cover hanging on the flat multicore cable in any case When installing you shall provide a support to the box cover or have it removed by disconnecting the easily dismantling line terminals 1 TERMINAL BLOCKS see their detailed desc...

Страница 5: ... phase output switched by Stage1 relay in case of a single stage burner or radiator the phase wire of burner radiator shall be connected here in case of a double stage burner or radiator the phase wire of first stage of burner radiator shall be connected here Stage2 output phase output switched by Stage2 relay in case of a single stage burner or radiator it is not in use shall be left free in case...

Страница 6: ...en the possibility to use Optimisation heating up mode Connection of auxiliary panel You shall exclusively use auxiliary panels which being compatible with EVO control unit information thereof can be obtained in the description of complementary panel Insert complementary panel into 10 pin serial connector of control unit as shown in figure Fig 2 and check then correctness of connection Power up th...

Страница 7: ...EN 7 Fig 5C Connection of Terminal Blocks EVO3 Fig 5D Connection of Terminal Blocks EVO4 ...

Страница 8: ...idays during both optimisation heating up and overtime heating up the remaining duration will be displayed In case of manual mode the manual mode type selected will be displayed 4 INNER TEMPERATURE the temperature measured within zone will be displayed 5 OUTTER TEMPERATURE displays the temperature measured by outside heat sensor of system if mounted 6 KEY SYMBOL displays actual access level which ...

Страница 9: ...setting date time language etc which are not in close relationship with individual heating zones Zone settings can be performed from zone menu according to Chapter Zone menu The figure shows the structure of main menu system Fig 6 and accessibility of each setting The description of numbered menu points can be found below figure 9 Fig 6 Main Menu System page1 ...

Страница 10: ...ncy to display zone costs 8 ENERGY COST unit price of energy calculated from fuel price and specific heat EUR kWh Calculation for oil unit price of oil EUR kg caloric power MJ kg 3 6 MJ kWh Calculation for gas unit price of gas EUR m3 caloric power MJ m3 3 6 MJ kWh 9 LANGUAGE SELECTION setting of controller language 10 PC KEYBOARD setting the layout of PC keyboard to be connected 11 KEYBOARD BEEP ...

Страница 11: ... notofication there will be no alert when service date reached Message notification when service time reached an alert box will be opened periodically to alert to service needed Message sound notification when service time reached there is an acoustic sound together with opening alert box 18 OUTTER SENSOR setting whether an external thermal sensor connected to system or not 19 OUTTER SENSOR CORREC...

Страница 12: ...between zones without leaving menu which enables significantly quicker setting of zones or inspection zone settings Miscellaneous other general settings which are relating to controller unit or to the whole of heating system can be carried out in main menu according to Chapter Main menu The structure of zone menu system can be seen in figure Fig 7 together with accessibility of individual settings...

Страница 13: ...to consideration during which holiday temperature is permanently maintained When temperature optimisation function set night time temperature can earlier be changed against daytime temperature than set in weekly time program optimised heating up mode so as to reach daytime temperature in desired time In night time mode one hour of daytime temperature period can be requested by actuating push butto...

Страница 14: ...8 INNER SENSOR CORRECTION setting temperature correction caused by the location where internal heat sensor of zone installed the value set here shall be deducted added from to real temperature measured by heat sensor 9 HYSTERESIS setting switching hysteresis of burner radiator 1st stage hysteresis switching hysteresis of stage1 of burner radiator see fig 8 2nd stage delta T switching hysteresis of...

Страница 15: ...age 2 10 00 600 00 sec 14 tvondelay Delay time of fan start 0 00 10 00 sec 15 tvoffdelay Delay time of fan shut off 0 00 20 00 min 16 tvoffmin Minimal idle time of fan 10 00 600 00 sec 17 Burner power in stage 1 0 50 1000 00 kW 18 Total burner power 0 50 1000 00 kW 19 Correction of internal clock 22 20 22 20 sec day Table 1 List of Parameters TECHNICAL DATA Description of product EVO1 heating cont...

Страница 16: ...ard beep Language selection Mainmenu 9 Settings Language keyboard Language selection Login Mainmenu 23 Login Monthly costs Zonemenu 21 Zone info Costs Monthly costs Night temp Zonemenu 6 Settings Temperatures Night temp Notification Mainmenu 17 Service menu Servicing datas Next servicing Notification Outter sensor Mainmenu 18 Service menu Misc settings Outter sensor Outter sensor correction Mainme...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Отзывы: