Selcon PRG-SE-C O1 Series Скачать руководство пользователя страница 2

PROGRAMMER FOR START, FLAME SUPERVISION  

AND SAFE STOP OF BURNER 

PRODUCT:

 

PRG-SE-C -O1

                                      

TECHNICAL SHEET 2/6 

  

 Costumer Service 55 11 3019-1616

                                

For further details see technical bulletin

 

 

SELCON

 

S

ISTEMAS  

E

LETRÔNICOS DE 

C

ONTROLE 

L

TDA

.

 

CNPJ 56.935.877/0001-29 

Street Américo Samarone, 502 • CEP 04284-000 • Moi-
nho Velho •   São Paulo • SP • Tel/Fax: 

(55 11) 3019-1616 

http://www.selcon.com.br 

 

 

 

2/6 

  

SELCON

 

 

Automação Industrial

 

Selcon Ltda., keeps the right to modify this technical sheet  

when never it is necessary

 

February/10

 

 

Representative or Distributor 

 

 

Minimum current flame: 2 microamperes dc (uA) 

NOTE:  The  cable  of  flame  sensor  must  be  installed  separately  from  other 

cables that are part of the command set of the burner. The best type of cable 

recommended for this purpose is used for ignition.           

 

  Protection against short circuit failure sensor ionization for mass. 

 

  Blocking with local signaling (LED) and remote (contact N.O.) 

 

   

With verification of premature flame or false flame signal, before starting the burner. 

 

Purge Time: 0, 10 or 20 seconds (see field code for request) 

 

Time of ignition: 6 sec. 

 

Time of ignition: 6 sec. 

 

  Time to confirm the signal of flame: 

<

1 sec. 

 

  Time of answer to the flame flaw: 

<

 4 seg. 

 

  

Signaling LED (

S

): power-purge (

LJ

) / VS FUEL (

VD

) / ALARM (

VM

).

 

 

Maximum current per output command (

TI

VS

 and 

AL

): 2 A in 250 Vac (resistive).

 

 

Electric connections: through socket of fast extraction polarized (see figure below).  

 

Expected electrical life of output contacts:

>

 100,000 operations. 

 

Expected mechanical life of output contacts:

>

 10,000,000 operations. 

 

Reset (

R

), through the interruption and return of the supply in the programmer. 

 

Degree of environmental protection: IP 55 (except connector of fast extraction - IP 50) 

 

Cabinet: box ABS black color  

 

Mounting: On a flat surface protected 

 

  Mounting: Through 2 screws mounted on the ears to fix of box.  

 

Weight : 180 grams 

 

Warranty: 6 months 

(see the guarantee)

 

 

Отзывы: