Selco C6200 FlexGen Скачать руководство пользователя страница 19

Selco

C6200 FlexGen

Revision: 03-06-2014

Page 19 of 24

5.8.6

Dead Bus lock

The dead bus lock signal is used to prevent more than one generator from connect simultaneously to
a dead bus bar (e.g. in a blackout situation).

The Dead Bus Lock signal (terminal 46) must be interconnected between all C6200 FlexGen
modules that operates generator connecting to the same busbar.

Wiring of Dead bus Lock signal

5.9 Relays

5.9.1

C/B Close

The C/B close relay is a change-over relay intended for control (Closure) of the generator circuit
breaker. The C/B close relay has two contact sets and is normally de-energized by default. Note that
this relay can be reconfigured to normally energized operation.

Terminal

Signal

Description

47

Relay de-energized position

Breaker remote close

48

Relay contact

Signal source

49

Relay energized position

Breaker remote close

5.9.2

Protection Trip

The protection trip relay is a change-over relay intended for tripping the circuit breaker in case of a
protection fault (e.g. over-curremt or reverse power). The built-in protection trip relay has two
contact sets and is normally energized by default. Note that the protection trip relay can be
reconfigured to normally energized operation.

Terminal

Signal

Description

50

Relay de-energized position

Breaker remote trip

51

Relay contact

Signal source

52

Relay energized position

Breaker remote trip

The protection trip relay connects to the remote trip input of the generator circuit breaker.
Terminals 50 and 52 are typically not connected at the same time. Only one of these signals is taken
to the breaker, depending on whether the Protection Trip relay is configured for normally energized
or de-energized operation.

Содержание C6200 FlexGen

Страница 1: ...C6200 FlexGen Generator Controller Installation Manual 4560 River Bottom Drive Norcross GA 30092 P 1 770 455 9110 W SELCOUSA com...

Страница 2: ...ts 12 5 5 Analogue Inputs 14 5 5 1 Voltage Input 14 5 5 2 Frequency Input 14 5 6 Parallel Lines 15 5 7 GOV AVR Control 16 5 8 Inputs 18 5 8 1 C B 18 5 8 2 Manual 18 5 8 3 Unload 18 5 8 4 Reset 18 5 8...

Страница 3: ...on check and automatic synchronisation voltage matching active and reactive load sharing basic and programmable I O and data acquisition The Littelfuse Selco C6200 FlexGen can operate in parallel with...

Страница 4: ...Selco C6200 FlexGen Revision 03 06 2014 Page 4 of 24 2 Front View...

Страница 5: ...f the switch board using four 5 mm screws DIN rail mounting is not advisable due to the weight Please ensure that enough space is given around the module so that the plug in terminals can be removed a...

Страница 6: ...vessels hull is considered as ground Connecting any of the COM connections on the C6200 FlexGen to ground hull or switchboard chassis may cause electrical noise to be injected into the system The gene...

Страница 7: ...vide a nominal voltage of 24 V DC The C6200 FlexGen will tolerate relatively wide variations in the supply voltage please refer to the specifications The supply is connected to terminal 30 and 32 of t...

Страница 8: ...The generator should be stopped and blocked against starting the busbar should be dead Also make sure that there is no risk of another power source being connected to the busbar while you are working...

Страница 9: ...ltage Generator phase L2 7 AC voltage Generator phase L3 The BUSBAR VOLTAGE LED shows by steady light whether the voltage levels measured between the phases are within limits The reference is the nomi...

Страница 10: ...s are isolated by e g transformers inside the third party equipment The CT ratio should cover the maximum current of the generator The CTs must be capable of coping with limited time short circuit cur...

Страница 11: ...a connection between S1 and S2 before you disconnect the CT cables from the GENERATOR CURRENT terminals Please note that incorrect connection of the current transformers e g by reversing the terminals...

Страница 12: ...lexGen Configuration Manual Terminal Signal Description 15 NO contact to COM Programmable input 1 16 NO contact to COM Programmable input 2 17 NO contact to COM Programmable input 3 18 NO contact to C...

Страница 13: ...lco C6200 FlexGen Revision 03 06 2014 Page 13 of 24 Programmable inputs and outputs used for control of conventional speed governor Programmable inputs and outputs used for load depending start and st...

Страница 14: ...nected to terminal 32 Supply minus In rare situations gound loops can cause noise to be injected into the application Ground loops happen when multiple COM connections between modules e g parallel ope...

Страница 15: ...ignal Description 27 DC voltage kW BALANCE of other FLEXGEN modules 28 Common reference COM of the other FLEXGEN modules 29 DC voltage kVAr BALANCE of other FLEXGEN modules Please note that terminal 2...

Страница 16: ...current input 36 DC voltage Governor voltage input 37 reference isolated AVR reference 38 PWM signal AVR PWM input 39 DC current AVR current input 40 DC voltage AVR voltage input It is important to n...

Страница 17: ...7 of 24 C6200 FlexGen controlling electronic speed governor by a DC voltage C6200 FlexGen controlling ECU by a PWM signal Note that the amplitude of the PWM signal is determined by the configuration o...

Страница 18: ...perational situation of the system 5 8 2 Manual Activating the manual input will prevent the C6200 FlexGen from interfering with the speed and voltage controls of the generator unless it gets a comman...

Страница 19: ...on Breaker remote close 48 Relay contact Signal source 49 Relay energized position Breaker remote close 5 9 2 Protection Trip The protection trip relay is a change over relay intended for tripping the...

Страница 20: ...inal 64 REF The outputs are used for indication and control of external equipments e g common alarms or speed voltage control relay pulses Terminal Signal Description 56 Normally open relay output Pro...

Страница 21: ...n applies between the output resistor and the internal resistance of the driven equipment Example equipment with an internal resistance of only 10 k would reduce a 10 VDC output voltage to 5 VDC The t...

Страница 22: ...toggeling DIP switch 5 to ON position The termination resistor must be enabled only on the first and on the last unit on the RS485 bus The maximum cable length for RS485 is 1 000 meters The cable must...

Страница 23: ...23 AWG22 Cable resistance should be less than 26 m per meter The first and the last module on the CANbus need a termination resistor 150 between lines A and B It is not necessary to connect external r...

Страница 24: ...mbient temp range 20 C 70 C Vibration IEC 60068 2 6 Humidity IEC 60068 2 30 EMC IEC 61000 4 3 2006 IEC 61000 4 6 2004 IEC 61000 4 5 2005 IACS E10 2006 Test No 15 CISPR 16 1 1999 CISPR 16 2 2002 Relay...

Отзывы: