2.8
SEL-DTA2 Instruction Manual
Date Code 20020329
Specifications
Rear Panel Connections and Configurations
Each output channel is independently programmable with output quantity
(Vab, Ia, Fault Location, etc.) and range.
Contact Outputs
The rear panel has six relay contact outputs (A1–A6). These outputs indicate
fault conditions and acknowledge reset commands. An additional relay
contact indicates self-test failure or other alarm conditions. All contact outputs
are dedicated and not programmable.
shows contact assignments
and signal descriptions.
Table 2.1
Adapter Board Signal Assignments
Signal Description
Pin
Voltage output 1
Ground 1
Current output 1
13
25
12
Voltage output 2
Ground 2
Current output 2
11
24
10
Voltage output 3
Ground 3
Current output 3
9
23
8
Voltage output 4
Ground 4
Current output 4
7
22
6
Voltage output 5
Ground 5
Current output 5
5
21
4
Voltage output 6
Ground 6
Current output 6
3
20
2
Voltage output 7
Ground 7
Current output 7
1
19
14
Voltage output 8
Ground 8
Current output 8
15
18
16
Table 2.2
Contact Assignments and Signal Descriptions
(Sheet 1 of 2)
Terminal
Block
Terminal
Block
Positions
Standard
Contact
Arrangement
a
Signal
Description
POWER
1,2,3
N/A
+,–,GND
AC/DC power to unit.
IS01
4,5
N/A
RESET
Clears analog channels
indicating fault location, and
clears contacts A1–A5.
A1
6,7
a
A
The current fault involves Phase
A.
A2
8,9
a
B
The current fault involves Phase
B.
A3
10,11
a
C
The current fault involves Phase
C.
A4
12,13
a
G
The current fault involves
ground.
A5
14,15
a
FAULT
A fault has occurred.