![Sel SEL-421 Скачать руководство пользователя страница 249](http://html1.mh-extra.com/html/sel/sel-421/sel-421_user-manual_1236405249.webp)
U.6.9
Date Code 20020501
User’s Guide
SEL-421/SEL-421-1 Relay
Testing and Troubleshooting
Relay Test Connections
Relay Test Connections
NOTE:
The procedures specified in
this subsection are for initial relay
testing only. Follow your company
policy for connecting the relay to the
power system.
The SEL-421 Relay is a flexible tool that you can use to implement many
protection and control schemes. Although you can connect the relay to the
power system in many ways, connecting basic bench test sources helps you
model and understand more complex relay field connection schemes.
Test Setup
Test Source Connections
For each relay element test, you must apply ac voltage and current signals to
the relay. The text and figures in this subsection describe the test source
connections you need for relay protection element checks. You can use these
connections to test protective elements and simulate all fault types.
Connections for Three Voltage Sources and Three Current Sources
shows the connections to use when you have three voltage sources
and three current sources available.
Figure 6.2
Test Connections Using Three Voltage and Three Current
Sources.
Three-Phase
Voltage and Current
Test Sources
IA
VB
IB
VC
IC
VA
IAW
Z01
Z02
Z03
Z04
Z05
Z06
Z13
Z14
Z15
Z16
Z17
Z18
IBW
ICW
VAY
VBY
VCY
Relay Rear-Panel Analog
Voltage and Current Inputs
Содержание SEL-421
Страница 8: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 110: ...This page intentionally left blank ...
Страница 204: ...This page intentionally left blank ...
Страница 284: ...This page intentionally left blank ...
Страница 286: ...This page intentionally left blank ...