Sel SEL-2725 Скачать руководство пользователя страница 1

Schweitzer Engineering Laboratories, Inc.

SEL-2725 Data Sheet

                    

Features and Benefits

The SEL-2725 is an unmanaged five-port Ethernet switch and copper-to-fiber media converter. Single- or multimode 
fiber optics are available to accommodate a wide range of utility and industrial applications. The environmental specifi-
cations exceed the requirements of IEEE 1613 Class 2 and IEC 61850-3, making it suitable for operation in harsh envi-
ronments, such as electric utility substations or industrial plants.

Easy Installation.

 The SEL-2725 has no settings. Copper ports autoconfigure for crossover cables, autospeed 

detects for 10 or 100 Mbps links, and automatically detects half- or full-duplex operation.

Reliable Power Supply.

 10–275 Vdc power supplies exceed all harsh environmental standards along with a 

3,000 year MTBF.

Robust Performance.

 Operates above the required temperature range (–40° to +85°C). Exceeds the requirements 

of IEEE 1613 and IEC 61850-3.

Use as a multiport media converter to connect Ethernet 10/100BASE-T devices to one location or equipment rack. Use 
the 100BASE-FX multimode or 100BASE-LX10 single-mode fiber-optic port options to interconnect devices with the 
central or managed Ethernet switch. Keeping the electrical connections short and localized greatly reduces the possibil-
ity of induced noise.

SEL-2725 Unmanaged Ethernet Switch

Содержание SEL-2725

Страница 1: ...for crossover cables autospeed detects for 10 or 100 Mbps links and automatically detects half or full duplex operation Reliable Power Supply 10 275 Vdc power supplies exceed all harsh environmental...

Страница 2: ...supplied packaging and must be kept between 40 degrees to 176 degrees Fahrenheit Protective Ground Use 1 5 mm2 16 AWG wire or heavier to connect to the Protective Ground terminal Disconnect Device Dis...

Страница 3: ...rol Address Table 1000 MAC addresses RJ45 Ports Recommended Cable Category 5 e Shielded Twisted Pair Cable STP SEL C627 Autonegotiation 10 or 100 Mbps full or half duplex and MDI MDI X crossover Fiber...

Страница 4: ...pply Reverse Polarity and Slow Ramp IEC 60255 27 2013 Radiated RF Immunity IEC 60255 26 2013 IEC 61000 4 3 206 A1 2007 A2 2010 Severity Level 10 V m unmodulated 80 MHz 1 GHz 1 4 GHz 2 7 GHz IEEE C37 9...

Страница 5: ...of any protective conductor connection must be checked before carrying out any other actions It is the responsibility of the user to ensure that the equipment is installed operated and used for its i...

Страница 6: ...NT Ne pas appliquer une proc dure ou un ajustement qui n est pas d crit explicitement dans ce manuel d instruction WARNING During installation maintenance or testing of the optical ports use only test...

Страница 7: ...he responsibility of the user to ensure that the equipment is installed operated and used for its intended function and in the manner this manual specifies The equipment should not be serviced If this...

Страница 8: ...nternational copyright and patent laws in its products including without lim itation software firmware and documentation The information in this document is provided for informational use only and is...

Отзывы: