SEL-2414
Data Sheet
Schweitzer Engineering Laboratories, Inc.
16
Optional Communications Card
Standard EIA-232 or EIA
-
485 (ordering option)
Data Speed:
300–38400 bps
Communications Protocols
Modbus RTU slave or Modbus TCP
DNP3 Level 2 Outstation (LAN/WAN and Serial)
IEC 61850 Communications
Ethernet FTP
Telnet
SEL M
IRRORED
B
ITS
(MBA, MBB, MB8A, MB8B, MBTB)
Ymodem file transfer on the front and rear port
Xmodem file transfer on the front port
SEL ASCII and Compressed ASCII
SEL Fast Meter
SEL Fast Operate
SEL Fast SER
SEL Fast Message unsolicited write
SEL Fast Message read request
SEL Event Messenger Points
Maximum Concurrent Connections
Modbus Slave:
1
DNP3 Level 2 Outstation: 3
a
Ethernet FTP:
2
Telnet:
2
a
Maximum in any combination of serial and/or LAN/WAN links.
Power Supply
Rated Supply Voltage
Low-Voltage Model:
24/48 Vdc
High-Voltage Model:
110/250 Vdc
110/230 Vac, 50/60 Hz
Input Voltage Range
Low-Voltage Model:
19.2–60 Vdc
High-Voltage Model:
85–275 Vdc
85–264 Vac
Power Consumption
AC:
< 40 VA
DC:
<15 W
Interruptions
Low-Voltage Model:
10 ms @ 24 Vdc
50 ms @ 48 Vdc
High-Voltage Model:
50 ms @ 125 Vac/Vdc
100 ms @ 250 Vac/Vdc
AC Metering Accuracies
Current
Phase Current:
±0.5% typical, 25°C, 60 Hz, nominal
current
Neutral Current:
±0.5% typical, 25°C, 60 Hz, nominal
current
Negative Sequence (3I2): ±0.5% typical, 25°C, 60 Hz, nominal
current (calculated)
Residual Ground
Current:
±0.5% typical, 25°C, 60 Hz, nominal
current (calculated)
Voltage
Line-to-Neutral Voltage: ±0.08% typical, 25°C, 60 Hz, nominal
voltage
Line-to-Line Voltage:
±0.08% typical, 25°C, 60 Hz, nominal
voltage
Negative-Sequence
(3V2):
±0.5% typical, 25°C, 60 Hz, nominal
voltage (calculated)
Power
Three-Phase Real Power
(kW):
±1% typical, 25°C, 60 Hz, nominal
voltage and current with 0.10 to 1.00
power factor
Three-Phase Reactive
Power (kVAR):
±1% typical, 25°C, 60 Hz, nominal
voltage and current with 0.00 to 0.90
power factor
Three-Phase Apparent
Power (kVA):
±1% typical, 25°C, 60 Hz, nominal
voltage and current
Power Factor
Three-Phase
(wye connected):
±1% typical, 25°C, 60 Hz, nominal
voltage and current (between 0.97
and 1)
Sampling and Processing Specifications
Without Voltage Card or Current Card
Analog Inputs
Sampling Rate:
Every 4 ms
Digital Inputs
Sampling Rate:
2 kHz
Contact Outputs
Refresh Rate:
2 kHz
Logic Update:
Every 4 ms
Analog Outputs
Refresh Rate:
Every 4 ms
New Value:
Every 100 ms
Timer Accuracy:
± 0.5% of settings and ±4 ms
With Either Voltage Card, Current Card, or
Both Voltage and Current Cards
Analog Inputs
Sampling Rate:
4 times/cycle
Digital Inputs
Sampling Rate:
32 times/cycle
Contact Outputs
Refresh Rate:
32 times/cycle
Logic Update:
4 times/cycle
Analog Outputs
Refresh Rate:
4 times/cycle
New Value:
Every 100 ms
Timer Accuracy:
±0.5% of settings and ±1/4 cycle
Processing Specifications
AC Voltage and
Current Inputs:
16 samples per power system cycle
Frequency Tracking
Range:
44–66 Hz
Digital Filtering:
Cycle cosine after low-pass analog
filtering. Net filtering (analog plus
digital) rejects dc and all harmonics
greater than the fundamental.
Control Processing:
Four times per power system cycle or 4
ms if no current or voltage card
(except for math variables and analog
signals used in logic, which are
processed every 100 ms)