background image

Schweitzer Engineering Laboratories, Inc.

SEL-2414

 

Data Sheet

SEL-2414 Transformer Monitor

Complete System for Control and Monitoring

Major Features and Benefits

The SEL-2414 Transformer Monitor provides an exceptional combination of monitoring, control, and communications
in a compact package.

Thermal Monitoring and Metering Capabilities.

 Safeguard transformers from overheating by tracking thermal

conditions. Track the minimum and maximum transformer top oil temperature, hot-spot temperature, and as many

as  10  RTDs  or  thermocouples.  Calculate  hot-spot  temperature  according  to  the  IEEE C57.91-2011  or  the

IEC 60076-7:2018 Ed. 2 standards.

Load Tap Position and Control Monitoring.

 Monitor tap position and raise and lower controls and as many as

32 tap positions by using digital inputs in the binary-coded decimal (BCD) or binary format.

High Reliability, Rugged Design, and Low Price.

 Apply the SEL-2414 in harsh physical and electrical environ-

ments. The SEL-2414 withstands vibration, electrical surges, fast transients, extreme operating temperatures from

–40° to +85°C, and meets stringent utility standards. Compare our superior specification compliance, higher reli-

ability, lower price, and worldwide, ten-year warranty to other transformer monitor alternatives.

Flexible I/O for Transformer Status, Alarms, and More.

 Take advantage of input/output options including dig-

ital inputs for status such as oil level and sudden pressure; RTD and thermocouple inputs for measurements such as

ambient, top-oil, and hot-spot temperatures; digital outputs for control and alarms; analog inputs and outputs; and

ac current and voltage inputs. Easily program monitoring and control functions with powerful logic, math, timers,

counters, and edge-trigger functions. These features allow easy integration with new and retrofit transformer mon-

itor  applications.  Monitor  critical  substation  assets  with  comprehensive  transformer  thermal  and  through-fault

monitoring.

Содержание SEL-2414

Страница 1: ...n and Low Price Apply the SEL 2414 in harsh physical and electrical environ ments The SEL 2414 withstands vibration electrical surges fast transients extreme operating temperatures from 40 to 85 C and...

Страница 2: ...guration access and displays settings measurements and calculated values Easily set with ACSELERATOR QuickSet SEL 5030 Soft ware Product Summary The SEL 2414 Transformer Monitor withstands harsh physi...

Страница 3: ...cumulation Alarm Top Oil Alarm Hot Spot Alarm OLTC Oil Differential Alarm Pressure Vacuum Alarm Pressure Relief Alarm Cooling Alarm Load Voltage 3 for 1 Load Current 3 for 1 OLTC Tank Oil Sensors Pres...

Страница 4: ...s For a 50 Hz system the report lengths are 0 30 s and 1 28 s Figure 4 Example SYNCHROWAVE Event Waveform Plot Trend Transformer Temperatures and Other Analog Inputs Record measured ambient transform...

Страница 5: ...lation aging acceleration factor FAA and loss of life quantities Use the thermal element to indicate alarm conditions and or activate control actions when one or more of the following exceed settable...

Страница 6: ...fy Your Transformer Commissioning The SEL 2414 front panel simplifies commissioning and troubleshooting View field data and calculated values Diagnose data flow problems in seconds instead of hours Dr...

Страница 7: ...ettings using a simple PC com munications link Analyze event records with the integrated wave form and harmonic analysis tool Use the PC interface to remotely retrieve reports and other system data Mo...

Страница 8: ...nd Real Power Demand and Peak Demand IA IB IC IG 3I2 Analog Input AIx01 AIx08 Math Variable MV01 MV32 Remote Analog RA001 RA128 Analog Signal Profiling Optional Temperature and thermal with the extern...

Страница 9: ...panel lights with 32 pro grammable displays Define custom messages e g Fan On Fan Off to report transformer or device conditions on the front panel display Use advanced SELOGIC con trol equations to c...

Страница 10: ...61850 Ethernet Switch DCS or SCADA Master EIA 485 Modbus RTU DNP3 Level 2 Slave DCS or SCADA Master A Ethernet Communications Architecture B EIA 485 Communications Architecture SEL 2414 SEL 2414 SEL 2...

Страница 11: ...Figure 11 Front Panel With Default Configurable Labels Figure 12 Rear Panel Connections and Labels Expansion Slots Slot C Slot E Slot Z Slot D Power Supply 2 DI 3 DO Ethernet Fiber Optic IRIG B EIA 2...

Страница 12: ...SEL 2414 Data Sheet Schweitzer Engineering Laboratories Inc 12 Dimensions Figure 13 SEL 2414 Panel Mount Figure 14 SEL 2414 Surface Mount Dimensions...

Страница 13: ...A according to IEC 60255 5 60664 1 Note This is a linearity specification and is not meant to imply continuous operation Continuous Thermal Rating 15 A 3 A according to IEC 60255 6 IEEE C37 90 1989 1...

Страница 14: ...latinum PT100 100 nickel NI100 120 nickel NI120 10 copper CU10 J K T E Measuring Range RTDs PT100 200 to 850 C NI100 80 to 250 C CU10 200 to 250 C 0 5 10 15 20 25 30 35 40 45 50 55 0 5 10 15 20 25 30...

Страница 15: ...ing 3600 VA cos 0 3 Electrical Durability Break VA Rating 360 VA cos 0 3 Fast Hybrid high speed high current interrupting Make 30 A Carry 6 A continuous carry at 70 C 4 A continuous carry at 85 C 1 s...

Страница 16: ...oltage Line to Line Voltage 0 08 typical 25 C 60 Hz nominal voltage Negative Sequence 3V2 0 5 typical 25 C 60 Hz nominal voltage calculated Power Three Phase Real Power kW 1 typical 25 C 60 Hz nominal...

Страница 17: ...ty Electrostatic Discharge Immunity IEC 60255 22 2 2008 IEC 61000 4 2 2008 Severity Level 4 8 kV contact discharge 15 kV air discharge Radiated RF Immunity IEC 60255 22 3 2007 IEC 61000 4 3 2010 10 V...

Страница 18: ...ppreciate your interest in SEL products and services If you have questions or comments please contact us at Schweitzer Engineering Laboratories Inc 2350 NE Hopkins Court Pullman WA 99163 5603 U S A Te...

Страница 19: ...Schweitzer Engineering Laboratories Inc SEL 2414 Data Sheet 19 Notes...

Страница 20: ...and international copyright and patent laws in its products including without limitation software firmware and documentation The information in this document is provided for informational use only and...

Отзывы: