Sel SEL-2243 Скачать руководство пользователя страница 4

4

© 2011–2018 by Schweitzer Engineering Laboratories, Inc. All rights reserved.

All brand or product names appearing in this document are the trademark or registered
trademark of their respective holders. No SEL trademarks may be used without written
permission. SEL products appearing in this document may be covered by U.S. and Foreign
patents.

Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded under
federal and international copyright and patent laws in its products, including without lim-
itation software, firmware, and documentation.

The information in this document is provided for informational use only and is subject to
change without notice. Schweitzer Engineering Laboratories, Inc. has approved only the
English language document.

This product is covered by the standard SEL 10-year warranty. For warranty details, visit
selinc.com or contact your customer service representative.

EtherCAT

®

is registered trademark and patented technology, licensed by Beckhoff 

Automation GmbH, Germany.

                    

*PDS2243-01*

2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A.

Tel: +1.509.332.1890 • Fax: +1.509.332.7990

selinc.com • [email protected]

SEL-2243 Data Sheet

Date Code 20180629

Redundant Installation

Each node may have one or two SEL-2243 modules installed. When 

two are used, they operate in load sharing mode.

Type Tests

Communication Product Testing

IEEE 1613-2009 + A1-2011 Performance Class 1

Environmental Tests

Enclosure Protection:

IEC 60529:2001 + CRGD:2003
IP3X excluding the terminal blocks

Vibration Resistance:

IEC 60255-21-1:1988

Vibration Endurance, Severity: Class 2
Vibration Response, Severity: Class 1

Shock Resistance:

IEC 60255-21-2:1988

Bump Test, Severity: Class 1
Shock Withstand, Severity: Class 1
Shock Response, Severity: Class 1

Seismic:

IEC 60255-21-3:1993

Quake Response, Severity: Class 1

Cold:

IEC 60068-2-1:2007

–40°C, 16 hours

Dry Heat:

IEC 60068-2-2:2007

+85°C, 16 hours

Damp Heat, Cyclic:

IEC 60068-2-30:2005

25°C to 55°C, 6 cycles,
95% relative humidity

Dielectric Strength and Impulse Tests

Impulse:

IEC 60255-5:2000 

Severity Level: 0.5 Joule, 5 kV

IEEE C37.90-2005 

Severity Level: 0.5 Joule, 5 kV

Dielectric (HiPot):

IEC 60255-5:2000 

Severity Level: 3100 Vdc on power 

supply for 1 minute

IEEE C37.90-2005

Severity Level: 3100 Vdc on power 

supply for 1 minute

Insulation:

IEC 60255-5:2000 

Severity Level: 500 V for greater than 
1 minute

RFI and Interference Tests

EMC Immunity

Electrostatic Discharge 

Immunity:

IEEE C37.90.3-2001
IEC 60255-22-2:2008
IEC 61000-4-2:2008 

Severity Level: 4
8 kV contact discharge
15 kV air discharge

Radiated RF Immunity:

IEEE C37.90.2-2004 

Severity Level: 35 V/m

IEC 61000-4-3:2010

Severity Level: 10 V/m

IEC 60255-22-3:2007

Severity Level: 10 V/m

Digital Radio Telephone 

RF Immunity:

ENV 50204:1995 Severity Level: 10 V/m 

at 900 MHz and 1.89 GHz

Conducted RF Immunity: IEC 60255-22-6:2001 

Severity Level: 10 Vrms

IEC 61000-4-6:2008

Severity Level: 10 Vrms

Surge Immunity:

IEC 60255-22-5:2008 

Severity Level: 1 kV Line to Line, 
2 kV Line-to-Earth

IEC 61000-4-5:2005

Severity Level: 1 kV Line to Line, 
2 kV Line-to-Earth

Fast Transient, Burst 

Immunity:

IEC 60255-22-4:2008 

Severity Level: Class A: 4 kV, 5 kHz;
2 kV, 5 kHz on communications ports

IEC 61000-4-4:2011

Severity  Level:  4 kV,  5 kHz

Power Supply Immunity: IEC 61000-4-11:2004 

IEC 61000-4-29:2000 
IEC 60255-11:2008

Magnetic Field 

Immunity:

IEC 61000-4-8:2009 

Severity Level: 1000 A/m for 3 seconds, 
100 A/m for 1 minute

IEC 61000-4-10:2001 
   Severity Level: 100 A/m

Surge Withstand 

Capability Immunity:

IEEE C37.90.1-2002, 

2.5 kV oscillatory, 4 kV fast transient 

IEC 60255-22-1:2007 

2.5 kV common-mode 
1.0 kV differential-mode (cable length 
< 2 m for RJ45 power couplers)

Oscillatory Waves 

Immunity:

IEC 61000-4-12:2006 

Ring Wave: 2 kV common, 
1.0 kV differential 
Oscillatory: 2.5 kV common, 
1.0 kV differential

Common Mode 

Disturbance Immunity:

IEC 61000-4-16:2002 

Frequency: 0 to 150 Hz 
Severity: Level 4, segment 4: 30 Vrms 
open-circuit, 15 to 150 kHz

Emissions

Radiated and Conducted 

Emissions:

IEC 60255-25:2000 

Содержание SEL-2243

Страница 1: ...power couplers in a node both modules actively share load and provide the necessary power for node functions If one SEL 2243 becomes unavailable there is zero switching delay or power loss to the node EtherCAT Operation Each SEL 2243 provides two dedicated ports for Ether CAT networks The ports will either be standard 10 100BASE T or optional 100BASE FX Ethernet ports EtherCAT is a real time field...

Страница 2: ...pacitors should be safely discharged during decommissioning The power terminals on the high voltage power coupler 1 H and 2 N must connect to 120 240 Vac with the proper polarity or to 125 250 Vdc The power terminals on the low voltage power coupler 1 H and 2 N must connect to 24 48 Vdc The power terminals are isolated from the chassis ground Use 16 14 AWG 1 5 2 5 mm2 wire of sufficient current ca...

Страница 3: ...te Not applicable to UL applications Operating Environment Pollution Degree 2 Overvoltage Category II Insulation Class 1 Relative Humidity 5 95 noncondensing Maximum Altitude 2000 m EtherCAT Ports Ports 2 Data Rate Automatic Connector RJ45 Female or LC Fiber Protocols Dedicated EtherCAT Fiber Optic Ports Class 1 LASER LED Wavelength 1300 nm Optical Connector Type LC Multimode Option Link Budget 11...

Страница 4: ...rs Damp Heat Cyclic IEC 60068 2 30 2005 25 C to 55 C 6 cycles 95 relative humidity Dielectric Strength and Impulse Tests Impulse IEC 60255 5 2000 Severity Level 0 5 Joule 5 kV IEEE C37 90 2005 Severity Level 0 5 Joule 5 kV Dielectric HiPot IEC 60255 5 2000 Severity Level 3100 Vdc on power supply for 1 minute IEEE C37 90 2005 Severity Level 3100 Vdc on power supply for 1 minute Insulation IEC 60255...

Отзывы: