background image

SEL-2241 Data Sheet

Schweitzer Engineering Laboratories, Inc.

2

Figure 3

Final Module Alignment

Connections

Communications Ports

NOTE:

 Never connect two RTACs via USB to one PC.

All web access, settings changes, and ODBC connec-
tions use either the RTAC Ethernet ports or the front
USB type B port. Until you have configured the Ethernet
interfaces on the RTAC, you will need to use the supplied
USB type B cable to access the RTAC web interface. The

AC

SEL

ERATOR

 RTAC installation will place the required

USB driver on your PC so that you can allow Windows
to install the driver automatically when it detects the
USB connection. Plug the USB cable into the RTAC and
into your PC. If you receive a prompt to connect to Win-
dows Update, select 

No, not at this time

 and press 

Next

.

Then use the Windows Device Installation Wizard and
follow the automatic install prompts to install the SEL
USB driver.

After completing this step, you can use IP address
172.29.131.1 to access the RTAC web interface through
the USB cable. See 

Section 7: Security and Account

Management 

in the 

AC

SEL

ERATOR

 RTAC SEL-5033

Instruction Manual

 for RTAC web password setup.

The SEL-2241 has four nonisolated serial ports. You can
select all RTAC serial ports through software to be either
EIA

-

232 or EIA

-

485/EIA

-

422. You can configure any

serial protocol on the RTAC to use any of these serial
ports. See 

Table 1

 for the pinout of the RTAC serial ports.

Table 1

Nonisolated Female DB

-

9 Ports 

EIA

-

232

EIA

-

485/EIA

-

422

Pin 1: N/C or +5 Vdc (also 
DCD input on COM 1 if 
+5 Vdc is disabled)

Pin 1: N/C or +5 Vdc (also 
DCD input on COM 1 if 
+5 Vdc is disabled)

Pin 2: RXD

Pin 2: -RXD

Pin 3: TXD

Pin 3: -TXD

Pin 4: +IRIG-B (DTR jumper 
option for COM 1)

Pin 4: +IRIG-B

Pin 5: GND

Pin 5: GND

Pin 6: -IRIG-B (DSR jumper 
option for COM 1)

Pin 6: –IRIG-B

Pin 7: RTS

Pin 7: +TXD

Pin 8: CTS

Pin 8: +RXD

Pin 9: GND

Pin 9: GND

Table 2

Port Characteristics 

Port

Port Interface

Cables

USB B 

USB Type B to USB 
Type A

SEL-C664

ETH 1 

and 

ETH 2

10/100BASE-T (RJ45 
for Copper)

SEL-C627

COM 1—COM 4 (serial)

EIA

-

232 (Nonisolated)

SEL-C234A, 
SEL-273A, and 
SEL-C387 are 
popular selec-
tions

IRIG

-

B

 

IN

put

Female BNC

SEL-C953

IRIG

-

B

 

OUT

put

Female BNC

SEL-C953

Содержание SEL-2241

Страница 1: ...2242 chassis backplane has ten slots labeled A through J Only Slot A supports the SEL 2241 RTAC module To install the RTAC tip the top of the module away from the chassis align the notch on the bottom...

Страница 2: ...eb interface through the USB cable See Section 7 Security and Account Management in the ACSELERATOR RTAC SEL 5033 Instruction Manual for RTAC web password setup The SEL 2241 has four nonisolated seria...

Страница 3: ...ection 1 Getting Started in the SEL 5033 Instruction Manual for instructions on how to back up and restore RTAC projects Step 2 De energize any power source connected to the power coupler s in the Axi...

Страница 4: ...ection 3 Factory Reset in the SEL 2240 Instruction Manual describes Table 3 shows the configurable jumper positions SEL 2241 Disassembly To disassemble the SEL 2241 RTAC perform the fol lowing steps S...

Страница 5: ...EtherNet IP Explicit Message Client Server DNP3 Serial DNP3 LAN WAN Modbus RTU Modbus TCP SEL Fast Messaging LG 8979 SES 92 IEEE C37 118 IEC 61850 MMS IEC 60870 5 101 104 FTP SFTP CDC Type II EtherNe...

Страница 6: ...Ithe Rating 5 A Rated Frequency 50 60 5 Hz Operating Time coil energization to contact closure resistive load Pickup Dropout time 8 ms typical Electrical Durability Make VA Rating 3600 VA cos 0 3 Elec...

Страница 7: ...Power Supply Immunity IEC 61000 4 11 2004 IEC 61000 4 29 2000 IEC 60255 11 2008 Magnetic Field Immunity IEC 61000 4 8 2009 Severity Level 1000 A m for 3 seconds 100 A m for 1 minute IEC 61000 4 10 200...

Страница 8: ...oducts including without lim itation software firmware and documentation The information in this document is provided for informational use only and is subject to change without notice Schweitzer Engi...