Instruction Manual
SEL-751A Relay
Synchrophasors
View Synchrophasors Using the MET PM Command
The Time Synchronization Relay Word bits in
indicate the present
status of the timekeeping function of the SEL-751A.
View Synchrophasors Using the MET PM Command
The
MET PM
serial port ASCII command may be used to view the
SEL-751A synchrophasor measurements. See
for general information on the MET command.
There are multiple ways to use the
MET PM
command:
➤
As a test tool, to verify connections, phase rotation, and scaling
➤
As an analytical tool, to capture synchrophasor data at an exact
time, in order to compare it with similar data captured in other
phasor measurement unit(s) at the same time
➤
As a method of periodically gathering synchrophasor data
through a communications processor
The
MET PM
command displays the same set of analog synchrophasor
information, regardless of the Global settings PHDATAV, PHDATAI, and
PHCURR. The
MET PM
command can function even when no serial ports
are sending synchrophasor data—it is unaffected by serial port setting
PROTO.
The
MET PM
command will only operate when the SEL-751A is in the IRIG
timekeeping mode, as indicated by Relay Word bit TSOK = logical 1.
shows a sample
MET PM
command response. The synchrophasor
data is also available via the
HMI > Meter PM
menu in
AC
SEL
ERATOR
QuickSet, and has a similar format to
NOTE:
In order to have the
MET PM
xx:yy:zz
response transmitted from a
serial port, the corresponding port
must have the AUTO setting set to
YES (Y).
The
MET PM
time
command can be used to direct the SEL-751A to display
the synchrophasor for an exact specified time, in 24-hour format. For example,
entering the command
MET PM 14:14:12
will result in a response similar to
occurring just after 14:14:12, with the time stamp 14:14:12.000.
for complete command options, and error
messages.
TREA2
Trigger Reason Bit 2 (SEL
OGIC
)
TREA1
Trigger Reason Bit 1 (SEL
OGIC
)
Table H.7
Time Synchronization Relay Word Bits
Name
Description
IRIGOK
Asserts while relay time is based on IRIG-B time source.
TSOK
Time Synchronization OK. Asserts while time is based on an IRIG-B
time source of sufficient accuracy for synchrophasor measurement.
PMDOK
Phasor Measurement Data OK. Asserts when the SEL-751A is enabled
and synchrophasors are enabled (Global setting EPMU := Y).
Table H.6
Synchrophasor Trigger Relay Word Bits
(Sheet 2 of 2)
Name
Description
Содержание 751A
Страница 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Страница 6: ...This page intentionally left blank...
Страница 12: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 26: ...This page intentionally left blank...
Страница 92: ...This page intentionally left blank...
Страница 218: ...This page intentionally left blank...
Страница 250: ...This page intentionally left blank...
Страница 376: ...This page intentionally left blank...
Страница 392: ...This page intentionally left blank...
Страница 408: ...This page intentionally left blank...
Страница 418: ...This page intentionally left blank...
Страница 434: ...This page intentionally left blank...
Страница 462: ...This page intentionally left blank...
Страница 544: ...This page intentionally left blank...
Страница 580: ...This page intentionally left blank...
Страница 584: ...This page intentionally left blank...
Страница 632: ...This page intentionally left blank...
Страница 636: ...This page intentionally left blank...
Страница 640: ...This page intentionally left blank...