U.4.80
SEL-421 Relay
User’s Guide
Date Code 20090715
Basic Relay Operations
Readying the Relay for Field Application
Step 15. Set the relay (see
Making Simple Settings Changes on
Section 1: Protection Application Examples in the
Section 1: Protection Functions in
Step 16. Connect the relay for tripping/closing duty (see
Connection Diagrams on page U.2.50
).
Step 17. From Access Level 2, use a communications terminal to issue
the commands to clear the relay data buffers (listed in
).
Step 18. Connect the secondary voltage and current inputs (see
User’s
Guide Section 2: Installation
).
Step 19. Use the
MET
command or the
AC
SEL
ERATOR
QuickSet HMI
to view relay metering to confirm secondary connections (see
Examining Metering Quantities on page U.4.33
Table 4.11
Communications Port Commands That Clear Relay Buffers
Communications Port Command
Task Performed
MET RD
Reset demand meter data
MET RP
Reset peak demand meter data
MET RE
Reset energy meter data
MET RM
Reset maximum/minimum meter data
HIS CA
Reset event report and history buffers
SER CA
Reset Sequential Events Recorder data
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...