6

TDST24M000SE 032635 190619

STARTING

TURNING ON AND OFF

To turn the control unit on and off, press the ‘ 

esc

 ’ key for 

at least 3 seconds. When the control unit is turned on it will 

carry out a diagnosis of the internal circuitry to verify its 

correct operation and the red led will flash three times.

If the control unit reveals no anomalies the red led will 

remain on, otherwise it will continue to flash quickly and the 

display will show the type of error.

BACKLIGHT

By pressing any key the backlight of the display is activated. 

The backlight automatically shuts off after about 20 seconds 

from the last key depressure.

ACOUSTIC SIGNALS

The control unit is supplied with an internal buzzer that gives 

the user an acoustic feedback in case of pressure on the 

keys, alarms and failure. The acoustic signal can be disabled 
by properly setting the relevant ‘ Installer Parameter ’.

TEST FUNCTION FOR LOAD WIRINGS CHECK

By  keeping  pressed  for  10  seconds  the  ‘ 

 ‘ button, the 

control unit performs the functionality test of the loads 

connected to it, in order to allow the installer to check 

the  wirings

.  The control unit checks the connected loads, 

depending  on  the  configured  layout,  by  simultaneously 
activating the relays outputs for about 30 seconds, while the 

PWM outputs will be raised at the maximum speed.
The test activation is showed on the control unit by 

activating the ‘ TEST ’ icon on the display.

To exit the Test mode, push the ‘ 

esc

 ‘ button at any time.

TEMPERATURE AND SPEED DISPLAY

The unit will normally show on the alphanumeric display the 

temperature (in °C) measured by the sensors connected and 

the speed (in %) of the collector pump controlled with the 

PWM or 0..10V output.
The power on of the collector pump (Erp and/or Traditional) is 

shown on the display with the icon ‘   ‘ as follows:

Icon ‘   ‘ still lit: 

Erp  and/or  Traditional 

pumps OFF

Icon ‘ 

 ‘ flashing slow: 

Erp  Pumps  ON  and 

Traditional OFF

Icon ‘ 

 ‘  flashing fast: 

Erp 

Pumps 

and/or 

Traditional ON

By pressing the keys ‘ 

 ‘ or ‘ 

 ‘ you can cycle through 

the display of the value of the sensor or pump speed:

  S_1  

  S_2  

  S_3  

  %PWM  

  %010  

AUTOMATIC / ABC (Automatic Boiler Control) 

OPERATION

The control unit can manage the installation selected in 2 

different modes:

AUTOMATIC (Normal controller operation)

 

In this mode the control unit automatically manages and 
controls the operation of the installation according to the 
programmed data (normal controller operation).

ABC (Automatic Boiler Control)

  By pressing the ‘ 

 ‘ key you can enable or disable the ABC 

function on the unit.

  When the ‘ ABC ‘ function is active, the display will turn on 

the ‘ 

 ‘ icon.

  Following are the conditions which result in activating the 

collector pump:

  S_1≥TABC+Hysteresis value

 and

  S_1≥S_2+ Hysteresis value
  Following are the conditions which result in turning off the 

collector pump:

 S_1<TABC
 or
 S_1<S_2
 Where:
 

S_1

: Temperature measured by the collector sensor.

 

S_2

: Temperatura measured by the boiler sensor.er.

 

TABC

: Temperature set with installer parameter P2.

 

Hysteresis value for ABC function

:  3.0°C  (fixed  - 

unchangeable)

 The only active controls will be those relative to the 

maximum and safety temperatures.

RESET

In  order  to  reset  the  device,  press  the  key  labelled  as                   
‘ 

RESET

 ’ located behind the removable door; 

DO NOT USE 

PINS OR NEEDLES

.

Содержание TDST24M

Страница 1: ...LAR SYSTEMS c The installation technician shall operate in full compliance with all the applicable technical standards in order to grant the unit safety WARNING DESCRIPTION OF THE KEYS RESET KEY MENU...

Страница 2: ...C 145 C 180 C Offset adjustment on S1 5 0 C on S2 5 0 C on S3 5 0 C Installer Password 0000 9999 default 0000 Acoustic Signal On Off default On Backlight timing 20 sec from last keypress OUT2 Relay L...

Страница 3: ...to pass through and fit the blocks delivered 6 INSTALLATION 2 Remove the two screws shown in the drawing then remove the whole body from the base 5 Fit the cover again with the electronics at the bas...

Страница 4: ...obe blue cable must be used while the probes with the range of 50 C 110 C yellow cable can be used for the other probes The outputs OUT1 OUT2 and Alarm are voltage free It is advisable to fit a 10A 25...

Страница 5: ...hat the removable wiring terminals have been inserted with the correct orientation the terminals screws must be facing upward EXAMPLE OF CONNECTION FOR 3 SPEED SOLAR CIRCULATORS WITH WET or HIGH EFFIC...

Страница 6: ...ow on the alphanumeric display the temperature in C measured by the sensors connected and the speed in of the collector pump controlled with the PWM or 0 10V output The power on of the collector pump...

Страница 7: ...ng the Password In order to modify the stored password first press the key then proceed as follows PRESS THE MENU KEY THE DISPLAY SHOWS PWDH0000 Pressing the esc key at any time will exit the password...

Страница 8: ...ic hysteresis WARNING The thermal parameters to be set are displayed when the relevant scheme is selected this means the power unit will only display the thermal parameters actually activated for the...

Страница 9: ...nstallation with 1 tank and additional thermostatic heating Control logic OUT 1 TS2 TS3 TS1 T1 2 TM3 TAF AFR 1 0 OUT 2 TAH TAH OUT 3 SCH 06 Solar heating installation with 1 tank and only 2 probe Cont...

Страница 10: ...0 C TS3 20 0 90 0 C 80 0 C WARNING It is not possible to set the Safety Temperatures TS2 and TS3 to a value lower than the relevant Maximum Temperature as the value of the Safety Temperature is limit...

Страница 11: ...ety Temperature TS 5 C To increase the Maximum Temperature value it is first necessary to increase the value of the Safety Temperature Integration Temperature After Heating on probe S3 Data Regulation...

Страница 12: ...CTING PARAMETER P3 PRESS THE KEY USE THE OR ARROWS TO SET THE DESIRED NUMERIC VALUE PRESS THE KEY TO CONFIRM THE PROGRAMMING OR PRESS THE esc KEY TO CANCEL THE CHANGES PRESS THE KEY TO MODIFY THE THER...

Страница 13: ...he function is not supported by the layout selected the controller will display NONE Note 1 means Normally Open N O logic while 0 means Normally Closed N C logic AFTER SELECTING PARAMETER P5 PRESS THE...

Страница 14: ...ion whenever on the relevant panel is measured a temperature lower than the one set in this parameter The function Minimum Temperature Limitation is not active when in ABC operation or in case the pum...

Страница 15: ...SET THE DESIRED NUMERIC VALUE PRESS THE KEY TO CONFIRM THE PROGRAMMING OR PRESS THE esc KEY TO CANCEL THE CHANGES In the following the regulation ranges allowed for each parameter are listed Setting...

Страница 16: ...NOR set by the parameter ERP P8 PUMP When parameter PUMP NOR PWM2 Tr 0 The pump takes its speed at level OFF or VOFF 0 Tr T The pump will have a variable rotation speed between ON and MAX or between...

Страница 17: ...and vice versa in order to prevent abrupt changes or oscillations in the system regulation Fixed mode temperature control Data Regulation range Default T_FT 0 C 90 C 60 C Note this parameter is activ...

Страница 18: ...temperature measurement could be slow because of its non optimal position By enabling the function you can choose between two different operating programs P_1 where VTC function is enabled and Boiler...

Страница 19: ...ella function The anti Legionella function activated by default consists of a boiler s water heating cycle at 65 C every 30 days for 5 minutes in order to carry out thermal disinfection action against...

Страница 20: ...erential value is fixedto 2 C therefore not adjustable FUNCTIONS ACCESSIBLE TO THE USER The functions accessible to the user are limited and do not allow setting those data influencing the installatio...

Страница 21: ...OWING THE USER PARAMETERS PRESSING RESETS THE TEMPERATURE RECORDED TO THAT POINT PRESSING esc RETURNS TO SHOWING THE MEMORIZED TEMPERATURE PRESS THE esc KEY TO QUIT THE MAXIMUM TEMPERATURE DISPLAY MOD...

Страница 22: ...d by a series of beeps together with the quick flashing of the red power supply led The probe originating the problem is flashing on the display The control unit has revealed an anomaly on the probe T...

Страница 23: ...23 TDST24M000SE 032635 190619 NOTE...

Страница 24: ...24 TDST24M000SE 032635 190619 SEITRON S p A a socio unico Via del Commercio 9 11 36065 Mussolente VI ITALY Tel 39 0424 567842 Fax 39 0424 567849 www seitron it info seitron it...

Отзывы: