DIGITAL CONTROL UNIT

FOR THERMAL SOLAR SYSTEMS

c

The installation technician shall operate in full compliance with all the applicable technical standards in order to 
grant the unit safety.

WARNING

DESCRIPTION OF THE KEYS

RESET KEY

MENU KEY

CANCEL KEY

KEY ‘ABC FUNCTION’

CONFIRMATION KEY

SELECTION KEYS

Содержание TDST24M

Страница 1: ...LAR SYSTEMS c The installation technician shall operate in full compliance with all the applicable technical standards in order to grant the unit safety WARNING DESCRIPTION OF THE KEYS RESET KEY MENU...

Страница 2: ...C 145 C 180 C Offset adjustment on S1 5 0 C on S2 5 0 C on S3 5 0 C Installer Password 0000 9999 default 0000 Acoustic Signal On Off default On Backlight timing 20 sec from last keypress OUT2 Relay L...

Страница 3: ...to pass through and fit the blocks delivered 6 INSTALLATION 2 Remove the two screws shown in the drawing then remove the whole body from the base 5 Fit the cover again with the electronics at the bas...

Страница 4: ...obe blue cable must be used while the probes with the range of 50 C 110 C yellow cable can be used for the other probes The outputs OUT1 OUT2 and Alarm are voltage free It is advisable to fit a 10A 25...

Страница 5: ...hat the removable wiring terminals have been inserted with the correct orientation the terminals screws must be facing upward EXAMPLE OF CONNECTION FOR 3 SPEED SOLAR CIRCULATORS WITH WET or HIGH EFFIC...

Страница 6: ...ow on the alphanumeric display the temperature in C measured by the sensors connected and the speed in of the collector pump controlled with the PWM or 0 10V output The power on of the collector pump...

Страница 7: ...ng the Password In order to modify the stored password first press the key then proceed as follows PRESS THE MENU KEY THE DISPLAY SHOWS PWDH0000 Pressing the esc key at any time will exit the password...

Страница 8: ...ic hysteresis WARNING The thermal parameters to be set are displayed when the relevant scheme is selected this means the power unit will only display the thermal parameters actually activated for the...

Страница 9: ...nstallation with 1 tank and additional thermostatic heating Control logic OUT 1 TS2 TS3 TS1 T1 2 TM3 TAF AFR 1 0 OUT 2 TAH TAH OUT 3 SCH 06 Solar heating installation with 1 tank and only 2 probe Cont...

Страница 10: ...0 C TS3 20 0 90 0 C 80 0 C WARNING It is not possible to set the Safety Temperatures TS2 and TS3 to a value lower than the relevant Maximum Temperature as the value of the Safety Temperature is limit...

Страница 11: ...ety Temperature TS 5 C To increase the Maximum Temperature value it is first necessary to increase the value of the Safety Temperature Integration Temperature After Heating on probe S3 Data Regulation...

Страница 12: ...CTING PARAMETER P3 PRESS THE KEY USE THE OR ARROWS TO SET THE DESIRED NUMERIC VALUE PRESS THE KEY TO CONFIRM THE PROGRAMMING OR PRESS THE esc KEY TO CANCEL THE CHANGES PRESS THE KEY TO MODIFY THE THER...

Страница 13: ...he function is not supported by the layout selected the controller will display NONE Note 1 means Normally Open N O logic while 0 means Normally Closed N C logic AFTER SELECTING PARAMETER P5 PRESS THE...

Страница 14: ...ion whenever on the relevant panel is measured a temperature lower than the one set in this parameter The function Minimum Temperature Limitation is not active when in ABC operation or in case the pum...

Страница 15: ...SET THE DESIRED NUMERIC VALUE PRESS THE KEY TO CONFIRM THE PROGRAMMING OR PRESS THE esc KEY TO CANCEL THE CHANGES In the following the regulation ranges allowed for each parameter are listed Setting...

Страница 16: ...NOR set by the parameter ERP P8 PUMP When parameter PUMP NOR PWM2 Tr 0 The pump takes its speed at level OFF or VOFF 0 Tr T The pump will have a variable rotation speed between ON and MAX or between...

Страница 17: ...and vice versa in order to prevent abrupt changes or oscillations in the system regulation Fixed mode temperature control Data Regulation range Default T_FT 0 C 90 C 60 C Note this parameter is activ...

Страница 18: ...temperature measurement could be slow because of its non optimal position By enabling the function you can choose between two different operating programs P_1 where VTC function is enabled and Boiler...

Страница 19: ...ella function The anti Legionella function activated by default consists of a boiler s water heating cycle at 65 C every 30 days for 5 minutes in order to carry out thermal disinfection action against...

Страница 20: ...erential value is fixedto 2 C therefore not adjustable FUNCTIONS ACCESSIBLE TO THE USER The functions accessible to the user are limited and do not allow setting those data influencing the installatio...

Страница 21: ...OWING THE USER PARAMETERS PRESSING RESETS THE TEMPERATURE RECORDED TO THAT POINT PRESSING esc RETURNS TO SHOWING THE MEMORIZED TEMPERATURE PRESS THE esc KEY TO QUIT THE MAXIMUM TEMPERATURE DISPLAY MOD...

Страница 22: ...d by a series of beeps together with the quick flashing of the red power supply led The probe originating the problem is flashing on the display The control unit has revealed an anomaly on the probe T...

Страница 23: ...23 TDST24M000SE 032635 190619 NOTE...

Страница 24: ...24 TDST24M000SE 032635 190619 SEITRON S p A a socio unico Via del Commercio 9 11 36065 Mussolente VI ITALY Tel 39 0424 567842 Fax 39 0424 567849 www seitron it info seitron it...