thermal inertia and the various environmental conditions. 

Generally, a minimum of 1°C is recommended for underfloor 

plants and 3°C for metal ceilings.

‘CndP’ Rate of check for the dew-point regulation

This parameter allows to set the minimum time, in minutes, which 

must elapse between two consecutive activations of the output 

relays, caused by the ‘ 

c-dP

 ‘ function intervention.

This time interval can be set in steps of 3 minutes; itwill be re-

initialised every time the dew-point regulation mode is changed by the 

user (‘ 

d-EF

 ’, ‘ 

d-EC

 ’ or ‘ 

d-FP

 ‘).

Cntr

’ THERMOSTAT RELAY ACTIVATION TIMER

Using this parameter it is possible to display the thermostat 

relay activation time meter relative to the actual day. The timer is 

automatically reset at midnight.

Proceed as follows:

1.

 Select the ‘ 

Cntr

 ’ parameter and press ‘ 

OK 

’, the device displays 

the hours of activation of the thermostat relay alternating with the 

wording ‘ 

Cntr

 ’ + the ‘ 

P

 

‘ icon.

2.

 To go back to the list of user parameters, press ‘ 

OK

 ’ and then the 

‘   ‘ key.

3.

 To exit user parameters setting and restore normal operation, press 

‘   ‘ or do not press any key for 10 seconds.

dFLt

’ SET DEFAULT DATA

With this parameterit ispossible to resetuser parametersin order 

tobring back all theparameters to thefactory defaults. 

Proceed as follows:

1.

 Select the parameter ’

dFLt

’ and press ’

OK

’; the device 

automatically sets the default data and the display will show ’

-dF-

’ 

and the ‘ 

P

 

‘ icon flashes.

2.

 To return to the list of user parameters, press the ‘

OK

’ button.

3.

 To exit the user parameter settings and resume normal operation, 

press the ‘   ‘ button or wait 10 seconds without pressing any key.

WARNING!

Restoring the Default Data will reset all settings made by the 

user, such as Time Program, Heating/Cooling, Set-Points and all 

other programmable data.

SWITCHING OFF - ANTIFREEZE FUNCTION

To deactivate the programmable thermo-hygrostat press the ‘   ‘ 

button.

The display will show the word ‘ 

OFF

 ’.

If the programmable thermo-hygrostat has been set in the heating 

mode, the Antifreeze function will be active and the ‘   ‘ symbol 

will appear on the display; in such a case the room temperature will be 

controlled based on the value set for the Antifreeze temperature (see 

paragraph ‘SETTING THE USER PARAMETERS‘).

AUTOMATIC OPERATION / 24H MANUAL / PERMANENT 

MANUAL OVERRIDE FUNCTION

With the ‘   ‘ key, the programmable thermo-hygrostat may be forced 

to adjust the room temperature and humidity according to the comfort 

temperature and humidity set, regardless of the time programming 

settings.

By pressing the ‘   ‘, button repeatedly you can switch from 

Automatic to 24 hour Manual, from 24 hour Manual to Permanent 

Manual and from Permanent Manual back to Automatic.

During operation in manual mode, the display does not show the time 

program, but only the room temperature, the status of the relays (any 

switch-on of the ‘   ‘ or ‘   ‘ or ‘   ‘ symbols), the ‘ 

24h

 ‘ symbol 

(manual 24h) or ‘   ‘ (permanent manual) and the ‘   ‘ symbol.

Pressing the ‘   ‘ button once will activate the 24 hour Manual mode 

and the programmable thermo-hygrostat will remain in this mode 

until the time 23:59 is reached, after which it will go back into the 

Automatic mode.

Note: If the device is set in the 24h Manual mode and the Vacation 

program is activated, after the Vacation period has elapsed, if it is 

past the time 23.59, the programmable thermo-hygrostat will go back 

into the Automatic mode and follow the set program schedule.

Pressing the ‘   ‘ button a second time will switch the programmable 

thermo-hygrostat into the Permanent Manual mode and it will remain 

in this mode until you press the ‘   ‘ button again.

TIME/TEMPERATURE/HUMIDITY DISPLAY

By repeatedly pressing the ‘ 

 ‘ button, the display can show the 

actual time with the icon relative to the temperature adjustment probe 

(internal ‘ 

 ‘ or external ‘ 

 ‘), the room temperature read by the 

internal sensor, distinguished by the ‘   ‘ icon, the room temperature 

read by the remote probe (if connected) distinguished by the ‘ 

 ‘ 

icon and the room humidity  read by the internal sensor, distinguished 

by the ‘   ‘ icon.

The temperature and humidity readings are displayed corrected by the 

Offset value set.
Note:  If the ‘ 

rEG

 ’ parameter is set at ‘ 

In

 ’, but an error is detected 

on the internal sensor, the display will show ‘ 

SEnS E xx

 ’. In 

this situation the adjustment will be automatically interrupted 

and both relays will be placed in the Normally Open position.

 

If the ‘ 

rEG

 ’ parameter has been set at ‘ 

Out

 ‘ but the remote 

probe has not been connected or is damaged, the display will 

show the respective wording ‘ 

SEnS OPEN

 ‘ or ‘ 

SEnS SHrt

 ‘ 

with the ‘ 

 ‘ icon on.

ATTENTION:

- In order to optimise battery duration, the programmable 

thermo-hygrostat reads the room temperature every 3 minutes 

and, consequently, decides on activation or deactivation of the 

relays.

-  Press the ‘ OK ’ button briefly to perform an instant refresh.

BACKLIGHTING

The display backlight turns on whenever and button is pressed. It 

turns off automatically 20 seconds after the last pressing of a button.

HOW TO INSERT / REPLACE BATTERIES

The  battery  charge  status  is  constantly  displayed  by  means  of  the           

‘ 

 ‘ symbol.

The battery charge is at a maximum if all three level indicators are lit 

inside the symbol. If the ‘ 

 ‘  symbol (completely empty) flashes, 

it means that the batteries are depleted and must be replaced. In 

this case, both the relays are placed in the safety position (N.C.) and 

the display alternately shows the time (or temperature or humidity) 

and the word ‘ 

BATT

 ’. If the batteries are not replaced as soon as 

possible, the      ‘   ‘ or ‘ 

 ‘ symbols will also flash indicating that 

the device is blocked.

To replace the batteries proceed as follows:

1.

 Open the flap of the battery compartment (Fig. 1).

2.

 Remove the batteries, prying them out with the aid of a tool if 

necessary.

3.

 Insert the new batteries, which must be alkaline 1.5V type AA.

4.

 Check for correct time and date and eventually reset it.

CONNECTION TO A TELEPHONE INTERFACE

The programmable thermostat allows to connect a telephone interface 

with continuous operation (latching relay) to the connector ‘ 

B

 ‘ in 

Fig. 6.

Use of a suitable telephone interface does not require any setting to be 

made on the programmable thermo-hygrostat; for directions on using 

the  telephone interface see the instruction manual provided.

Via a telephone interface it is possible to turn the programmable 

thermo-hygrostat Off or turn it On in the Permanent Manual mode.

Depending on the commands received from the telephone interface the 

programmable thermo-hygrostat will act according to the following 

operating logic:

1. Telephone interface contact closed:

 

 The programmable thermo-hygrostat will switch into the 

‘Permanent Manual’ mode: the ‘   ‘ and ‘   ‘ symbols will be 

shown on the display.

2. Telephone interface contact open

, after (and only after) a 

previous closure, if no buttons have been pressed (Manual/Off):

  The programmable thermo-hygrostat will be switched off and the 

word ‘OFF‘ will be displayed along with the ‘   ‘ symbol. If the 

‘Antifreeze’ function is active the ‘   ‘ symbol will be displayed.

IMPORTANT: the commands input by pressing the control 

buttons will always have priority over the commands received 

from the telephone interface.

If you press the ‘   ‘ or ‘   ‘ button on the programmable thermo-

hygrostat, the device will change its status and the ‘   ‘ icon will 

flash to indicate that the interface command has been overridden by a 

command input with a control button.

The ‘ 

 ‘ icon will stop flashing if the telephone interface sends the 

programmable thermo-hygrostat the same command as the one made 

with the button or if the telephone interface is reset. In such a case 

the status set by means of the control button will not be changed 

and the programmable thermo-hygrostat will be ready to receive a 

new command.

IMPORTANT

If an Off command is sent to the programmable thermo-

hygrostat via the telephone interface (contact open), it is a 

good idea to check that the command has been executed by the 

programmable thermo-hygrostat by carrying out the following 

realignment procedure:

1. Using the functions of the telephone interface, check that the 

contact is open, sending an Off command if necessary.

2. Send a command to the telephone interface to close the 

contact (the programmable thermo-hygrostat will turn on).

3. Using the functions of the telephone interface, check that the 

contact is closed.

4. Send a command to the telephone interface to open the 

contact (the programmable thermo-hygrostat will turn off).

During this sequence no commands should be input with the 

control buttons as they have priority over the interface commands.

TECHNICAL CHARACTERISTICS 

Power supply:      

2 x 1.5V, alkaline batteries (Type AA)

Battery life:        

>1 year

Backlight turns off:   

20 sec. after the last pressing of a 

button

Thermostat section

Range of adjustment: comfort:  5°C .. 40°C

 

 

economy:  5°C .. 40°C

Asymmetrical differential: 

0,1°C .. 5°C (Default 0,2°C)

Thermostat relay

contacts capacity:   

5(1)A 250V~ SPDT

Hygrostat section

Range of adjustment: comfort:  10%RH .. 95%RH

 

 

economy:  10%RH .. 95%RH

Differential:   

 

0,5%RH .. 10.0%RH (Default 2.0%RH)

Hygrostat relay

contacts capacity:   

5(1)A 250V~ SPDT

Sensor type:  

 

Internal (temperature/humidity)

Humidity reading saturation: 

Probe temp. <10.0%RH (- - - -)

 

 

 

Probe temp. >90.0%RH (E E E E).

Temperature accuracy (-40°C .. 120°C):

Humidity accuracy (0%RH .. 100%RH @25°C):

Resolution:   

 

0.1°C. (-9.9°C .. 50°C)

 

 

 

0.1%RH (10%RH .. 90%RH)

Internal sensor Offset:

 

Temp.:   

± 5.0°C. (Default 0.0°C)

 

Humidity: 

± 5.0% RH. (Default 0.0°C)

Remote probe type:   

NTC 10K Ohm ±1% @ 25°C (optional)

Remote probe Offset: 

± 5.0°C. (Default 0.0°C)

Antifreeze:   

 

OFF / 0.5°C .. 25.0°C (Default 3.0°C)

Dew point:   

 

OFF / d-EF / d-EC / d-FP (Default d-FP)

Ext. Interface Input:   

On/Off type continuous signal.

Protection rating:   

IP 30

Insulation class:  

 

II ( 

 ) 

Number of manual cycles: 

1,000

Number of automatic cycles:  100,000

Type of action:   

 

1CU

Tracking index:   

 

PTI 175

Pollution situation:   

2 (normal)

Overvoltage category: 

II

Operating temperature: 

0°C .. +40°C

Storage temperature: 

-10°C .. +50°C

Humidity limits:   

 

20% .. 80% RH non-condensing

Enclosure:  Material:  

ABS+PC V0 self-extinguishing

 

Colour:   

Signal white (RAL 9003)

 

     

 

Light grey (RAL 7035)

Weight: 

     

 

~ 156 gr.

CLASSIFICATION UNDER REG. 2013.811.EC

Class:    

 

Contribution to energy efficiency: 

1%

NORMATIVE REFERENCES

The product is conform with the following standards (EMC 2014/30/UE 

and LVD 2014/35/UE):

EN-60730-1 (2011)

EN-60730-2-7 (2010)

EN-60730-2-9 (2010)

DIMENSIONS

WARRANTY

In the view of a constant development of their products, the 

manufacturer reserves the right for changing technical data and 

features without prior notice. The consumer is guaranteed against any 

lack of conformity according to the European Directive 1999/44/EC as 

well as to the manufacturer’s document about the warranty policy. The 

full text of warranty is available on request from the seller.

Содержание T.HYGROS THW02B

Страница 1: ...highlighted by a box surrounding the number corresponding to the day of the week 1 Monday 7 Sunday 8 Confirm by pressing OK the output of the time and day setting is automatic Time Temperature Humidity Display By repeatedly pressing the the display can alternately show the actual time the room temperature in C read by the internal sensor distinguished by the icon the room temperature in C read by ...

Страница 2: ... OK button 5 To exit the user parameter settings and resume normal operation press the button or wait 10 seconds without pressing any key OFS2 REMOTE SENSOR OFFSET SETTING With this parameter it is possible to correct the temperature reading of the remote sensor by 5 C in order to correct any systematic reading errors due to the positioning of the remote sensor in areas unsuitable for measuring th...

Страница 3: ...cation devices on the basis of the comparison of the temperature value of the dew point calculated and the temperature values relative to the dew points set in the sub parameters TF1 and TF2 The following graphics describe the dew point control mode HYdP hysteresis OFF PRIORITY ON THERMOSTAT cooler dehumidifier TF1 0 C HYdP hysteresis PRIORITY ON DEHUMIDI FIER dP TF2 ON TF1 HYdP Dove dP dew point ...

Страница 4: ...pleted and must be replaced In this case both the relays are placed in the safety position N C and the display alternately shows the time or temperature or humidity and the word BATT If the batteries are not replaced as soon as possible the or symbols will also flash indicating that the device is blocked To replace the batteries proceed as follows 1 Open the flap of the battery compartment Fig 1 2...

Страница 5: ...at to the wall plate using the supplied screw that is located inside the battery compartment Fig 8 5 Fig 8 Insert the batteries in the battery compartment I in Fig 1 see paragraph HOW TO INSERT REPLACE THE BATTERIES 6 QUICKGUIDEFORSETTINGTHETIMESCHEDULE Press button P The display shows PrOG with the icon P turned on Press key OK the display shows the word dAY the icon P and the squares correspondi...

Отзывы: