background image

 

 

      

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DR

R42

M

0

0

0

1

A

N 0

3

3

6

0

0

 2

81

1

1

features  a  configuration  menu  where  you  can  customize  the 
regulation parameters that will be transmitted to the receiver and 
stored during the "test" mode procedure.  
It is possible to configure the type of regulation even when using a 
non configurable thermostat (i.e. DTPF85BC) in this case you have 
to temporarily learn the address and configure the output with a 
display  thermostat,  then  you  learn  the  address  of  the  final  non 
configurable thermostat.  
The  receiver  maintains  the  output  configuration  of  the  display 
thermostat  even  when  a  new  non  configurable  thermostat  is 
learned. In case you have customized the output and you want to 
return to the factory default ON/OFF configuration it is necessary 
to do a factory default reset. 

 

FACTORY DEFAULT RESET 

A  factory  default  reset  clears  the  non-volatile  memory  of  the 
device  deleting  any  address  learned  with  the  self-learning 
procedure and restoring the default ON/OFF output configuration 
with predefined hysteresis.  
To factory reset: 
- Power down 
- Press and hold both buttons        

  

and          Fig.1 

- Power on 
- Wait until the LEDs blink 
- Release the buttons 

 

REGULATION WITH DEAD BAND

 

The receiver can be set on jumper JP1 to regulate with dead band 
(see step 7 under "Installation"). 
When  regulating  with  dead  band,  the  receiver  drives  the  “heat” 
valve with the relay  of channel 1 and the “cool” valve with the 
relay of channel 2. 
When regulating with dead band, the receiver can learn only one 
thermostat on channel 1 and the thermostat will drive both relays 
of channel 1 and channel 2. If the setpoint temperature is greater 
than the room temperature there  is a “heating”  request  and the 
“heat”  valve  on  relay  1  will  be  turned  on,  conversely,  if  the 
setpoint temperature is lower than the room temperature there is 
a “cooling” request and the “cool” valve on relay 2 will be turned 
on.  If  the  room  temperature  matches  the  setpoint  temperature 
both outputs remain off. More in detail the width of the dead band 
determines  the  temperature  range  in  which  the  outputs  remain 
off. The dead band‘s width can be set on the trimmer with a small 
screwdriver in the range 1 to 11 °C (see step 8 in "Installation"). 
The heating output will be activated when the room temperature 
is below the setpoint temperature of half the dead band, while the 
cool output will be activated when the room temperature will be 
higher than the temperature setpoint of half the dead band. 
When in dead band regulation it is assumed that the heating and 
cooling  systems  are  always  available  and  the  heating/cooling   
status  of  the  transmitter  will  be  ignored,  as  it  is  the  room 
temperature that will determine whether to heat or to cool. 
When in dead band regulation, the “test” mode of the thermostat 
will toggle every 2 seconds only output 1 (heating). 
When  the  receiver  is  set  for  dead  band  regulation,  it  can  not 
perform the lower and upper floor temperature limitation that can 
be set on TRD01B and DCW01B thermostats. 

TROUBLESHOOTING 

 

SYMPTOM

The receiver appears completely “dead”. 

PROBABLE CAUSE

: There’s no mains power. 

REMEDY

Check  the  mains  power  connection. 
Usually  LEDs  may  remain  off,  but  they 
perform  a  blinking  sequence  “green-red-
green-red” when the receiver is switched on 
to indicate correct operation. 

 

SYMPTOM

One  of  receiver’s  LED  continuously  blinks 
green. 

PROBABLE CAUSE

: The device is signaling a fault because it has 

detected  an error in the temperature probe 
of the wireless thermostat or programmable 
thermostat. 

REMEDY

Check  the  temperature  probe  of  the 
transmitter  and,  if  present,  the  jumper  for 
selecting between the internal and external 
probe. Carefully read the instructions of the 
transmitters for further information. 

 

SYMPTOM

One  of  receiver’s  LED  continuously  blinks 
yellow. 

PROBABLE CAUSE

: The device is signaling a fault because it has 

detected  the  wireless  thermostat  or 
programmable  thermostat  batteries  to  be 
running low. 

REMEDY

Replace  the  batteries  of  the  transmitters 
concerned. Carefully read the instructions of 
the transmitters for further information. 

 

SYMPTOM

One  of  receiver’s  LED  continuously  blinks 
red. 

PROBABLE CAUSE

: The  channels  in  question  are  in  an  “alarm 

status”  due  to  the  absence  of  radio 
communication. 

REMEDY

Check the radio communication again using 
the  “test”  function  on  the  transmitter. 
Assess  whether  the  devices  need  to  be 
moved  away  from  metal  shields  or  a 
“repeater” needs to be installed. 

 

SYMPTOM

When  starting  the  self-learning  procedure, 
the receiver does not blinks the LED yellow. 

PROBABLE CAUSE

: The  self-learning  button  has  been  pressed 

too quickly. 

REMEDY

Start  the  self-learning  procedure  keeping 
pressed  the  self-learning  button  for  one 
second. 

 

SYMPTOM

The  transmitter  is  in  the  “test”  mode  but 
the  receiver  fails  to  switch  on  any  relay. 
The LED does not indicate any reception of 
commands via radio. 

PROBABLE CAUSE

: The signals received are too weak to enable 

correct decoding of the commands . 

REMEDY

Assess  whether  the  devices  need  to  be 
moved  away  from  metal  shields  or  a 
“repeater” needs to be installed. 

 

SYMPTOM

The  receiver’s  LED  remain  red  despite  the 
communication  with  the  transmitter  had 
been restored.  

PROBABLE CAUSE

: The long-term analysis of the signal quality 

reports the history of the last 90 minutes of 
the channel activity. 

REMEDY

Verify  with  the  “test”  mode  that  the 
“immediate” indication on the LED indicates 
a  sufficient  signal  quality  and  allow  up  to 
90  minutes  for  the  long-term  analysis  to 
turn green. 

TECHNICAL FEATURES 

Power supply: 

230V  50Hz / 24V  

Absorption:   

11VA 

Relay contacts ratings: 

2 x 6(4)A 250V  (voltage free) 

Regulation hysteresis : 

0,3°C 

Frequency:    

868,150 MHz 

Sensitivity:    

-105 dBm 

Modulation:    

GFSK 

Bandwidth (-3 dB):  

100 KHz 

Type of antenna:  

internal stylus  

Max. distance from transmitter:  >300m in free field 
 

 

>50 m in buildings (depending 
on the building and environment) 

Protection rating: 

IP 3X 

Type of action:  

1  

Overvoltage category: 

II 

Pollution degree:  

Tracking index (PTI): 

175 

Class of protection  
against electric shock:  

II   

Rated impulse voltage: 

2500V 

Number of automatic cycles: 

100000 (diagrams on  Fig. 7, 8, 
9, 10) 

Software class:  

EMC test voltage:  

230V  50Hz 

EMC test current:  

45 mA 

Distances tolerances fault 
mode ‘short’ exclusion: 

±0,15 mm 

Ball pressure test temperature:  75 °C 
Operating temperature: 

0°C .. 40 °C 

Storage temperature: 

-10°C .. +50 °C 

Humidity limits: 

20% .. 80 % RH non-condensing  

Enclosure:  Material: 

ABS V0 self-extinguishing 

 

Color:    

Signal White (RAL 9003) 

 

 

(RAL 9003) 

Installation:   

Wall mounted 

 

DIMENSIONS 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

WARRANTY

 

In  the  view  of  a  constant  development  of  their  products,  the 
manufacturer reserves the right for changing technical  data and 
features without prior notice. 
The  consumer  is  guaranteed  against  any  lack  of  conformity 
according to the European Directive 1999/44/EC as well as to the 
manufacturer’s document about the warranty policy. The full text 
of warranty is available on request from the seller. 

- ENGLISH - 

Содержание DRR42M

Страница 1: ...ro Modbus del ricetrasmettitore E comunque possibile gestire separatamente i due canali da due diversi canali del ricetrasmettitore Modbus eseguendo un autoapprendimento per ogni canale E possibile anche gestire uno dei canali da un ricetrasmettitore Modbus e l altro canale da un termostato o cronotermostato Procedura di auto apprendimento Alimentare il ricevitore i LED lampeggiano per qualche sec...

Страница 2: ...e di rete Normalmente i LED possono rimanere spenti ma all accensione eseguono una sequenza di lampeggii verde rosso verde rosso per segnalare il buon funzionamento SINTOMO Uno dei LED del ricevitore lampeggia continuamente di colore verde PROBABILECAUSA Il dispositivo segnala un anomalia perché ha rilevato un errore sulla sonda di temperatura del termostato o cronotermostato trasmettitore RIMEDIO...

Страница 3: ...ta la regolazione con zona neutra 8 Fig 12 Fig 5 E F F Fig 4 D D ITALIANO Fig 7 Posizionare il coperchio cavi sulla base e ruotarlo verso la base spingere verso l interno la linguetta plastica posta sulla parte inferiore della base ed esercitare una pressione che faccia scattare la linguetta plastica di fissaggio all interno del foro sul lato inferiore del coperchio cavi Fig 3 9 IL JUMPER JP1 PERM...

Страница 4: ... bottom slot and slightly lift the cable lid up Fig 2 2 Set JP1 jumper if the dead band regulation is desired 7 THE JP1 JUMPER ALLOWS TO SET THE WORKING MODE OF THE RECEIVER B A B A Two channels receiver default One channel receiver with dead band regulation Fig 11 Set the dead band width trimmer if dead band regulation has been chosen 8 Fig 12 Make the electrical connections following the appropr...

Страница 5: ...ter of the transceiver Anyway it is possible to manage separately the two channels by two different channels of the Modbus transceiver by performing a self learning procedure for each channel It is also possible to manage one of the channels with a Modbus transceiver and the other one by a thermostat or a programmable thermostat Self learning procedure Switch on the receiver the LEDs blink for a f...

Страница 6: ...he device is signaling a fault because it has detected an error in the temperature probe of the wireless thermostat or programmable thermostat REMEDY Check the temperature probe of the transmitter and if present the jumper for selecting between the internal and external probe Carefully read the instructions of the transmitters for further information SYMPTOM One of receiver s LED continuously blin...

Отзывы: