Seifert 850310001 Скачать руководство пользователя страница 3

Version Nr. 1-8 - 24.12.2020

Doc. Nr. 99850310001

3 / 19

Disregarding the instruction manual
Operating error
Inappropriate work on or with the unit
The use of non-specified spare parts and accessories
Unauthorised modifications or changes to the unit by the user or his personnel

The supplier is only liable for errors and omissions as outlined in the guarantee conditions contained in the main
contractual agreement. Claims for damages on any grounds are excluded.

3. Safety instructions

Upon delivery the unit is already meeting current technical standards and can therefore be safely taken into
operation. Only authorised personnel is allowed to work on the unit. Unauthorised personnel must be prohibited
from working on the unit. Operating personnel must inform their superiors immediately of any malfunction of
the unit. 
Please note that before starting to work on or with the unit, a procedure must be carried out inside the cabinet
on which the unit is to be mounted.
Before commencing work inside the cabinet, the control cabinet manufacturer's instruction must be read with
regards to:

Safety instructions.
Instructions on taking the cabinet out of operation.
Instructions on the prevention of unauthorised cabinet reconnection.

The electric equipment meets the valid safety regulations. One can find dangerous voltages (above 50 V AC or
above 100 V DC)

Behind the control cabinet doors.
On the power supply in the unit housing.

The unit has to be operated according to the type plate and the wiring diagram, and must be protected
externally from overloading and electrical faults via suitable protective devices.

Danger through incorrect work on the unit
The unit can only be installed and maintained by technical competent and qualified personnel,
using only supplied material according to the supplied instructions.

Danger from electrical voltage
Only specialised personnel are allowed to maintain and clean the unit. The personnel must
ensure that for the duration of the maintenance and cleaning, the unit is disconnected from
the electrical supply.
Attention
Damage to the unit through the use of inappropriate cleaning materials. Please do not use
aggressive cleaning material.
 

Instruction
Damage to the environment through unauthorised disposal. All spare parts and associated
material must be disposed according to the environmental laws.

Содержание 850310001

Страница 1: ...2 3 Safety instructions 3 4 Settings 4 5 Functional principle 8 6 Technical data 9 7 Mounting 10 8 Mounting Principle 13 9 Electrical connection 14 10 Wiring diagram 15 11 Taking into operation 15 12 Trouble shooting 16 13 Maintenance Cleaning 16 14 Transport Storage 17 15 Parts supplied Spare parts Accessories 18 ...

Страница 2: ... instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the following High electric voltage Indicates electric shock danger Important safety instruction Indicates instructions for safe maintenance and operation of the unit Attention Indicates possible burns from hot components Attention Indicates poss...

Страница 3: ...ad with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid safety regulations One can find dangerous voltages above 50 V AC or above 100 V DC Behind the control cabinet doors On the power supply in the unit housing The unit has to be operated according to the ty...

Страница 4: ...dditional electrical cabinet heater For the cooling capacities and evironmental ratings please refer to the type plate data Controller The display shows the temperature in the range of 50 C to 150 C 58 F to 302 F The temperature is displayed with resolution of tenths between 19 9 C and 99 9 C 3 8 F to 211 8 F During programming it shows the codes and values of the parameters The display also shows...

Страница 5: ...perature units C F low temperature alarm and high temperature alarm 1 Press PRG button for 5 seconds to reach the modifiable parameter list 2 Use or to reach the desired parameter C18 for temperature unit of measure C 0 F 1 P25 for low temperature alarm threshold default 10 C 14 F P26 for high temperature alarm threshold default 55 C 131 F c68 for door contact NO NC logic change 0 ON if closed 1 ON...

Страница 6: ...ally closed NC and normally open NO alarm contacts are provided These refer to the alarm state Under normal conditions the NC contact is closed and the NO contact is open When an alarm condition is present or the door contact is open the NC contact will open and the NO contact will close System power failure will give an alarm condition State Alarm relay Display 1 System powered OFF 2 System power...

Страница 7: ...s and compressor s correct operation Contact your service partner E05 Low temperature alarm The measured temperature has fallen below the threshold P25 E07 E08 Controller error Contact your service partner Important Notes Whilst programming if no button is pressed for 10 seconds the display starts flashing and after 1 minute returns to the main display without saving changes To increase scrolling s...

Страница 8: ...nt thus taking it to high pressure and high temperature and pushes it through the condenser where it is cooled by ambient air thus passing from the gas to the liquid state At the liquid state it then passes through the capillary pipe being a much lower pressure the refrigerant arrives to the evaporator where it absorbs the necessary heat to change from liquid to gas state The gas is then drawn bac...

Страница 9: ...ge 50 F 140 F Air volume flow system unimpeded Ambient air circuit 118 240 cfm Cabinet air circuit 72 106 cfm Mounting Wall mounted recessed Housing Material Mild steel powder coated Dimension H x W x D 23 7 x 9 9 x 5 4 inch Weight 30 lbs Voltage Frequency 120 V 60 Hz Current 95F95F 2 1 A Starting current 7 5 A Max current 2 6 A Nominal power 95F95F 200 W Max power 300 W Fuse 15 A T Connection 5 po...

Страница 10: ...t internal and external are not obstructed It must also be ensured in accordance with UL that the air outlet is not blowing air directly at an equipment operator Should this be the case a barrier or duct shall be provided to redirect the airflow Cooling unit enclosure air suction hole must be installed in the highest possible point When installing the unit on a door ensure it can take the weight Be...

Страница 11: ... Nr 1 8 24 12 2020 Doc Nr 99850310001 11 19 Cold air outlet duct When using a cold air outlet duct please follow the steps below Filter installation If you install replace a filter please follow the steps below ...

Страница 12: ...ted condensate evaporation of the cooling unit releases the condensate to the environment If condensate formation is too great additional condensate can drip into an overflow trough which then drains off on the ambientt side In order to prevent the formation of excessive condensate you should nevertheless check the seals at regular intervals consider installing a door contact switch order no 3100001...

Страница 13: ...50310001 13 19 8 Mounting Principle Do not use within the first 15 minutes after installation 1 M6 screws 2 M6 toothed washers 3 M6 flat washers 4 Enclosure 5 Mounting gasket 6 Lifting hook 7 Cover 8 M4 screws Fig 1 Recessed Fig 2 External ...

Страница 14: ...le below and section Controller Setting temperature units C F low temperature alarm door contact logic section for more information c68 0 default ON if closed Door contact terminals bridged or NC door switch connected contact must be closed when cabinet door is closed c68 1 ON if open Remove bridge or NO door switch connected contact must be open when cabinet door is closed Alarm Contacts Alarm co...

Страница 15: ...nnected to the mains and taken into operation The unit system must be protected with a MCB Type D or K Upon connection the internal fan will start working If the temperature inside the enclosure is higher than the set value of the controller both the compressor and external air fan start working The cooling cycle will either stop once the air inside the enclosure reaches the set temperature minus ...

Страница 16: ...t leakage Contact dealer service center Excessive condensate Enclosure door open Ambient air gets into the enclosure Ensure door is closed add a door switch and connect it to controller Enclosure door closed Enclosure IP protection class is below IP54 Seal all openings of the enclosure Damaged or misplaced sealing strip Repair sealing strip accordingly 13 Maintenance Cleaning Always switch power s...

Страница 17: ...s temperature range 40 F to 158 F Relative humidity at 77 F max 95 The cooling unit should always be stored according to the installation position Returning the unit To avoid transport damage the unit should be returned in the original packing or in a packing case and must be strapped to a pallet If the unit cannot be returned in the original packing please ensure that A space of at least 30 mm mu...

Страница 18: ...Version Nr 1 8 24 12 2020 Doc Nr 99850310001 18 19 15 Parts supplied Spare parts Accessories Parts supplied ...

Страница 19: ...06 BF 1 Cold air outlet duct AC 8503 06 BZ 1 External transformer 400 460 V 2 AC 8503 05 06 CS 1 Door switch contact 3100001 Seifert Systems GmbH Seifert Systems Ltd Seifert Systems AG Seifert Systems Inc Seifert Systems Pty Ltd Albert Einstein Str 3 HF09 10 Wilerstrasse 16 75 Circuit Drive 105 Lewis Road Hal Far Industrial Estate North Kingstown Wantirna South 42477 Radevormwald Birzebbuga BBG 30...

Отзывы: