Seifert 752501B001 Скачать руководство пользователя страница 14

Version Nr. 1-3 - 09.11.2022

Doc. No. 99752501B001

14 / 17

14. Taking into operation

The cooling performance of the heat exchanger is dependent on the water flow rate available from the supply.
The water flow is dependent on the water supply system to which the heat exchanger is connected and is
affected by various factors, such as conduit pressure, conduit diameter, etc.

1. Units without water flow regulator
These units do not have any automatic control functions.

2. Units with Solenoid valve
The solenoid valve is switched electrically. If the unit power is off, the valve is open.

3. Units with temperature controller
The unit is equipped with a temperature controller which regulates the function of the unit. On normal working
conditions the display shows the temperature inside the enclosure. The controller “set point” for the interior of
the enclosure (parameter St) is pre-set at 77°F and can be adjusted b68°F and +122°F.
The High temperature alarm (parameter AH) is preset at 131°F.

Modifying controller parameters
1. Press the SET button for more than 3 sec. (if there are active alarms, mute the buzzer).The display shows the
parameter code ‘PS’ (password).
2. Only for parameters requiring password: Press the SET button to access the password setting, use the UP and
DOWN buttons to scroll the numbers until displaying, “22” (default password to access the parameters), press
the SET button to confirm the password
3. Use the UP and DOWN buttons to scroll the parameters. The LED corresponding to the category of
parameters will be on
4. Press SET to display the value associated with the parameter
5. Increase or decrease the value using the UP or DOWN button respectively
6. Press SET to temporarily save the new value
7. Press the SET button for more than 3 sec. to permanently save the new parameters and exit the parameter
setting procedure.

If no button is pressed for 60 sec. all changes made to the parameters, temporarily saved in the RAM, will be
cancelled and the previous settings restored. The cooling unit manufacturer is in no way liable for any
alterations the customer may make to the factory set parameters, unless the manufacturer has authorized the
customer in writing to change them.

This manual is intended as quick reference for controller, for a full controller manual or if you need to restore
the factory parameters please go to our website to download the full manual or to locate your nearest servicing
office.

4. Units with door switch
The unit can be switched on and off via a door contact switch (optional). When delivered the door contact
terminals are bridged on the female connector. To connect the door contact switch remove the bridge and
connect door contact switch. The contact must be closed when the cabinet door is closed.

 

Содержание 752501B001

Страница 1: ...fety instructions 3 4 Settings 4 5 Functional principle 5 6 Technical data 6 7 Performance graph 7 8 Mounting 8 9 Mounting Principle 9 10 Cut out dimensions 10 11 Dimensions H x W x D 11 12 Controller...

Страница 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage Indicates e...

Страница 3: ...ad with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid sa...

Страница 4: ...t be soft enough to avoid scale deposits but should not be too soft as this would corrode the heat exchanger Where the cooling water is cooled for reuse part of the water has to be changed with fresh...

Страница 5: ...s circulation of the air in the cabinet This circulation prevents hot spots within the control cabinet During this process the coolant heats up and is returned to the coolant supply system at an incre...

Страница 6: ...terial Mild steel powder coated Dimension H x W x D 1 350 x 395 x 192 37 155 mm Weight 29 kg Voltage Frequency 230 V 50 60 Hz Starting current 0 6 0 7 A Max current 0 5 0 6 A Max power 105 125 W Press...

Страница 7: ...Version Nr 1 3 09 11 2022 Doc No 99752501B001 7 17 7 Performance graph...

Страница 8: ...sealed control cabinet will result in an increased level of condensation The control cabinet should have a minimum of IP54 protection in accordance with IEC 60 529 Cooling medium connection There are...

Страница 9: ...Version Nr 1 3 09 11 2022 Doc No 99752501B001 9 17 9 Mounting Principle...

Страница 10: ...Version Nr 1 3 09 11 2022 Doc No 99752501B001 10 17 10 Cut out dimensions...

Страница 11: ...Version Nr 1 3 09 11 2022 Doc No 99752501B001 11 17 11 Dimensions H x W x D...

Страница 12: ...e gesch tzten Parameter Sobald Sie auf die Parameterliste zugreifen wird wieder PS angezeigt Dr cken Sie die Tasten UP oder DOWN um durch die verschiedenen Parameter zu bl ttern Dr cken Sie SET um bei...

Страница 13: ...Version Nr 1 3 09 11 2022 Doc No 99752501B001 13 17 13 Wiring diagram Zuleitung PE N L1 Signalsteckverbinder T rkontakt T2 T rkontakt T1 Alarmkontakt P2 Alarmkontakt P1...

Страница 14: ...s to scroll the numbers until displaying 22 default password to access the parameters press the SET button to con rm the password 3 Use the UP and DOWN buttons to scroll the parameters The LED corresp...

Страница 15: ...fan by loosening the 4 fastening screws To detach the fan from the fan support loosen a further 4 screws and the fan connecting cable When connecting the new fan take care that the correct polarity is...

Страница 16: ...to the unit through incorrect transport Please ensure that all liquid has been removed prior any transport To avoid transport damage the unit should be returned in the original packing or in a packin...

Страница 17: ...state North Kingstown Wantirna South 42477 Radevormwald Birzebbuga BBG 3000 4563 Gerla ngen 4901 Ottnang 26100 Cremona RI 02852 3152 Victoria Germany Malta Switzerland Austria Italy USA Australia Tel...

Отзывы: