7

No special tools other than those normally contained in an electronic technicians 
toolkit are required to service the DP140e. To check the system voltage and reset as 
necessary, it is recommended that a quality digital voltmeter be used. 

 

Adjustments

 

 

The rectifier used in the DP140e may require adjustment of the output voltage. Care 
should be used if this adjustment is made. Connect the digital voltmeter to the external 
battery connector and adjust the rectifier for a voltage of 54.6 Vdc on the external 
battery connector. 

 

 

TROUBLESHOOTING

 

 

Troubleshooting

 

 

The attached guide is intended to provide help with any problems you may run into. 
Please note that this is not a complete list of problems.  

 

Question

 - We have just completed installation of the system and we have 

no front 

panel indicator.

 

 
 

Answer

 - You will need to check the following: 

 

 

Check the power cord on the left side of the unit. 

 

 

Check the power cord at the commercial wall outlet. 

 

 

Check the circuit breaker in the power distribution panel. 

 

 

Using a voltmeter, check the AC voltage at the wall outlet. This voltage 
should be between 92 and 132 volts AC. 

 
 

Question

 - We have just completed installation of the system and we have a power 

problem. 

There are no indicators on the equipment connected to the 

power supply.

 

 
 

Answer

 - There are several things which need to be checked. 

 

 

First, are the front panel indicators on the power supply on? If not go to 
7.1.2. 

 

 

At the distribution module, disconnect the cable. Using a voltmeter, check 
the output connector. If your voltage is 54 volts or more the power supply is 
okay. 

 

Содержание DP140e

Страница 1: ...m Engineering International Installation Operations Manual 5115 Pegasus Court Suite Q Frederick MD 21704 Fax 301 694 9608 SEI Incorporated Web http www seipower com Phone 301 694 9601 800 765 4SEI 19 058 000 Rev A ...

Страница 2: ...3 Safety Information 4 Installation Instructions 4 Start Up and Checkout 6 Repair and Maintenance 6 Troubleshooting 7 TABLE OF ILLUSTRATIONS DP140e Figure 1 1 2 DP140e Models Appendix A 8 9 DP140e Distribution Configurations Appendix B 10 Wiring Configurations Appendix C 12 Connector Wiring Appendix D 13 ...

Страница 3: ...al configurations a 14 inch chassis with an internal 8 amp hour backup battery and a 7 inch chassis with no internal battery Additional external battery packs may be added to provide up to 8 hours or more of hold over time Additional features include a Low Voltage Disconnect LVD to protect the backup batteries from deep discharge manual and automatic internal battery test front panel status indica...

Страница 4: ...t 14 00 in Environmental Temperature Operating 0 C to 40 C Storage 10 C to 50 C Humidity 0 to 95 non condensing Thermal 190 BTU hr max LED Indicators User Interface Battery Charge Status Constant Green Fully Charged Flashing Green Charging Constant Red On Battery Fast Flash Red Adjust Supply Manual Battery Test Switch Push to Test NOTE The Manual Battery Test switch is disabled when the battery is...

Страница 5: ...AL The installation section of this manual will provide all of the information required for room requirements proper inspection and installation as well as instructions on checking and bringing the DP140e on line for use Inspection The equipment has been fully tested and inspected prior to shipment Although the unit has been packed in accordance with good commercial practices this does not preclud...

Страница 6: ...wering the DP140e Each unit requires a separate NEMA 5 15R receptacle A standard 7 foot 6 inch power cord with a molded NEMA 5 15 plug is supplied with each unit Environmental Requirements A clean dry location should be picked for installing this unit Mounting Instructions When mounting keep in mind the DP140e weighs 19 lbs and the DP140e 8 weighs 32lbs The DP140e is designed to mount to a wall a ...

Страница 7: ...on the right side of the unit You should have power indicator on the equipment you connected to the power supply Your DP140e supply should now be functioning properly in addition to the equipment you have connected Battery Test When the battery is fully charged Battery Charge Status LED constant green press the Manual Battery Test switch Wait five seconds then verify that the Battery Test Status L...

Страница 8: ...te list of problems Question We have just completed installation of the system and we have no front panel indicator Answer You will need to check the following Check the power cord on the left side of the unit Check the power cord at the commercial wall outlet Check the circuit breaker in the power distribution panel Using a voltmeter check the AC voltage at the wall outlet This voltage should be ...

Страница 9: ...ply Disconnect the cable from the load unit Measure the voltage at the cable connector Is it the right polarity and voltage If you have a specific question not addressed in this manual please call 1 800 765 4SEI and ask for technical support ...

Страница 10: ...tant Green Fully Charged Flashing Green Charging Constant Red On Battery Fast Flash Red Adjust Supply Constant Green Fully Charged Flashing Green Charging Constant Red On Battery Fast Flash Red Adjust Supply Battery Charge Status Battery Charge Status Push to Test Battery DP140e Constant Green Battery Good Fast Fast Red Wait Then Test Slow Flash Red Replace Battery Fast Flash Red Adjust Supply ...

Страница 11: ...10 ...

Страница 12: ...11 ...

Страница 13: ...Central Office Lines 1 12 Power Connecti ons NT1 7 12 Cabling A NT1B 310 Card Cage Cabling A NT1 200 Card Cabling A NT1M 210 Appendix C 66 110 To Phones Power S T Power DC SEI DP Series Power U Interface from Service SEI DP Series Power U Interface from Service To 66 110 To 66 110 U Interface from Service SEI DP Series Power ...

Страница 14: ...13 ...

Страница 15: ...14 ...

Отзывы: