30
TD_MRI1_06.05_GB
6.4.8
Test circuit earth fault directional feature
Figure 6.3:
Test circuit
For testing relays with earth fault directional feature,
current and voltage input signals with adjustable
phase shifting are required. Figure 6.3 shows an ex-
ample of a single phase test circuit with adjustable
voltage and current energizing the
MRI1
relay under
test.
For testing a relay with earth fault directional feature,
one of the input energizing quantity (voltage) shall be
applied to the relay with a constant value within its ef-
fective range. The other input energizing quantity (cur-
rent) and phase angle shall be appropriately varied.
With the aid of phase angle indicated on the display
the correct function of the relay can be checked (ER-
relay type).
Parameters I
E>
and I
E>>
should be set to EXIT.
The following measured values are shown:
Measured value
LED
Earth current
E, I
E>
Active share
E, I
P
reactive share
E, I
Q
Earth voltage
E, U
E>
Angel E,
I
E>
, U
E>