Setting list
MRI1
Note !
All settings must be checked at site and should the occasion arise, adjusted to the object/item to be protected.
Project:
SEG job.-no.:
Function group: =
Location: +
Relay code: -
Relay functions:
Password:
Date:
Setting of the parameters
Default
Actual
Function Unit
settings
settings
I>S
Normal
Low set current at nominal voltage
x In
0.2
I>S
Low
Low set current at low voltage
x In
0.2
CHAR I>
Tripping characteristics
DEFT
tI>
Time delay at independent time
s
0.03
tI>
Time multiflier at dependent time characteristics
tI> Reset
Reset Modus for dependent time characteristics
I>>S
Normal
High set current at nominal voltage
x In
1.0
I>>S
Low
High set current at low voltage
x In
1.0
tI>> Time
delay
s
0.03
U
Threshold value for undervoltage setting
V
10V/20V/40V *
Rated frequency
Hz
50
RS Slave
address
1
All settings must be checked at site and should the occarision arise, adjusted to the object/item to be protected.
* thresholds dependent on rated voltage 100 V / 230 V / 400 V