SEFRAM DBX2000 Скачать руководство пользователя страница 12

 

 

AIR FLOW RATE 

CALCULATOR

 

 

 

Technical Notice             

 

  FI 72.0190.1021E 

 

Page 12 of  12 

 

NOTICE:

 

 

All of the parameters are recorded in the memory.  
If an error is detected at power up, the display indicates « Config. Error.  Code :X » where X represents an error 
code (0 if error is on the zero setting, 1 if error is on the measurement scale; if a problem occurs, contact us). 
In the event of a defect, the outputs 4-20mA are 0mA 
 

CALIBRATION: 

 

The device leaves our workshops, calibrated at 0, for zero pressure and at the maximum for the maxi pressure value 
of the range.  Settings done, device stabilised and at 20° C. 
It is possible to adjust the zero pressure: 
  - put the device off-pressure (disconnect both pressure inlets) 
  - in the pressure display mode, press the « left » button and keep it pressed 
  - press the « valid » button 
  - release the buttons: zero is set 
 

MAINTENANCE: 

 

The device does not require any special maintenance. However, to ensure the measurements are precise, an annual 
calibration is recommended especially with regard to « zero » (see CALIBRATION).

 

 

WARRANTY: 

 
The DBX2000 has a 2-year warranty (equipment returned to our workshops). The warranty does not apply in the 
following cases: 
- breakage through dropping or knocks to the unpackaged products, 
- damage caused by abnormal use (connecting error, surge, etc.) 
- any work on the device apart from the connections 
For ATEX devices : 
No intervention can be done on the device: this one must be sent back to our workshop. Otherwise, it may lose its 
homologation and warranty.

 

 

The unit must be returned to the following address: 

 

 

 

 

 
 
 

CONFORMITY: 

 
The DBX2000 device respect the European directives ( CEM and ATEX ), which concerns it. 
 
However, it must be used correctly in applications for which it is intended, and should be linked or near CE 
approved products. 

 

 

WE RESERVE THE RIGHT TO MAKE ANY CHANGES TO OUR DEVICES THAT WE CONSIDER APPROPRIATE. 

SEFRAM 

PLACE GUTENBERG 

59175 TEMPLEMARS 

FRANCE 

Содержание DBX2000

Страница 1: ...AIR FLOW RATE CALCULATOR Technical Notice FI 72 0190 1021E Page 1 of 12 SUPPLY VOLTAGE...

Страница 2: ...It is equipped as standard with 1 differential pressure sensor scale 0 100mmCE 2 alarm relays mini flow rate and maxi flow rate temperature correction manual input absolute pressure correction manual...

Страница 3: ...s the measurements and the results of the calculations of the DBX2000 to be displayed The parameters menu gives access to the device parameterisation The default display is the measurements menu If th...

Страница 4: ...The temperature alarm is activated The temperature value for the calculations is replaced by that entered manually see parameters menu 3 display of the absolute pressure measured by the sensor 4 calc...

Страница 5: ...ERS MENU movement from one step to the next is made with the valid button access to the parameter modification is made with the right button after modifying a parameter you come back into this menu fr...

Страница 6: ...analogue input or if the analogue input is defective 3mA if right button input of the temperature from 50 to 500 degrees C press valid button 4 absolute pressure display if no absolute pressure senso...

Страница 7: ...mat with the right and left buttons X XX XX X XXX XXX0 XXX00 XXX000 XXX being a value set from 000 to 999 press valid button 8 and 9 mini air flow and maxi air flow alarms display XXXX is the value of...

Страница 8: ...arm disappears the K2 led is extinguished the K2 relay is supplied contact between 21 and 24 Temperature alarm If the temperature is higher than the value set for longer than the time delay set or if...

Страница 9: ...24VDC Housing PC IP65 PRECAUTIONS For the supply version in 115V or 230VAC the DBX2000 leaves our workshops with the jumper positioned for use in 230VAC unless stated when ordering Check the position...

Страница 10: ...1 Electrics Bottom card user connections This card is accessible directly under the housing terminal cover At rest de energised contacts between C and NC 11 and 12 21 and 22 31 and 32 41 and 42 When...

Страница 11: ...AIR FLOW RATE CALCULATOR Technical Notice FI 72 0190 1021E Page 11 of 12 SPACE REQUIREMENTS AND FIXINGS...

Страница 12: ...e does not require any special maintenance However to ensure the measurements are precise an annual calibration is recommended especially with regard to zero see CALIBRATION WARRANTY The DBX2000 has a...

Отзывы: