Oil Smart® Simplex Panel

Installation Manual

Oil Smart® Simplex System:

The Oil Smart® OSSIM-30 System incorporates pump 

controls and alarm sensors that differentiate between 

oil and water, allowing companies to responsibly 

discharge the water without the risk of pumping oil. 

Installation of the Simplex Panel keeps companies 

in compliance with Elevator Code ASME A17.1 and 

State/Federal regulations while reducing the risk of 

adverse publicity, fines and expensive cleanup costs.

OSSIM-30

Single Phase 120/208/240V 60Hz.

(0-16.0 Pump Full Load Amps) 

Features:

• 

Oil Smart® and Liquid Smart® Controls with 20’ 

cords and mounting hardware

• 

NEMA 4X Panel Enclosure: Heavy Duty 

Polycarbonate, 10″x8″x4″, Clear Front

•  CSA International Certified No. 229294

• 

UL Listed for the United States and Canada

• 

High Liquid Alarm with Test and Silence Features, 

Red Beacon Alarm Light, White Light for Water 

Present, Yellow Light for Oil Present

• 

Alarm Horn that Sounds at 85 Decibels at 10 Feet

• 

Complete Panel Remote Monitoring Dry Contacts: 

Oil, Water, High Liquid

• 

HOA Switch and Green Light for Pump Run

Panel and Component Installation:

1.  Caution: To maintain the NEMA 4X rating, make 

all wiring connections with seal tight cable grips or 

conduit connections (supplied by end user).

2.  Determine mounting location for control panel. Mount 

panel using mounting feet supplied.

3.  The control panel should not be mounted in an 

area that is subject to submersion. 

4.  It is recommended to use separate 120VAC sources 

for the pump and alarm circuits.

5.  Run pump cable, Liquid Smart® cable, and Oil 

Smart® cable through conduit. Make field connections 

as shown on wiring diagram.

6.  Run power line conductor through conduit. Wire to 

terminals per enclosed schematic. Branch circuit 

protection to be provided by end-user.

7.  Mount Oil Smart Pump Control and Liquid Smart 

Sensor with provided mounting hardware to pump 

discharge pipe. The off sensor of the Oil Smart Switch 

shall be positioned at least 3” above the impeller 

of the pump. The Liquid Smart Sensor shall be 

positioned at the appropriate high liquid level point.

Start up:

1.  When power is applied, the green power light located 

on the white front swing panel shall light.

2.  The Pump HOA Switch shall be placed to the A (auto) 

position to ensure the system will pump. The pump 

can be tested or turned on manually if the HOA switch 

is in the H (Hand-Manual) position.

To test the alarm circuit, push the test button on the front 

panel, the audible alarm shall sound and the red beacon 

will light.  

Service:

Caution: Before checking electrical connections within 

the control or attempting to replace any components, 

turn off all branch circuits supplying power to the main 

control panel.

Protecting the Environment since 1995.

www.seewaterinc.com

or www.oilsmart.org

951.487.8073 • 888.733.9283

Email: [email protected]

121 North Dillon Avenue • San Jacinto, CA 92583

P.O. Box 1269 • San Jacinto, CA 92581

 l

a

ci

rt

c

el

E

 l

a

n

oi

t

a

N

 

e

h

h

ti

w

 

e

c

n

a

d

r

o

c

c

a

 

ni

 

e

b

 t

s

u

m

 s

n

oi

t

al

la

ts

ni

 ll

A   

 .

1

Code, and any other applicable state and local electrical 

requirements.

1. The switch and pump are not rated for explosive environments. 

This product is intended for hydraulic oils only.

IM 701, Rev. 0515