MR-2900 Installation Manual

1

1.0 Technical Information

1.1 General

The MR-2900 Fire Alarm Control Unit provides capability for up to 24 Input Circuits, 8 Polarity Reversing
Bell Circuits, network capabilities (with use of an MR-2910 Network Board) and 4 General Purpose Form
"C" Relays as well as system operated relays for alarm, trouble and supervisory indication. If the MR-2900
is ordered with a printer, it is ordered under the panel number MR-2920.

The Control Unit can be networked to provide additional input circuits, visual zones, bell circuits and relays.
Up to 40 Units (Control and/or Annunciator) can be connected to form the network. The network is a Style
7 (Data Communications Link, Redundant (DCLR)) loop.

All programming is done through the LCD and keypad. Input circuit programming and special features,
day/night mode, etc., are done from an externally generated database, while system parameters are
programmed from the LCD and keypad. For programming information, refer to 

LT-2011 MR-2900

Programming Manual

.

The basic MR-2900 Fire Alarm Control Unit consists of the:

Main Circuit Board (MR-2931) 

Terminal Board (MR-2936)

Annunciator Strip (MR-2902)

Power Supply (MR-2905)

Door Assembly (MR-2972) 

Back Box (MR-2971)

1.2 Main Circuit Board

The Main Circuit Board (MR-2931) provides system controls and visual indications, and contains the
system processor, programming port, printer port and non-volatile memory for system firmware. Software
is installed on the main board for critical functions such as programmable logic and timing functions and
non-critical functions, such as custom zone and devices messages. All jumpers on the board are for
diagnostic and test purposes. There are 6 LEDs in the middle of the right edge for diagnostic purposes.

The visual display consists of a series of LEDs for common system indication of power, alarm, supervisory,
and trouble. An LED clock display is provided to display real time. The flashing colon of the clock provides
visual indication of system processor operation. The clock also displays dashes if a major error/change
occurs. When this happens, the system requires a Hard reboot. A Hard reboot is done by pressing and
releasing the button inside the top of the inner door assembly.

The Circuit Board has an 80-character alphanumeric LCD. It provides descriptions for inputs, display of
archived events, first/last device in alarm, custom messages, etc. The keypad is used to scroll through the
display.

There are three connectors on the bottom of the Main Circuit Board, an audio output jack, a 9-pin service
terminal port and a 25-pin printer port. The ports are discussed below. The audio jack produces various
tones for use in walktesting of the system.

Содержание MR-2900

Страница 1: ...10 Rev 2 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be r...

Страница 2: ......

Страница 3: ...ions 26 5 1 General 27 6 0 Appendix B ULC Listed Compatible Smoke Detectors 28 6 1 ULC Listed Compatible Addressable Devices 30 7 0 Appendix C UL Listed Compatible Devices 31 7 1 UL Listed Class B Smo...

Страница 4: ......

Страница 5: ...Circuit Wiring 18 Figure 22 Style Z Class A Bell Circuit Wiring 19 Figure 23 Relay 19 Figure 24 Auxiliary Power Connections 19 Figure 25 Ribbon Cable Installation 20 Figure 26 Standard Network Wiring...

Страница 6: ......

Страница 7: ...Circuit Board MR 2931 provides system controls and visual indications and contains the system processor programming port printer port and non volatile memory for system firmware Software is installed...

Страница 8: ...e operating program Typical uses are a central station connection or remote LED annunciation of system status The operation of this port is software defined and requires the use of an MR 2109 x commun...

Страница 9: ...0 End of Line Resistor model EOL 471 Two wire smoke detectors cannot be used on this type of circuit Smoke Detector This is a supervised circuit supporting two wire smoke detectors only Both Class B u...

Страница 10: ...of origin Conventional Input Modules Model MR 2928 supports all seven classes of conventional circuits Smoke detector circuits are current limited to 80 mA while all other circuits are current limite...

Страница 11: ...r factor of 35 and are rated at 0 6A 30VAC 2 0A 30VDC The system defined Form C relays are for Alarm Supervisory and Trouble indication These relays have a power factor of 35 and are rated 1 0A 24VDC...

Страница 12: ...ontrol Unit with integrated printer are detailed below in section 1 11 1 10 Networking The basic MR 2900 Control Unit can be networked to other Control Units and Annunciator Units to provide additiona...

Страница 13: ...The printer uses thermal paper A Paper Advance button is on the right side of the Printer Compartment Cover If the paper runs out the printer stops printing To start printing after installing paper ho...

Страница 14: ...er Supply Transformer Terminal Board Hardware pack including 8 x NAC EOL resistors Door keys taped to outside of cabinet Installation manual and operating manual ALL CIRCUITS EXCEPT AUX POWER ARE SUPE...

Страница 15: ...m from getting lost or discarded 8 Open the Door to approximately 135o and lift up to remove the outer door from the backbox store door in a safe place Removing the MR 2900 Electronics A Removing the...

Страница 16: ...the wires provided the black wire to the black negative terminal and the red wire to the red positive terminal If the batteries need charging the Low Battery condition remains until they are charged R...

Страница 17: ...mm 8 1 2 216 mm 7 8 23 mm lip each side 3 4 19 mm lip top and bottom 4 102 mm 16 7 8 429 mm 26 1 2 673 mm 3 76 mm 29 740 mm 22 1 16 560 mm 27 1 2 699 mm 1 1 4 32 mm Battery shelf 7 8 23 mm lip each si...

Страница 18: ...Style B Class B Circuit This is a 2 wire power limited and supervised Style B Class B initiating device circuit using conventional normally open contact devices and an end of line resistor supported b...

Страница 19: ...is is a 4 wire power limited and supervised Style D Class A initiating device circuit using 2 wire smoke detectors and conventional normally open contact devices optional Maximum wire lengths are show...

Страница 20: ...t using addressable devices It requires the use of the MR 2929 or MR 2909 module Wire capacitance and resistance affects the allowable wire length The recommended wiring is twisted unshielded pair Con...

Страница 21: ...14 Use only approved devices Return wiring must be in a separate conduit When using isolators it is necessary to put an isolator between panel terminal blocks and the device Table 3 Maximum Wiring Len...

Страница 22: ...16 Addressable Modules The addressable module extended circuits are wired as shown on the next page in Figures 15 20 Figure 15 MRI M500M Wiring Figure 16 MRI M501 Wiring...

Страница 23: ...MR 2900 Installation Manual 17 Figure 17 MRI M502M Wiring Figure 18 MRI M500S Wiring for Signalling Circuits...

Страница 24: ...illustrated in Figure 21 Maximum wire lengths are shown in Table 4 Use only approved devices Note The inrush current of some devices may cause the current to exceed the 1 5A current limit momentarily...

Страница 25: ...Alarm Supervisory and Trouble relays have a power factor of 35 power limited at 5A 30VAC 1 0A 24VDC Auxiliary Power Circuits The auxiliary power circuits provide 24 VDC for external devices The polar...

Страница 26: ...MR 2944 Annunciator Unit are connected the same as the Control Unit Wiring is not polarity sensitive Network wiring is power limited Only COMLINK 1 is supervised for ground faults COMLINK 2 is superv...

Страница 27: ...sensitive MR D1010R Wiring Refer to LT 2048 MR D1010R Fiber Optic Module Installation Instructions Baud Rate Maximum Capacitance Maximum Network Nodes 9600 100 nF 254 4800 220 nF 254 2400 470 nF 254 1...

Страница 28: ...s wiring is 900m 3000 ft using 22 AWG The maximum length of power wiring is 300m 1000 ft using 18 AWG Evax System Wiring Notes For all EVAX installations the maximum wiring distance from the FACP to t...

Страница 29: ...ignalling Non coded Applicable Standards NFPA 70 and 72 UL 864 Rev 9 ULC S 524 ULC S 527 99 Input Initiating Device Circuits 24 Conventional Addressable Voltage 24 VDC 24 VDC Ripple Voltage 2 V p p N...

Страница 30: ...2910 Network Communication Module Both Ports Standard MR 2910 R1 Network Communication Module Port 1 RS 232 Port 2 Standard MR 2910 R2 Network Communication Module Port 1 Standard Port 2 RS 232 MR 29...

Страница 31: ...Both Ports RS 232 MR 2109 3 Port 3 Communications Board for connection to MR 2614 MR 2644 MR 2900 DACT and MR 2900 CITY MR D1010R1 Fiber Optic Module One Modem MR D1010R2 Fiber Optic Module Two Modem...

Страница 32: ...m Control Unit includes MR 2931 MR 2905 MR 2902 X 0 092 0 107 MR 2900 Unique LED s X 0 005 n a MR 2910 Network Communication Module X 0 005 0 005 MR 2938 Conventional Input Circuit Module X 0 018 0 10...

Страница 33: ...ell load for a relatively short time at the end of a 24 hour standby current drain This protection necessitates certain over sizing Regardless of the standby calculation and tables the battery must be...

Страница 34: ...HSC 220R 30 73595 73486 60 SIJ 24 NS6 220 30 73595 73497 60 SIJ 24 NS4 220 30 73594 73400 60 SIJ 24 HSC 220R 30 73405 73400 100 SLR 24 NS6 220 30 73594 73401 60 SLR 24 NS4 220 30 73405 73401 100 SLR...

Страница 35: ...SD 7130 70 201000 005 42 6269C 003 60 PSD 7128 70 201000 001 42 6270C 003 60 PSD 7126 70 201000 002 42 Apollo PSD 7126 70 201000 003 42 55000 325 30 PSD 7126 70 201000 005 42 55000 325 45681 251 255 2...

Страница 36: ...Intelligent Laser Some Sensor 330 MRI 5251P Thermal detector 200 MRI 5251B Thermal detector 300 MRI 5251RP Thermal detector w rate of rise 200 MRI 5251RB Thermal detector w rate of rise 300 MRI 5251H...

Страница 37: ...nsor 1400 A N A N A 100 A 1451 A B401 A 120 A 1451 A B401B A 120 A 2300T A N A N A 120 A 2300TB A N A N A 120 A 2400 A N A N A 120 A 2400TH A N A N A 120 A 2451 A B401 A 120 A 2451 A B401B A 120 A 245...

Страница 38: ...FE01A 120 A PSD 7135 P15FE1 CPD 002 FE02A 120 A PSD 7135 P15FE1 CPD 003 FE03A 120 A PSD 7135 P15FE1 CPD 005 FE05A 120 A PSD 7155 P55FE1 2 Wire FE51A 70 A PSD 7155 P55FE1 2WRLT FE52A 70 A PSD 7155 P55F...

Страница 39: ...F 24F HD 2 YBA M221 HB 4 102 A SIH 24F HD 3 HS 221D HB 4 130 A SIH 24F HD 3 YBA M221 HB 4 130 A SLK 24F HD 3 HS 221D HB 4 142 A SLK 24F HD 3 YBA M221 HB 4 142 A SLK 24FH HD 3 HS 221D HB 4 142 A SLK 24...

Страница 40: ...odel Standby Identifier Current System Sensor 1400 A N A N A 100 A 1451 A B401 A 120 A 1451 A B401B A 120 A 2400 A N A N A 120 A 2400TH A N A N A 120 A 2451 A B401 A 120 A 2451 A B401B A 120 A 2451 A...

Страница 41: ...Strobe Horn Dual Input 17 88 EH EL1 WM 24 VF R Electronic Strobe Horn Dual Input 17 88 AES DL1 WS 24 VF R Multi tone Horn w Strobe 50 Hi 25 Lo 25 AES EL1 WS 24 VF R Multi tone Horn w Strobe 50 Hi 25 L...

Страница 42: ...2475W Strobe Horn 163 combined NS 24110W Strobe Horn 195 combined NS4 2415W Strobe Horn 28 57 NS4 241575W Strobe Horn 28 72 NS4 2430W Strobe Horn 28 85 NS4 2475W Strobe Horn 28 140 NS4 24110W Strobe...

Страница 43: ...243OW Strobe Chime 20 85 CH70 2475W Strobe Chime 20 140 CH70 24110W Strobe Chime 20 169 CH90 2415W Strobe Chime 20 53 CH90 241575W Strobe Chime 20 68 CH90 2430W Strobe Chime 20 85 CH90 2475W Strobe C...

Страница 44: ...Commander2 Horn Strobe 75 cd 110 combined GEC24 110 Commander2 Horn Strobe 110 cd 123 combined GMS24 15 Mechanical Horn Strobe 15 cd 116 combined GMS24 15 75W Mechanical Horn Strobe 15 75 cd 131 combi...

Страница 45: ...0 75 cd 172 combined SHG24 60 Electronic Horn Strobe 60 cd 145 combined SHG24 110 Electronic Horn Strobe 110 cd 250 combined ST24 15 Commander Strobe 15 cd 45 ST24 15 75 Commander Strobe 15 75 cd 57 S...

Страница 46: ...M Strobe 125 SS24MC Strobe 125 SS24LOLA Strobe 80 MASS24LO Electronic Sounder Strobe 59 45 MASS24LOC Electronic Sounder Strobe 59 45 MASS24LOLA Electronic Sounder Strobe 59 80 MASS24M Electronic Sound...

Страница 47: ...SS241575ADAS Strobe 180 MASS2415ADAS Horn Strobe 59 125 MASS241575ADAS Horn Strobe 59 180 RP2415ADA Strobe 90 RP241575ADA Strobe 120 RP2475ADA Strobe 200 RP24110ADA Strobe 245 Model Type Input Current...

Страница 48: ...each device for details of installation wiring and proper application Manufacturer Model Type Secutron MRI 1251B Ionization type smoke detector MRI 2251B Photoelectric type smoke detector MRI 2251TB P...

Страница 49: ...etector 5251RP Thermal detector w rate of rise 5251RB Thermal detector w rate of rise 5251H High Temperature Thermal detector IM 10 10 Input Monitor Module CR 6 6 Relay Control Module SC 6 6 Supervise...

Страница 50: ...m relay as follows Trouble and supervisory contacts must be connected to the panel Note The Radionics 2071C and 2071AC are separately listed equipment Refer to the installation and wiring instructions...

Страница 51: ...ontacts must be connected to the panel Note The Silent Knight 5104 is separately listed equipment Refer to the installation and wiring instructions provided with the unit Figure 32 MR 2900 and Silent...

Страница 52: ...ating Voltage 24 VDC Standby Current 2 mA Alarm Current 1 5 A less than 10 milliseconds for Model DC 2A Master Box UL listed File S3610 City Tie Box Series type Coil Resistance 14 5 ohms The CTM is wi...

Страница 53: ...2900 are wired together as shown below Addressable control modules cannot be used with the Keltron 3158 TTM Note The Keltron 3158 TTM is separately listed equipment Refer to the installation and wirin...

Страница 54: ...complete system test to ensure that the system operates as intended Failure of Replaceable Batteries Systems with wireless transmitters have been designed to provide several years of battery life und...

Страница 55: ...ain periods of time Also the telephone lines may be compromised by such things as criminal tampering local construction storms or earthquakes Insufficient Time There may be circumstances when the syst...

Страница 56: ...e installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintenance damage arising out of any othe...

Страница 57: ...ny shipment whatsoever for which prior authorization has not been obtained Products which Secutron Inc determines to be repairable will be repaired and returned A set fee which Secutron Inc has predet...

Страница 58: ......

Страница 59: ......

Страница 60: ...Niagara Falls New York 14305 Tel 888 SECUTRON 888 732 8876 Fax 905 660 4113 No part of this publication may be reproduced transmitted transcribed stored in a retrieval system or translated into any la...

Отзывы: