Mounting 

 

ASD 535, Mounting and installation, T 140 333 d en 

19 / 40 

2.5.6 

Mounting the sampling pipe 

 

Notice 

When mounting the sampling pipe, the points be-
low must be observed and adhered to (see 

Sec

 

2.5.5): 

  Clips and pipe clamps at 1 m intervals are used to fasten 

the sampling pipe. 

  The tubes must be cut with a pipe cutter to required 

lengths. In doing so, ensure that the cut is at a right-angle 
to the tube axis. Any projecting burrs must be removed 

Fig. 6

. 

  The ends of the individual tube pieces are to be slightly 

angled with a suitable tool, e.g. slightly bevel with a pipe 

peeler

Fig. 6

. 

  The individual pipe sections are connected to each other 

with fittings. Depending on the used tube material, gluing 

as described in Sec. 

 

2.5.2  and 

 

2.5.3  or pressing as de-

scribed in Sec. 

 

2.5.4  is used. The tubes are pushed into 

the fittings to the stop, 

Fig. 7

. 

  The connection points must be absolutely sealed to pre-

vent the wrong air from entering. 

  For vertically arranged sampling pipe or parts thereof (e.g. 

in a riser or high-rack storage building) make certain that 
the tubes cannot slide down (fasten clips directly under fit-

tings as shown i

Fig. 8

). 

  The sampling pipe must be fastened so that the tube can 

“work” in the clips (linear expansion, see Sec. 

 

2.5.5). 

  Beginning at the branching points of the sampling pipe, a 

distance of at least 0.2 m must be maintained from the T-

piece to the clips

Fig. 9

. 

  For changes of direction in space surveillance installations, 

it is advisable to use 90° bends rather than 90° angles, 

Fig. 9

. 

  When using flush mounting or in false ceilings, it must be 

ensured that the tubes are not able to vibrate. 

  How the tubes are laid out – especially for flush mounting 

– must be precisely entered in the dimensional data in the 
installation plans. 

 

 

Fig. 6  Cutting the tubes 

 

 

Fig. 7  Joining the tubes 

 

 

Fig. 8  Vertical sampling pipe 

 

 

Fig. 9  90° bend, branching point 

Angled cut

Pressure points

Burrs

Bevel

approx. 30º

wrong

correct

wrong

correct

Tube

Sleeve Stop

Tube

Sleeve

Clip 

below 

fitting

Vertical sampling pipe

90º arc

ASD 535

0,2 m

0,2 m

0,2 m

0,2 m

T-piece

End cap

Clip

Clip

90º arc

Содержание ASD 535

Страница 1: ...Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 140 333 d en ASD 535 Aspirating Smoke Detector Mounting and installation Beginning with FW version 01 08 xx...

Страница 2: ...ch The product hardware software and technical documentation is subject to the copyright of the manufacturer Any prohibited modification misuse copying or prohibited sale of this product represents a...

Страница 3: ...version Production version FW version from 300418 from 01 08 xx The validity of older production versions and firmware versions is guaranteed with the exception of the new func tionalities described...

Страница 4: ......

Страница 5: ...e sampling pipe 20 2 5 7 2 Transition to flexible tube 21 2 5 8 Making the sampling holes 22 2 5 9 Mounting maintenance and sampling hole clips 22 2 5 10 Mounting the sampling funnel 22 2 5 11 Mountin...

Страница 6: ...1 Detector housing and accessories 37 4 2 Sampling pipe and accessories 37 _________________________________________________________________________________________ 5 Technical data 38 ______________...

Страница 7: ...is available in four versions ASD 535 1 for 1 sampling tube without smoke level indicator for 1 smoke sensor ASD 535 2 for 2 sampling tubes without smoke level indicator for 2 smoke sensors ASD 535 3...

Страница 8: ...The product may represent a possibly imminent danger with a medium level of risk to persons if the notice is not duly observed If the danger is not avoided death or serious injury may result Caution...

Страница 9: ...rd with smoke level indicator Advanced Control Board AFS 35 Air Flow Sensor AFU 35 Aspirating Fan Unit Al Alarm AMB 35 ASD Main Board ASD Aspirating Smoke Detector ASD Config Configuration software fo...

Страница 10: ...emi conductor relay Port Input or output component PVC Polyvinyl chloride plastic RAM Memory component RIM 35 Relay Interface Module RoHS Restriction of Certain Hazardous Substances environmentally fr...

Страница 11: ...s listed below are required for mounting and installation sorted by the sequence of use in this document Opening the detector housing Flat blade screwdriver no 5 8 mm Removal of pipe plugs Flat blade...

Страница 12: ...of the paint to the tube The following materials are available Material Connection method PVC polyvinyl chloride contains halogen Gluing ABS acrylonitrile butadiene styrene contains no halogen Gluing...

Страница 13: ...special adjustments larger airflow window longer delay time etc may have to be performed for the sampling pipe and on the detector housing This also applies to temperature dif ferences of more than 2...

Страница 14: ...e detector housing After the detector housing is open the four mounting holes in the housing base are accessible To facilitate mounting work remove the entire housing cover of the detector housing inc...

Страница 15: ...th fitted pipe plugs tube network I and II entries Similarly all cable screw unions are closed The pipe plug is removed on entry I for ASD 535 1 and 3 and on entry II for ASD 535 2 and 4 For ASD 535 1...

Страница 16: ...from the device undo the flat cable Depending on the device version there is a different number of labelling strips printed on both sides in the control unit ASD 535 1 1 x A ASD 535 2 1 x A ASD 535 3...

Страница 17: ...instructions must be followed Before gluing use household paper to remove dust and grease deposits from the surfaces to be glued do not use textile cloths If the tube parts are very dirty a cleaning a...

Страница 18: ...ance of taking linear expansion into account increases as the temperature at the time of installation deviates from the usual operating temperature Linear expansion can be calculated as follows Calcul...

Страница 19: ...ertically arranged sampling pipe or parts thereof e g in a riser or high rack storage building make certain that the tubes cannot slide down fasten clips directly under fit tings as shown in Fig 8 The...

Страница 20: ...sible to quickly remove the sampling fixture or the sampling pipe during maintenance work on the monitored objects The click pipe clamps are screwed onto the support rails by means of threaded plates...

Страница 21: ...of ABS is used The flexible tube can be easily snapped into the quick release coupling and for maintenance work it can be easily snapped out Notices It is imperative to implement the interfaces of th...

Страница 22: ...le of 8 5 mm is made in the sampling pipe uniform The holes are made at a right an gle to the centre of the pipe axis as shown in Fig 12 The sampling hole clips are available in various sizes 2 0 2 5...

Страница 23: ...f the ASD PipeFlow calculation software Notices It is imperative to implement the interfaces of the flexible tube cleanly so that the sealing ring does not become damaged in the quick release coupling...

Страница 24: ...box and or filter unit Filter box filter unit dirt trap box dust retaining box and water retaining box must always be mounted under the detector housing The water retaining box or dust retaining box m...

Страница 25: ...ing for the electrical installation If needed two reserve holes blind plugs can be fitted with two more cable screw unions 1 x M20 1 x M25 The cable screw unions are suitable for cable with an externa...

Страница 26: ...resulting from mounting the detector housing must be removed The installation position of the smoke sensors depends on the particular smoke sensor chamber I or II The installation posi tion is always...

Страница 27: ...SD memory card or when subse quently removing an expansion module e g if not used the expansion module must first be logged off via op eration on the AMB 35 Main Board switch setting o When installing...

Страница 28: ...ew terminals Individual terminal blocks are built on for supply voltage relay contacts inputs outputs etc Notices Inside the detector housing the lines should be conducted the shortest possible path t...

Страница 29: ...t opto isolator input Wiring acc to Fig 20 and Fig 22 20 Reset external input opto isolator input 21 F power supply F may be available at a later date 22 DF Asynchronous data line F 23 0 V power suppl...

Страница 30: ...ogrammable 14 NC 15 COM Notice Depending on the device version the assigned criteria signals upon product delivery apply to smoke sen sor I on the first RIM 35 connected to the AMB 35 and to smoke sen...

Страница 31: ...termine the required power supply and cable cross section it is essential to perform the calculations described in sec tion Planning T 131 192 For applica tions with redundant power supply the cal cul...

Страница 32: ...1 A should always be used e g PMR 81 semi conductor relay see Fig 21 C The ASD supply path via the auxiliary relay contact must be short circuit proof or con ducted via a fuse component circuit breake...

Страница 33: ...ly fromFACP from line plus local supply from OC output via relay or PMR 81 supply from FACP from OC output via PMR 81 or relay local supply from relay contact of control module supply from FACP or loc...

Страница 34: ...ency can also be programmed in the FACP In that case the same applies as in B both sampling pipes from one monitoring area or merging of a sampling pipe on tube input I and II If wiring as in Fig 23 C...

Страница 35: ...5 50 units per SecuriFire Integral addressable loop 62 units country specific regulations and guidelines must be ob served Fig 25 Wiring from XLM 35 SLM 35 Notices There are two switches S1 and S2 on...

Страница 36: ...ways identical with the programming on relay 3 of the AMB 35 Fig 26 Wiring the OC outputs Notices When connecting inductive consumers e g relays a freewheel diode is to be installed directly at the co...

Страница 37: ...00613 2203 eXtended Line Module XLM 35 including mounting set 11 2200003 01 XX SecuriLine module SLM 35 including mounting set 4000286 0101 Relay Interface Module RIM 35 including mounting set 4000287...

Страница 38: ...ent conditions Detector housing temperature range 30 60 UL max 40 C Temperature range of detector housing to Australian Standard AS 1603 8 30 55 C Sampling pipe temperature range 30 60 C Temperature r...

Страница 39: ...ching point 19 Fig 10 Screw free fastening of a sampling fixture 20 Fig 11 Transition from fitting to flexible tube 21 Fig 12 Making the sampling holes 22 Fig 13 Mounting clips 22 Fig 14 Using samplin...

Страница 40: ...c Notice about screening observe manufacturer s specifi cations of the FACP and SecuriFire Integral addressable loop Rectification 4 1 c Cable screw union in set of 10 industrial SD memory cards Corr...

Отзывы: