Data Sheet 

2 / 4 

T 811061 en f 

CCD 573X 

Planning  

The  country-specific  directives  apply  when  planning  and  installing 
automatic fire detector systems. 
For combined fire detectors (CCD 573X) additional directives may 
apply if one of the detection properties is continuously or temporar-
ily deactivated. 
 
The  following  table shows  all  of  the  possibilities  for combining  the 
modes of operation and the recommended planning directive. 
 

Mode of operation

 

Planning 

compliant 

with

 

Smoke 

Heat 

CO 

EN 54-7 CUBUS 

 

 

EN 54-7 

EN 54-7 CUBUS 

EN 54-5 

 

EN 54-7 

EN 54-7 CUBUS 

EN 54-5 

EN 54-26 

EN 54-7 

EN 54-7 CUBUS 

 

EN 54-26 

EN 54-7 

EN 54-7 CUBUS 

EN 54-30 

 

EN 54-7 

EN 54-7 CUBUS+ 

 

 

EN 54-7 

EN 54-7 CUBUS+ 

EN 54-5 

 

EN 54-7 

EN 54-29 

 

 

EN 54-7 

EN 54-29 

EN 54-5 

 

EN 54-7 

EN 54-29 

 

EN 54-26 

EN 54-7 

EN 54-29 

EN 54-30 

 

EN 54-7 

EN 54-29 

EN 54-30 

EN 54-26 

EN 54-7 

 

EN 54-5 

 

EN 54-5 

 

EN 54-5 

EN 54-26 

EN 54-5 

 

EN 54-30 

 

EN 54-5 

 

 

EN 54-26 

No recommenda-

tion 

 

 

Under normal ambient conditions an operating time 
of  up  to  7  years  is  possible;  however,  it  is  abso-
lutely  necessary  that  the  detector  is  commissioned 
no  later  than  7  months  after  the  production  date 
(see product identification). 

 

 

It  is  imperative  that  the  maximum  permitted  ambi-
ent temperature is observed; if not, the CO cell may 
be destroyed. 

 

 

Increased concentrations of hydrogen or alcohol in 
the ambient air may cause CO false alarms. 

 
 

Mounting/installation  

Mounting  and  installation  of  the  CCD  573X  is  accomplished  with 
the assembly base series USB 502. 

  USB 502-1  Standard base for surface mounting  

  USB 502-2  Base for flush mounting in dropped ceilings 

  USB 502-3  Base for damp rooms 

  USB 502-4  Base for flush mounting in concrete 

  USB 502-6  Standard base surface mounting without loop con-

tact 

  USB 502-20 Standard  base  with  illuminated  ring  without  loop 

contact 

 
The specifications in the data sheets shall apply for installation; de-
tector base series USB 502. 

Connection 

 

The maximum number of detectors on an address-
able loop has to be calculated. It must take into ac-
count  power  consumption,  the  installation,  other 
line  participants  and  the  applicable  directives  and 
regulations. 

 
The  electrical  connection  in  the  USB  502  base  is  with  terminal 
strips.  The  electrical  connection  between  detector  and  base  is  by 
means of a 5-pin plug connector. 
 

Terminal  Signal 

SecuriFire  

GND  

C1/C2 

DATA A 

L1 

DATA B 

L2 

GND

 

Alarm output 

 

   +

 

Alarm output 

 

Support point (screening) 

Screen 

 

 

Terminal  5  (alarm  output)  may  be  loaded  a  maxi-
mum of 5 mA, 1 mA or 0.1 mA. 

 
The connections of the USB 502 base are designed so that when 
the CCD 573X is removed the SecuriLine eXtended is closed. 
The USB502-6/USB502-6MC und USB502-20 bases do not have a 
loop  contact.  When  removing  the  detector  from  these  bases,  the 
SecuriLine eXtended is therefore not closed! 
A short-circuit disconnecter in the CCD 573X ensures that a short-
circuit  in  the  installation  (loop)  is  isolated  in  the  area  of  the  dam-
age. This allows the detectors to continue functioning unimpeded. 
 

Exception: 

Under  the  following  conditions  it  may  occur  that  detectors  are  no 
longer recognised on the SecuriLine eXtended: 

 

Detector defect (short-circuit or interruption)  

 

More than one short-circuit or interruption before and after the 
detector 

 

Short-circuit or interruption in stub line 

 

SecuriFire connection 

 

 

Fig. 2  CCD 573X connection 

 

USB 502    

1   

3    

4    

5    

6    

2    

GND

Data A

Shield

Data B

Alarm output
Plus     GND

6 5 4 3 2 1 

Shield
L2
C2

Shield

L1
C1

Содержание 988.975850

Страница 1: ...O gas pre signal adjustable in the range of 20 to 320 ppm does not correspond to any standard CO gas maintenance alarm Fault messages Ageing optical fault voltage supply fault NTC short circuit and interruption CO gas sensor fault EEPROM memory fault overtemperature Key features of the CCD 573X are Digital signal processing Alarm threshold tracking Temperature compensated smoke element Signature a...

Страница 2: ...s USB 502 4 Base for flush mounting in concrete USB 502 6 Standard base surface mounting without loop con tact USB 502 20 Standard base with illuminated ring without loop contact The specifications in the data sheets shall apply for installation de tector base series USB 502 Connection The maximum number of detectors on an address able loop has to be calculated It must take into ac count power con...

Страница 3: ...etector self test that automatically subjects the detectors to an extensive electronic function check They are also equipped with automatic soiling compensation It is nevertheless necessary that all active sensors of the detector undergo a physical and functional check on site for their set modes of operation at regular intervals Securiton recommends the following Maintenance and inspection work s...

Страница 4: ...on 2 conductor technology Operating voltage range incl modulation amplitude 7 to 31 VDC Power consumption When quiescent When alarm Alarm LED active Alarm output active 5 mA 1 mA 0 1 mA Typically 150 µA max 190 µA Max 20 mA pulsed Max 2 5 mA Max 7 5 mA 2 1 mA 0 7 mA Alarm output2 3 Output voltage Output voltage short circuit proof 5 0 VDC 1 V 0 3 V Min 5 mA min 1 0 mA min 0 1 mA Line isolator Rate...

Страница 5: ...5 base variants green terminal block are equipped with a loop contact This means terminals 2 and 3 are connected and are opened automatically when the detector is in serted On the 573 and MMD detector series the connection and thus also the ring is closed again when the detector is removed On the 563 detector series the connection remains open and the control panel signals a fault The USB 502 6 US...

Страница 6: ... the cable must be fitted with a drip nose before it reaches the base This applies in particular to flush mounting in stallations in wet rooms garages etc In such applications the bases must be mounted next to the flush mounting concrete box and openings C or D must be used for inserting the cable see Fig 4 The base has no strain relief The cable entry can be made ei ther from the rear through the...

Страница 7: ...ith the integrated claw fittings or using two screws fastening holes Insert the protective ring covers the screws afterwards together with the detector Fig 6 USB 502 2 installation Installation notes for USB 502 3 The USB 502 3 base variant is specially designed for use in wet rooms and consists of Mounting box with four cable inserts PG 13 5 and stopper plugs USB 502 1 standard base Sealing ring ...

Страница 8: ... and USB 502 8 Ex i base variants are permit ted for use in Ex zones in combination with the MMD 130 Ex i multi criteria detector The MMD 130 Ex i fire detector may only be oper ated with the USB 502 USB502 and using a Z787 Z787F or GTW 01 02 The safety barrier and GTW must be installed in the safe area The fire detector base is intended for surface mounting The Ex i detector is secured in the bas...

Страница 9: ...rved during connection Connection examples Fig 8 USB 502 connection with line technology Fig 9 USB 502 connection with addressable loop technology Dimensioned drawings Fig 10 USB 502 1 USB 502 6 USB 502 8 Ex i Fig 11 USB 502 2 Fig 12 USB 502 3 Fig 13 USB 502 4 Fig 14 USB 502 5 Fig 15 USB 502 7 Ex i Fig 16 USB 502 20 GND 1 3 4 5 6 2 SHLD L1 L2 1 3 4 5 6 2 SHLD GND L1 L2 SHLD 3 K Final detector GND ...

Страница 10: ...ring MC multicolour 988 943584 3110464 DNP 502 detector number plate 322 265242 31 3100001 01 01 DNP 521 531 detector number plate optional 322 215880 3110320 Replacement sealing ring for USB 502 3 3210296 Technical data Power consumption only USB 502 20 Typically 0 9 mA Illuminated ring only USB 502 20 Colour Visibility Flashing frequency Light intensity Red on alarm transmission 360 1 2 to 3 Hz ...

Отзывы: