Note:
Max relay power rating
with resistive load is 2A@24V DC or AC;
0.5A@115VAC. Use an interposing relay to switch greater loads.
The RK600e does not supply power to operate electric strike or
magnetic locks - a separate supply is required. Refer to strike/
magnetic lock manufacturers instructions.
Users can request to exit through the controlled door without using a tran-
sponder (and without causing an alarm condition), by pressing an Exit button
or triggering the relay output of an Exit PIR connected to the RK600e Unit.
This will operate the latch relay for the programmed latch time.
When wiring the REX Input, connect the brown wire to one side of the REX
switch contact and connect the other side of the switch to the orange wire.
This input must be a dry contact, with no voltage present.
Use a Separate Power Supply for Electric Locks
The access control unit and the electric locking device should be
connected to separate power supplies. Install the MOV provided as
shown below:
Auxiliary Reader Wire Connections
A short cable assembly extends from the back of the Optional Auxiliary
Reader. Connect Plug P2 at the end of the cable to Socket J2 at the RK600e
Unit. If the cable must be extended,
for the best performance, use TWO
SEPARATE CABLES:
one unshielded, non-twisted, two-conductor wire
to the antenna coil (Pins 1 & 2), plus a
SEPARATE
4-conductor shielded
cable to the LED and Beeper (Pins 3 - 6). These cables can be run in the
same conduit. Connect the cable shield from the LED/Beeper cable to the
black wire (GND) on P1 at the RK600e.
Route the auxiliary reader cable at least two feet away from sources of EMI
(electro-magnetic interference), such as radio transmitters, elevators, large
electric motors or fluorescent light ballasts.
Figure 2 - MOV Wiring Diagram