background image

4mA ZERO SET

The 4mA ZERO SET trimpot sets zero speed when a 4-20mA input signal is used.  

Maximum Speed (MAX)

The MAX setting determines the motor speed when the speed adjust potentiometer
is turned full CW.

Rotate the speed adjust potentiometer full CW.  Using a hand-held tachometer or
analog frequency meter as a reference, adjust the MAX trimpot until the desired
speed or frequency is reached.

Minimum Speed (MIN)

The MIN setting determines the motor speed when the speed adjust potentiometer is
turned full CCW.  It is factory set to zero speed.  The MIN setting range is 0 to 30%
MAX setting.

To calibrate MIN, turn the speed adjust potentiometer CCW.  Adjust the MIN trimpot
until the motor has stopped (for zero speed setting), or is running at the desired
minimum speed.

Deceleration Time (DECEL)

The DECEL setting determines the time the motor takes to ramp to a lower speed.
Decel is factory set for the fastest deceleration time (full CCW).

To set the deceleration time:

1.  Set the speed adjust potentiometer to maximum (full CW) and wait for the

motor to come to maximum speed.

2.  Set the speed adjust potentiometer to minimum speed (full CCW) and note the

time the motor takes to decelerate to minimum speed.

3.  If the deceleration time differs from the desired time, adjust the DECEL trimpot

until the desired time is reached.  Rotating the DECEL pot CW increases the
deceleration time.

Acceleration Time (ACCEL)

The ACCEL setting determines the time the motor takes to ramp to a higher speed.
ACCEL is factory set for the fastest acceleration time (full CCW).

To set acceleration time:

1.  Set the speed adjust potentiometer to zero (full CCW) and wait for the motor to

come to a stop (or minimum speed).

2.  Set the speed adjust potentiometer to maximum speed (full CW) and note the

time the motor takes to accelerate to maximum speed.

3.  If the acceleration time differs from the desired time, adjust the ACCEL trimpot

until the desired time is reached.  Rotating the ACCEL trimpot CW increases
the acceleration time.

Slip Compensation (SLIP COMP)

The SLIP COMP setting controls speed regulation during load changes.  
The SLIP COMP range is 0 - 5 Hz at base speed and load.

Increase the motor speed to maximum.  Slowly load the motor until the  AC phase
current is at its maximum (100%).  If the motor shows any signs of slowing, rotate the
SLIP COMP trimpot CW until the motor shaft rotates at the original set speed.

BOOST

The BOOST setting is used to increase motor torque at low speeds.  The minimum
setting is sufficient for most applications and does not need to be adjusted.  If the
motor stalls or runs too slowly due to excessive slip at very low speeds (below 10 Hz),
the boost trimpot may need adjustment.

To adjust the BOOST setting:

1.  Run the motor at the lowest continuous frequency/speed required.
2.  Monitor the motor phase current (with a true RMS meter) while very slowly

turning the BOOST trimpot CW until the motor operates properly, or 100% of
the motor nameplate current is reached.

Note:  Use the absolute minimum amount of BOOST necessary to achieve proper
motor operation.  Improper use of the BOOST feature may cause motor and/or drive
overheating and failure.  If proper motion operation cannot be achieved with the
above procedure, please contact your Danaher Motion representative for assistance.

TORQUE LIMIT

The TORQUE LIMIT setting determines the maximum torque for accelerating and
driving the motor.  TORQUE LIMIT is factory set at 100% of rated motor current.
Althought the TORQUE LIMIT trimpot can be set up to 100% of the drive nameplate
rating, continuous operation beyond the drive nameplate rating may cause damage to
the motor and/or drive.

To set the torque limit:

1.  With no power applied to the drive, connect a (true RMS) ammeter in series with

one of the motor leads.

2.  Set the TORQUE LIMIT trimpot to full CCW.
3.  Carefully lock the motor shaft.  Ensure that the motor is firmly mounted. 
4.  Apply line power.  The motor should be stopped.
5.  Set the speed adjust potentiometer to maximum speed.  The motor should

remain stopped.

6.  Slowly rotate the TORQUE LIMIT trimpot clockwise (CW) until the ammeter

reads 100% of maximum motor current.

7.  Set the speed adjust potentiometer to zero speed.
8.  Remove power from the drive.
9.  Remove the lock from the motor shaft.
10.  Remove the ammeter in series with the motor lead.

BRAKE CURRENT

The BRAKE CURRENT setting controls the amount of braking current applied,
ranging from 0 - 100% of drive rating.  

To set brake current:
Rotate the BRAKE CURRENT trimpot CW to increase the amount of current applied.
Rotate the BRAKE CURRENT trimpot CCW to decrease the amount of current
applied.

BRAKE TIME

The BRAKE TIME setting controls the amount of time brake current is applied to the
drive.  The BRAKE TIME range is 1 to 10 seconds.

To set the brake time:
Rotate the BRAKE TIME trimpot CW to increase the amount of time the drive takes to
break.  Rotate the BRAKE TIME trimpot CCW to decrease the amount of time the
drive takes to brake.

C A L I B R A T I O N   S E T T I N G S

J U M P E R   S E T T I N G S

JMP504

JMP504

JMP503

JMP505

JMP506

1 & 2 for Voltage Input
2 & 3 for Current Input

1 & 2 to Coast
2 & 3 to Brake

1 & 2 to Trip
2 & 3 to Restart

1 & 2 for 115VAC
2 & 3 for 230VAC

TRIP:
Drive has a low voltage fault & must be
manually re-enabled to restart.

RESTART:
Drive has a low voltage fault & will
momentarily stop then auto-restart when
input voltage returns to minimum level.

115 = 115 VAC INPUT DOUBLER MODE
230 = 230 VAC INPUT MODE

1 = 0 - 5 VDC INPUT
2 = 0 - 10 VDC INPUT
3 = 4 - 20 mA INPUT

1    2    3

1      2      3

JMP503

1    2    3

1    2    3

1    2    3

JMP505

JMP506

BRAKE

COAST

T

TRIP

RESTART

UV

JMP501

JMP501

115V

230V

WARNING!

Using 230 VAC input in Doubler mode
will damage the drive!

1-Phase Input  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .* 115/230 VAC

1 or 3 -Phase Output  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .230 VAC

Maximum Horsepower  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 HP

Maximum Continuous Output Current  . . . . . . . . . . . . . . . . . . . . . . . † 4.0 AC

AC Amps In  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 / 10 amps

AC Voltage Input Range . . . . . . . . . . . . . . . . . . . . . . . . .115/230 VAC ± 10%

50/60 Hz single phase

Standard Carrier Frequency  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 KHz

Output Frequency Range  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 - 120 Hz

Adjustable Maximum Output Frequency Range  . . . . . . . . . . . . .30 - 120 Hz

Acceleration Time Range  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 - 12 secs

Deceleration Time Range  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 - 12 secs

Analog Input Voltage Range

(S1 [-] to S2 [+])  . . . . . . . . . . . . . . . 0 - 5 VDC, 0 - 10 VDC, 4 - 20 mA

Input Impedance, S1 to S2  . . . . . . . . . . . . . . . . . . . . . . . . . . . .~ 100K ohms

Vibration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.5G max (20 - 50 Hz)

0.1G max (> 50 Hz)

Weight  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 lbs

Ambient Operating Temperature Range  . . . . . . . . . . . . . . . . . . . .10° - 40° C

S P E C I F I C A T I O N S

*  Connect only 115 VAC line input to the 115 VAC terminals.  Application of 230 VAC line input when set for

115 VAC will result in severe damage to the motor and drive.

†  Derate current by 2% per degree if the operating temperature is above 40°C.  Under no circumstances may

the ambient temperature exceed 55°C.

Отзывы: