PrimeTest 250+
Operating Instructions
25
•
Check that the appliance power switch is in the
ON position. The test will automatically proceed
if the appliance power switch is placed in the ON
position.
•
If the
LO LOAd
enunciator remains on the
display, the load presented by the appliance may
be too small for the PrimeTest 250+ to detect. In
this case, press the CLII test key to continue.
•
The PrimeTest 250+ will perform an Insulation
test. If the Insulation Resistance is greater than
the factory set limit a tick is placed next to the
Riso
enunciator. If the Insulation Resistance is
less than the set limit a cross is placed next to
the
Riso
enunciator, the
FAIL
enunciator is
displayed and the test sequence is halted.
Note
:
If a mains supply is detected, the
PrimeTest 250+ will perform a touch
leakage test.
If the PrimeTest 250+ does not detect a
mains supply then the PrimeTest 250+ will
perform a substitute leakage test.
•
If a Substitute Leakage test is performed then
the PrimeTest 250+ will start the test without the
need for user intervention. If the Substitute
Leakage is less than the factory set limit a tick is
placed next to the
I
EA
enunciator.
Содержание 403A910
Страница 1: ...Operating Instructions...
Страница 9: ...PrimeTest 250 Operating Instructions 8 Figure 1 PrimeTest 250 Front View...
Страница 11: ...PrimeTest 250 Operating Instructions 10 Figure 4 Testing CLII appliances no mains leakage...
Страница 12: ...PrimeTest 250 Operating Instructions 11 Figure 5 Testing CLI appliances mains leakage...
Страница 13: ...PrimeTest 250 Operating Instructions 12 Figure 6 Testing CLII appliances mains leakage...
Страница 14: ...PrimeTest 250 Operating Instructions 13 Figure 7 Testing IEC Leads...
Страница 15: ...PrimeTest 250 Operating Instructions 14 Figure 8 Testing Installation RCD...
Страница 16: ...PrimeTest 250 Operating Instructions 15 Figure 9 Testing Plug Top RCD...