ELECTRONIC PANEL  
LRX 2060 NEW READER 

 
Single-phase  electronic  control  unit  for  the  automation  of 
sliding  gates,  doors  and  barriers  with  incorporated  radio 
receiver  for  the  implementation  of  commands  given  via  Radio 
control, Transponder, Digital keyboard and Smartphone.  
The following can be connected to the control unit via BUS RS-
48:  

up to 2 BeSafe Readers New  

up to 2 BeSafe KEYBOARD selectors  

up to 2 BeSafe NFC Readers 

 

- Mod.  LG 2060 New Reader           : Without radio receiver 
- Mod.  LRS 2060 New Reader         : 433.92 Mhz 
- Mod.  LRS 2060 New SET Reader : 433.92 Mhz narrow band 
- Mod.  LRH 2060 New Reader        : 868.30 Mhz  narrow band 
 

I

MPORTANT FOR THE USER

 

 
- The device can be used by children over 8 years of age 
and persons with reduced physical or psychological 
abilities or with little knowledge and experience only if 
supervised or educated in its operation and safe use, in 
order to also understand the dangers involved in its use. 
- these instructions are also available at the website   

www.seav.com

  

- Do not allow children to play with the device and keep 
the radio controls away from their reach. 
- Frequently examine the system to detect any signs of 
damage. Do not use the device if it is in need of repair 
work.  
-Always remember to disconnect the power supply before 
carrying out any cleaning or maintenance. 
- Cleaning and maintenance must not be carried out by 
unsupervised children 
 
- ATTENTION: keep this instruction manual safe and 
observe the important safety requirements contained 
herein. Failure to comply with the requirements may 
cause damage and serious accidents. 
 
I

MPORTANT FOR 

the 

INSTALLER

 

 

1)  Before  automating  the  frame,  check  that  it is in good 
condition,  in  compliance  with  the  Machinery  Directive 
and with EN 12604. 
2)  Check  that  the  location  where  the  installation  is 
located  enables  compliance  with  operating  temperature 
limits specified for the device.  
3)  The safety of the final installation and compliance with 
all  prescribed  Standards  (EN  12453  -  EN  12445)  is  the 
responsibility  of  the  person  who  assembles  the  various 
parts to construct a total closing.  
4)  Use  safety  devices  capable  of  monitoring  the  status 
of their connection to the electrical control unit. 
5)  Once  installation  is  finished,  it  is  recommended  that 
all  necessary  checks  be  performed  (appropriate 
programming of the control panel and correct installation 
of  safety  devices)  to  ensure  that  compliant  installation 
has been performed.  
6)  Fix  the  control  unit  to  a  wall,  using  the  relevant 
support which is fitted to the casing, in such a way as to 
leave said support facing downwards and insert the fixing 
screws in the special holes. 

7)  The  control  unit  does  not  have  any  type  of  isolating 
device  for  the  230  Vac  line.  It  is  therefore  the 
responsibility of the installer to set up an isolating device 
inside the system. It is necessary to install an omnipolar 
switch,  surge  category  III.  It  must  be  positioned  to 
provide  protection  from  accidental  closing,  pursuant  to 
point 5.2.9 of EN 12453.   
8)  Cables  for  power  and  connection  to  the  motor 
suitable  for  insertion  in  the  pg9  cable  glands  provided 
must  have  an  outside  diameter  between  4.5  and  7  mm. 
The  internal  conductors  wires  must  have  a  nominal 
section  of  0.75mm2.  If  a  raceway  is  not  used,  use 
H05RR-F  cables.  Pay  careful  attention  when  fastening 
the cables so that they are anchored in a stable manner. 
Furthermore,  care  is  required  when  drilling  holes  in  the 
outside  casing  where  connecting  and  power  supply 
cables will pass, and when assembling the cable glands, 
so  that  everything  is  installed  so  as  to  maintain  the 
panel's IP protection characteristics. 
9)  The gear motor used to move the frame must comply 
with the requirements of point 5.2.7 of EN 12453. 
10) In  compliance  with  5.4.2  of  EN  12453,  it  is 
recommended  to  use  gear  motors  equipped  with  an 
electrical-mechanical  release  device,  so  that  the  frame 
can be moved manually in case of necessity. 
11) 

In  compliance  with  5.4.3.  of  EN  12453,  use  electrical-

mechanical release systems or similar devices which stop the 
frame safely in the end run position.

 

12) The  various  electrical  components  external  to  the 
control unit must be cabled in accordance with standard 
EN 60204-1 as amended, and as set forth in point 5.2.7 
of EN 12453. The power and connection cables must be 
secured through the use of cable glands supplied. 
13) The  assembly  of  a  push  button  panel  for  manual 
control  must  be  completed  positioning  the  push  button 
panel  in  such  a  way  that  the  user  is  not  placed  in  a 
dangerous position.   
14) The  safety  function  ensured  by  the  control  unit  is 
active  only  during  closing,  therefore,  protection  on 
opening  must  be  ensured  in  the  installation  phase  with 
measures  (guards  or  safety  distances)  independent  of 
the control circuit.  
15) For  proper  functioning  of  the  radio  receiver,  if  using 
one  or  more  control  units,  the  installation  at  a  minimum 
distance  of  at  least  3  metres  one  from  the  other  is 
recommended. 
 

 
 

 

The electronic control unit: 

 

LG 

2060 New Reader

 - LRS 

2060 New Reader 

  

  

LRS 

2060 New SET Reader

 - LRH 

2060 New Reader                   

 

they comply with the specifications of the Directives  

RED 2014/53/EU, EMC 2014/30/EU, LVD 2014/35/EU

 

 
 
 
 
 
 

GB 

Содержание LG 2060 New Reader

Страница 1: ...relevant support which is fitted to the casing in such a way as to leave said support facing downwards and insert the fixing screws in the special holes 7 The control unit does not have any type of isolating device for the 230 Vac line It is therefore the responsibility of the installer to set up an isolating device inside the system It is necessary to install an omnipolar switch surge category II...

Страница 2: ...l Keyboards Smartphones and stores up to 120 different users For use with radio controls the receiver unit is equipped with an incorporated receiver for use of the other devices the desired accessory must be connected by carefully following the connection diagrams described in the relative operating manuals supplied as optionals Operation with different radio control models Different radio control...

Страница 3: ... with 3 Keys The control unit can store the whole BeFree radio control by programming only the UP Key The BeFree radio control codes are programmed as follows press the SEL key the CODE LED will start flashing at the same time press the UP key of the desired radio control the CODE LED will remain on and programming will be complete Deletion All the stored devices are deleted as follows press the S...

Страница 4: ...her the Radio Control Transponder Digital keyboard Smartphone or the low voltage push button panel to operate the frame you will obtain the following function the first impulse commands opening until the motor time expires the second impulse commands frame closing If an impulse is sent before the motor time expires the control unit changes the direction of motion in the opening and closing phases ...

Страница 5: ...t means the input is closed when a LED is off it means the input is open MANAGING PROGRAMMING LEDS After 3 minutes of inactivity in the programming procedure the control unit will automatically switch off the programming LEDs to save energy The LEDs will light up depending on the previously set programs only when the SEL or SET keys are pressed or when a motion command has been received ...

Отзывы: