pH Relay

In the Relay Setup Menu scroll down to pH and press

Enter

. The following

reviews each command within a pH Relay selection that is set up as acid
(change to base in the Relay control Types Menu).

Manual Time 00:02:00:

Is the amount of time you can set a relay to turn

on manually (Default Setting 2 Minutes). To turn the relay on manually
you have to do so in the service menu which will be covered in the next
section. When you turn on the relay manually in the service menu, the
relay will be on for 2 minutes in this case. To change the time, simply
enter the new time and press

Enter

to save.

Proportional 10%:

The Proportional %-Age (Default Setting 10%)

means that as the measured pH reading gets to within 10% (6.75 in this

ManualTime 00:02:00
Proportional 10%
On If pH > 7.5
On Delay

00:00:20

On Time

00:01:00

MinTimeOff 00:05:00
Off if RLY On-none Off
if Flow Off-1
SetOvrfeed 00:00:00
Overfeed

02:00:00

pH Relay Selected

case) of the pH setpoint of 7.5, the amount
of relay on-time will proportionally decrease
as the reading gets closer and closer to the
setpoint. Proportional feed helps to prevent
chemical overshoot. To change the %-Age,
simply press

Enter

, change the value and

press

Enter

to save the new setting. To

deactivate this feature set the %-Age to zero “0” and press

Enter

to save setting.

On If pH > 7.5:

This is the pH set-point

and the factory default setting is 7.5. The
relay will turn the chemical feed pump on if
the measured pH reading is greater than 7.5. The relay will turn on for the
programmed on time, in this case for 1 minute as set in the “On Time 00:01:00” command or less than
1 minute if the measured reading is within the proportional feed %-age of 10%. When feeding base, this
command is the only difference and will be

On if pH < 7.5

.

On Delay 00:00:20:

The on delay, in this case 20 seconds, is necessary to prevent the relay and,

hence the chemical feed pump, from turning on and off frequently if the sensor measurement fluctuates
back and forth from 7.5 and 7.6. It means that the relay will not turn on unless the condition of “On If
pH > 7.5” is satisfied for at least 20 seconds - then the relay will turn on for the programmed “On Time
00:01:00” in this case 1 minute. To change the on delay time, press

Enter

and change the time, press

Enter

to save the new setting. The value 00:00:00 disables the on delay.

On Time 00:01:00:

This is the total amount of time the relay will be ON if the “On If pH > 7.5” condition

has been satisfied. The default setting is 1 minute. This command works in conjunction with the
MinTimeOff Command below. If the pH reading is not being maintained then more or less on time may
be needed.

MinTimeOff 00:05:00:

This is the total amount of time the relay will be OFF if the “On if pH > 7.5”

condition has been satisfied. This is the amount of time allowed for chemical mixing in the pool and
works in conjunction with the “On Time” Command above. Do not set to 00:00:00 if the On Time is not
also set to 00:00:00 as they work together.

Off If RLY On -none:

The default setting is none or disabled. This feature prevents 2 relays being on

at the same time. It means this pH Relay will be Off if the ORP relay is On. This is useful in cases
where the chemical injection points are very close together and prevents the pH relay injecting at the
same time the ORP relay is injecting. Simply press

Enter

to toggle between ORP and none.

Off if Flow Off - 1:

The pH Relay will be turned off if “No Flow” is detected in Flow Switch Input 1.

Note

: This setting can’t be changed as it relates to safety, pressing the

Right Arrow

to change has no

effect.

Содержание MINI WARDEN

Страница 1: ...SeaSide Automation MINIWARDEN SeaSide Automation 12933 Drummer Way Grass Valley CA 95949 Telephone 530 487 5007 www seasideautomation com Manual date 12 2021 Installation Operation Standard Version...

Страница 2: ...Board Acronyms for ORP pH 120 VAC Relays 9 ORP DRY CONTACT RELAY 10 Supported Auxiliary Dry Contact Loads Equipment 10 DEFAULT READINGS SCREEN 12 Selecting Simple Advanced Mode 12 Handy Menu 13 MiniW...

Страница 3: ...in this manner there is a ground current flowing indicating the possibility of an electric shock Disconnect the power until the fault has been identified and corrected 6 It is very important to follow...

Страница 4: ...ublic 11 WARNING Pool and Spa Chemical Safety 11 1 Never mix sodium hypochlorite and muratic acid 11 2 When mixing acid and water always add acid to the water never add water to the acid 12 CAUTION TE...

Страница 5: ...r remotely offsite INTERFACE MiniWarden uses a 16 button built in keypad and an easy to read 80 character liquid crystal display The display s internal back light provides controller viewing in pool r...

Страница 6: ...rs or flow cell MiniWarden FC Controller including flow cell and sensors MiniWarden MTD Controller including flow cell sensors and pre mounted on back board PW Lan Manage controller remotely using the...

Страница 7: ...install is to make sure the input source to the flow cell is well upstream from any chemical injection point C Below The Flow cell input and output points before and after the filter provide the grea...

Страница 8: ...ide the flow cell to make contact with the flow sensor To test this turn the input shut off valve to the off position and watch the flow magnet drop from the flow sensor Next turn the input shut off v...

Страница 9: ...both lines Load Equipment Connection Installation ORP pH RELAYS The chemical feed relays for pH and ORP are internally connected to the input VAC main input which is located on the left side connector...

Страница 10: ...hen the relay is off Supported Auxiliary Dry Contact Loads Equipment Chlorine Generators A high power chlorine generator should not be powered using MiniWarden s internal VAC power as it may exceed th...

Страница 11: ...ange numerical values Text Keys Some menus allow for entering or changing text The first press of a number key will display the number The next press will display the first Lower Case letter below the...

Страница 12: ...eed cycle An Up arrow indicates the relay is ON and in an active feed cycle A Down arrow indicates the relay is OFF and in the OFF part of an active cycle o An o indicates the relay has reached the on...

Страница 13: ...h the relays Startup Screen Press the Up Arrow from the readings screen to access the startup screen that shows the software version and serial number on the fourth line and the current time and date...

Страница 14: ...based control instead of a proportional percentage 3 Setpoints easy to set from the main menu 4 Alarm menu includes values for pH and ORP only 5 Adjustable ORP and pH spread including 0 6 PH Support f...

Страница 15: ...bration slightly The ORP sensor can be calibrated 200 mV ORP sensors are affected by cyanuric acid pH and other factors and it may take a few days to get it adjusted Temperature Enter the manually mea...

Страница 16: ...s is typically for spas and 60 is for pools pH Control Select either Acid or Base For Acid the pH relay will be in a feed cycle when the pH is higher than the set point For Base the pH relay will be i...

Страница 17: ...fault Readings Screen m v Time 12 36 17 Date 03 27 15 Day Friday Units English Daylight Savings No Langlier pH 0 2 TrueDPD Free Cl OFF TrueDPD Cycle 10 min ORP Cal Enabled Service QuickJmp On Display...

Страница 18: ...Handy Menu Flow Menu and Alarm Menu are not Password Protected anyone can access them From the Default Readings Screen simply press the Back button to access the Main Menu and use the Down Arrow to s...

Страница 19: ...w control type within MiniWarden Note The Back button will cancel the change only the Left Arrow will change the control type Note To reset a single relay back to factory default values select that re...

Страница 20: ...less than 700 The relay will turn on for the programmed on time in this case for 1 minute as set in the On Time 00 01 00 command or less than 1 minute if the measured reading is within the proportiona...

Страница 21: ...the ORP is within 5 of the setpoint the Setpoint Overfeed timer will clear If it would take 2 gallons of liquid chlorine to raise the chlorine level from 0 to the desired value calculate how much time...

Страница 22: ...age of 10 When feeding base this command is the only difference and will be On if pH 7 5 On Delay 00 00 20 The on delay in this case 20 seconds is necessary to prevent the relay and hence the chemical...

Страница 23: ...able pump setting Most variable pumps use a scale of 10 to 0 So if the pump is set on 8 then use 80 of the total GDP rate in this case 80 x 10 GPD 8 GPD Calculate the overfeed time with the following...

Страница 24: ...ng is fluctuating back and forth To change the command press Enter to change the value and press Enter again to save enter 00 00 00 to disable Off If Time 00 00 00 This is a time of day command The fa...

Страница 25: ...16 Cal pH 7 7 5 Cal Temp 78 12 Clear Cal ORP Clear Cal pH Clear Cal Temp Calibration when calibrating The percentage to the right of the current reading is the amount of calibration and if it is at 9...

Страница 26: ...a Once the maximum memory has been reached any new data will record over the oldest data To access Data Recording simply press the Back button from the default readings screen and scroll down to Data...

Страница 27: ...e data is in overflow mode and any new recorded data is erasing the oldest recorded data System Menu The System Menu is where many of the main operating system components are turned on or off Please r...

Страница 28: ...ings to the original factory defaults conditions including relay control types relay programming and calibrations When selected a Warning screen will display and you must press 9 to proceed or any oth...

Страница 29: ...o the threads and reinstall the sensors ORP and pH Sensor Replacement The PoolWarden ORP and pH sensors have a warranty to last at least 1 year and will most likely last from 1 5 to 3 years or longer...

Страница 30: ...ure with a digital voltmeter one of the ground terminals on the main board in the lid to a piece of metal in the pump room Chemical feeders are not turning on The first test is to make sure they can t...

Страница 31: ...iWarden has it s own unique reset code and one that works on one MiniWarden will not work on another Technical Support Please contact SeaSide Automation at 530 212 3497 for support and 530 212 3496 fo...

Страница 32: ...l use and the owners manual c damage as a result of misuse accident or neglect d damage from improper testing operation or installation e damage resulting from not operating the controller on a dedica...

Отзывы: