Positioning

The PE202 can be mounted vertically or horizontally. It is 

important to choose a position that will ensure full pipe.  

(Under certain conditions of empty or partially-full pipe 

the  meter  may  give  a  pulse  out  when  there  is  no  flow.) 

With a zero straight pipe requirement after an elbow, the 

PE meter can be installed in tight spaces.

Mounting

It is highly recommended to use the mounting bracket 

provided. The mounting bracket uses two #8 screws on a 

1.5” center. 

The PE202 may be supported by its piping connections 

IF

 

the piping is rigid. The meter and pipe must be perfectly 

aligned with no flexion at the fittings to prevent leakage or 

damage to the meter. 

FL

OW

FLOW

FL

OW

INSTALLATION

Piping

Metal pipe, metal tube, or plastic tubing can be used with 

the meter.  The standard NPT fittings can be used with or 

without NPT adapters on 3/4” or 3/8” pipe. If used, apply 

Teflon tape onto the NPT fittings. NPT adapters should be 

hand  tightened  onto  the  fittings.  Thoroughly  clean  the 

pipe  threads  and  nose  and  apply  Teflon  tape  to  adapter 

threads. Hold adapters with a wrench while tightening the 

pipe to prevent damage to the meter. 

Power Supply

A 12 Vdc linear, regulated power supply with an output 

current of at least 0.25A is recommended. If a switching 

power supply must be used, consult Seametrics for 

approved manufacturer’s model numbers.

Grounding

In addition, it is necessary for proper operation to ground 

the unit to a good quality earth ground. Assure negative 

power supply is grounded to earth and to the entire 

electrical/mechanical system.  If metal piping is used, 

jumper inlet and outlet pipes together and connect to 

ground for best results in metering accuracy.  The cable 

shield drain wire should be left unconnected.

Содержание PE202

Страница 1: ...PROUDLY MADE IN THE USA C e rtified Compa n y ISO 9001 2008 PE202 Low Flow Magmeter Instructions ...

Страница 2: ...ge 5 Installation Positioning Page 6 Mounting Page 6 Piping Page 6 Power Supply Page 6 Grounding Page 6 Connections General Connection Information Page 7 Pulse Output Only with FT520 Page 7 4 20 mA Device and FT430 440 with Single Power Supply Page 7 Dual Power Supply with Loop Isolation Page 7 Operation General Operation Information Back Troubleshooting Problem Back Probably Causes Back Things to...

Страница 3: ...mens of varying viscosities and densities FEATURES GENERAL INFORMATION The PE meter is compact enough to fit most pump injection systems With zero straight pipe required after an elbow it can be easily mounted in tight spaces The mounting bracket adds stability The PE meter has an optoisolated current sinking pulse output that can be connected to the Seametrics FT430 440 rate total display or FT52...

Страница 4: ... mA max Optoisolated 4 20 mA current loop 7 Vdc plus load voltage drop min 50 Vdc max 075 500 pulses liter 1892 pulses gallon 038 1000 pulses liter 3785 pulses gallon Power 10 15 Vdc 150 mA linear power supply recommended Conductivity 20 microSiemens Empty Pipe Detection Hardware software conductivity based Environmental NEMA 4X standard IP66 splashproof standard Specifications subject to change P...

Страница 5: ...K SHARP EDGES DRAWN MECH ENG ELEC ENG MFG ENG Q A DATE NAME TITLE SIZE B DWG NO REV SHEET 1 OF 1 CP PE202 038 DO NOT SCALE DRAWING A COMMON PARTS PE202 038 Mounting Bracket 7 2 18 3 cm with adapters as shown 4 2 10 7 cm meter without adapters 3 5 8 9 cm 2 0 5 0 cm 4 2 10 7 cm 2 1 5 3 cm Meter ID 038 0 19 075 0 50 4 2 METER WITHOUT ADAPTERS 7 2 WITH ADAPTERS AS SHOWN 3 5 2 0 4 2 2 1 A B C D 2 3 4 5...

Страница 6: ...ic tubing can be used with the meter The standard NPT fittings can be used with or without NPT adapters on 3 4 or 3 8 pipe If used apply Teflon tape onto the NPT fittings NPT adapters should be hand tightened onto the fittings Thoroughly clean the pipe threads and nose and apply Teflon tape to adapter threads Hold adapters with a wrench while tightening the pipe to prevent damage to the meter Powe...

Страница 7: ...h FT520 _ SEN 1 SEN 2 _ 12 G 12 Vdc power Green Brown White Red Pin 8 Pin 2 Pin 3 Pin 1 PE202 FT520 4 20 mA Device and FT430 440 with Single Power Supply Important 4 20mA device input resistance must not exceed 250 Ω Dual Power Supply with Loop Isolation _ S _ _ _ 4 20 mA loop 12 15 Vdc 4 20 mA device PE202 Sensor Input FT430 440 Power 4 8 3 1 2 7 Yellow Red Green White Blue Brown May be external ...

Страница 8: ...and register zero flow OPERATION The 4 20 mA signal outputs 4 mA at zero flow and 20 mA at 20 gallons minute flow or 3 gallons per minute depending on model The pulse signal is a 50 duty cycle pulse set at PE202 075 500 pulses liter 1892 pulses gallon PE202 038 1 000 pulses liter 3785 pulses gallon Problem Probable Causes Things to try No output Reversed flow direction Reverse flow connections Emp...

Отзывы: