0.03 Alarm reset / alarm log erasing
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 0 3 0 0 0
[0.03.0]
Set the cursor on DG3456 (DG3-DG6 flash), then press ˄ for 1 seconds to reset the alarms that
requires manual reset and which are currently causing out of service (see parameter
), or press ˄ for
about 5 seconds to erase also the alarm log (see parameters
).
The following result will be displayed:
DG6
R
ESULT
0
Alarms have not been reset
1
Alarms have been reset
2
The alarms log have been erased
A
LARM
RESET
BY
SW1
PUSH
-
BUTTON
Manual reset alarms can also be reset by pressing the SW1 button on the STK1R card for about
2 seconds, provided that this SW1 function is enabled (see parameter
).
N
OTES
•
It is never necessary to delete any automatic reset alarm: just eliminate its causes.
•
It is never necessary,
rather it is strongly advised not to erase
the alarms log,
especially when there are anomalies and the customer wishes to contact SEA SYSTEMS
for any clarification about them. By erasing the errors log, important informations are
deleted that could be very useful to understand the causes of such anomalies. When the
error log is full (32 alarms), automatically any new error is registered deleting the oldest
one.
0.04 Total runs count
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 0 4 _
DG3456
=
[0.04.0]
total number of runs, first part:
thousands (0000
9999)
DG0
DG1
DG2
DG3
DG4
DG5
DG6
0 0 4 0 _
DG456
=
[0.04.0]
total number of runs, second part: units
(000
999)