VERSO 50_v1.0.27_EN                                        33502027401_3_1                                                  page 13/24 

2- 3  M2 - Alternator setup 

Selecting the alternator setup you access directly to the programmation parameters about the generator, like frequency  and 
voltage. All these parameters are shown in the following table: 

 

POS. 

NAME 

DESCRIPTION 

RANGE OF 

VALUES 

DEFAULT 

3-phase 

DEFAULT 

1-phase 

GE rated V 

Rated voltage of the generator. 

0-600 [VAC] 

400 

230 

GE high V 

You can set the high threshold voltage; if the voltage 
measured is higher than this value, the generator is 
considered faulty and VERSO 50  shows the “high gen. 
voltage” alarm. 

100-200 [%] 

113 

113 

GE low V 

You can set the low threshold voltage; if the voltage 
measured is less than this value, the generator is 
considered faulty and VERSO 50  shows the “low 
generator voltage” alarm. 

70-100 [%] 

80 

80 

GE rated F 

Rated frequency of the generator. 

40-70 [Hz] 

50 

50 

GE high F 

You can set the high threshold frequency; if the 
frequency measured is higher than this value, the 
generator is considered faulty and VERSO 50  shows 
the “high generator frequency alarm”. 

100-200 [%] 

110 

110 

GE low F 

You can set the low threshold frequency;if the frequency 
measured is less than this value, the generator is 
considered faulty and VERSO 50  shows the “low 
generator frequency alarm”. 

0-100 [%] 

90 

90 

KG delay 

You can set a delay time for closing the generator 
contactor.This time starts from when the VERSO 50 
opens the mains contactor (software interlock function). 

0-100 [s] 

GE Ok delay 

It is the delay time over which if the voltage and 
frequency are within limits (parameters B, C, E, F), the 
generator is considered stable and its contactor is 
closed. 

0-9999 [s] 

KG alarm ON 

If On, the alarms set as “Global KG” cause the opening 
of the generator contactor.  If Off, the alarms set as 
“Global KG” permit the closure of the generator 
contactor if voltage and frequency are within the limits. 
Set this parameter to On if you want to reset the 
eventual alarms before a possible closure of KG. 

On-Off 

Off 

Off 

System type 

You can set the type of system.  
If you set it to Monophase, the system is considered as 
single-phase. 
If you set it to Threephase, the system is considered as 
three-phase. 

Monophase - 

Threephase 

Threephase  Monophase 

ON Alarms delay 

Time that passes from the starting of the generator and 
the evaluation of the eventual alarms. 

0-1000 [s] 

60 

60 

Cooling time 

You can set the time between the opening of KG and 
the removing of the remote start output. It works both in 
manual and automatic mode. 

0-255 [s] 

Neutral 

If On, the generator is considered with neutral 
connected. If Off, the generator is considered without 
neutral. 

On-Off 

On 

On 

 

NOTES: 

 To avoid any incompatibility between the timings  of the VERSO 50  and the controller for engine protection, remember 
that the “ON Alarms delay” must be at least 5 seconds higher than the preheat time set in the engine protection controller. 

The cooling procedure is managed by the VERSO 50. If the engine protection controller allows to set a cooling procedure, 
we advise to disable it and maintain active only the procedure on the VERSO 50 controller. 

Содержание VERSO 50

Страница 1: ...VERSO 50_v1 0 27_EN 33502027401_3_1 page 1 24 VERSO 50 Instructions Manual Release 1 0 27 33502027401_3_1...

Страница 2: ...VERSO 50_v1 0 27_EN 33502027401_3_1 page 2 24...

Страница 3: ...ains stats 9 1 8 3 Generator 9 1 8 4 Generator stats 9 1 8 5 Hours 9 1 8 6 Events log 9 1 8 7 Clock and warranty 9 1 8 8 I O Monitor 10 1 8 9 Info page 10 1 8 10 System data 10 1 8 11 Logo page 10 2 P...

Страница 4: ...e of fixation The panel must be fixed on the wall like the picture opposite with appropriate material Be careful there are 3 meters length cable between the genset control panel and the ATS Section of...

Страница 5: ...rior notice Technical data and descriptions in the documentation are accurate to the best of our knowledge but no liabilities for errors omissions or contingencies arising there from are accepted A ci...

Страница 6: ...C 70 C electric 30 C 70 C display 40 C 80 C storage DISPLAY 128x64 px 66x33mm DIGITAL INPUTS Number 1 STATIC OUTPUTS Number 1 CONTACTORS RELAYS Number 2 Type of contacts 1x N O genset contactor 1x N C...

Страница 7: ...that the connections strictly comply with the wiring diagram below NOTE The remote start output is a positive If you want to use a negative instead of a positive it s possible to use an external relay...

Страница 8: ...put NO 1 5 Genset voltage phase 1 1 6 Genset voltage phase 2 1 7 Genset voltage phase 3 1 8 Neutral J5 Supply and Outputs 5 1 Battery negative 5 2 Battery positive 5 3 Common positive for remote start...

Страница 9: ...tivated to test the genset for a programmable time Test duration can be programmed inside M3 Test setup parameter M When the test is finish automatically the controller returns in MAN mode and the tes...

Страница 10: ...s present J KR Key control to deactivate the remote start output only in manual mode keeping and releasing quickly the button the remote start output is removed immediately while keeping pressed the b...

Страница 11: ...rator A L1 L2 Vac voltage B L2 L3 Vac voltage C L3 L1 Vac voltage D L1 line voltage E L2 line voltage F L3 line voltage G Generator frequency 1 8 4 Generator stats A Maximum value measured on the L1 l...

Страница 12: ...T and the 3 outputs J1 2 KR J1 4 KG and J5 4 Remote start output 1 8 9 Info page This page contains the contacts data of the manufacturer web address telephone number and address 1 8 10 System data Th...

Страница 13: ...one alarm active Pressing the HELP button you directly go to the active alarms page With the arrows you can select the menu Once selected the desired menu press the i button to confirm and enter or pr...

Страница 14: ...remote start output in automatic mode 0 100 90 90 G KR delay You can set a delay time for the closure of the mains contactor This time starts from when the VERSO 50 opens the generator contactor soft...

Страница 15: ...0 s 1 1 H GE Ok delay It is the delay time over which if the voltage and frequency are within limits parameters B C E F the generator is considered stable and its contactor is closed 0 9999 s 5 5 I KG...

Страница 16: ...ou set the minute of test starting 0 59 0 Also you can set some parameters that are in common for the two tests POS NAME DESCRIPTION RANGE OF VALUES DEFAULT SETTINGS M Test lenght You set the length t...

Страница 17: ...events occurs 0 255 s 60 C Return to default It is the time after which the controller automatically returns to the standby page Mains 1 if no buttons are pressed Off 250 s Off D Contrast To set the...

Страница 18: ...ocks the alternator setup If you enter the code correctly to 50 the alternator setup is completely unlocked If you enter a wrong code the menu is locked 50 C Test password Enter the password that lock...

Страница 19: ...the parameters from D to L in the configuration of the alarm selected at parameter A D Activation It permits to choose when the alarm condition must be verified and make the alarm appear Always always...

Страница 20: ...generator Frequency values are under the programmed limits 2 1202 High frequency generator Frequency values are over the programmed limits 3 1203 Low voltage generator Voltage values are under the pr...

Страница 21: ...arting of the generator before the opening of KR and the closure of KG 0 59 min 0 D EJPT 2 input Function disabled in the VERSO 50 with only 1 input On Off Off E No KR with EJPT If ON when EJPT mode i...

Страница 22: ...3 PANELS ELECTRICAL DRAWINGS 3 1 Single Phase 40A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 20 24...

Страница 23: ...3 2 Single Phase 100A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 21 24...

Страница 24: ...3 3 Three Phase 25A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 22 24...

Отзывы: