Chiller wired controller
1.1.4 Installation instruction
Circuit of wired controller is the low voltage circuit. Never connect it with a standard 220V/380V circuit
or put it into a same Wiring Tube with the circuit.
The shield cable must be connected stable to the ground, or transmission may fail.
Do not attempt to extend the shield cable by cutting, if it is necessary, use Terminal Connection Block
to connect.
After finishing connection, do not use Megger to have the insulation check to the signal wire.
1. Structure size: 120*120*20mm
1
9
m
m
8
4
m
m
4
4
m
m
46mm
60mm
120mm
20mm
1
2
0
m
m
Figure A
Содержание KJR-120F
Страница 1: ...WIRED CONTROLLER MINI CHILLER USER MANUAL KJR 120F AIR CONDITIONING...
Страница 2: ...Original instructions...