SCS TB-9017 Скачать руководство пользователя страница 3

TB-9017

 Page 3 of 6

© 2022 DESCO INDUSTRIES INC

Employee Owned

SCS 

- 926 JR Industrial Drive, Sanford, NC 27332

East: (919) 718-0000 | West: (909) 627-9634 • Website: 

StaticControl.com

The following procedures should be followed when 

testing installed static control surfaces: 

1.  Complete BATTERY TEST and CONTINUITY TEST. 
2.  Set the SCS 701 Analog Surface Resistance 

Megohmmeter Kit on a table top or other stable     

surface and place a test weight at the desired test     

point as shown in Figure 5. Connect the test leads     

to the meter using the right angle banana plugs at 

the meter. Then connect one of the test leads to 

the test weight and the other to the ESD GROUND 

using one of the supplied clips. 

3.  Test the static control surface using the 100 volts 

SURFACE TEST. Press the TEST button for 15 

seconds, allowing the pointer to stabilize; record the 

readings for each test point. If the reading is below  

1 x 10

6

 ohms, check the static control surface for an 

alternate path to ground; correct and retest. If some 

or all the readings are above 1x10

9

 ohms, the static    

control surface may be dirty. Clean the surface 

using the manufacturer’s recommended cleaning 

procedure. If the resistance reading is “infinite,” there 

is an interruption (open) in the ground connection; 

repair and retest. 

Qualification of Installed Static Control Surfaces

 

[Measurement of resistance of the top surface to the 

groundable point of the static control surface (RTS-

GP)]. GROUNDABLE POINT is the point at which the 

grounding conductor is connected to the static control 

surface; the GROUNDABLE POINT is most commonly 

a snap (mats), a bolt (laminate), or a strip of conductive 

foil tape (flooring). This QUALIFICATION measurement 

is similar to those described in the test description 

section and is used to verify the correct installation of 

the GROUNDABLE POINT by the manufacturer or by 

the user. While the test procedure is the same, the test 

setup is slightly different; see Figure 5.

 

Evaluation of Static Control Materials

[Measurement of the resistance between two points 

on top of a static control surface (RTS-TS), and the 

resistance between a point on the surface and the 

groundable point (RTS-GP)] Material measurements are 

done to determine the intrinsic electrical properties of 

static control work surface materials. 

 

Note: Values obtained by these tests may not reflect how 

a material will perform when installed as a static control 

surface. 

 

Material evaluations are typically done at two humidities 

(12% RH and 50% RH) to determine whether the 

electrical properties of the material are humidity-

dependent. If the low humidity test results are borderline 

or not within the expected ranges, caution should be 

exercised when using such materials in winter months or 

in dry conditions. To assure test accuracy, a minimum of 

six samples should be tested.

 

The test procedure is as follows:

A.  Prepare a minimum of six samples of each material 

to be tested as shown in Figure 6. 

B.  Clean samples per manufacturers recommended 

cleaning procedures. Condition samples at 73°F 

(23° C) and 50% RH for 48-72 hours. Note: Samples 

must be maintained at the appropriate humidity level 

throughout the test procedures. 

C.  Complete BATTERY TEST and CONTINUITY TEST. 
D.  Surface-to-Groundable Point Test: Test samples 

per Figure 7, using both the 100 volts and 10 volts 

SURFACE TEST ranges at 50% RH and record the 

values as (RTS-GP).

2021

Figure 5. Qualification tests of installed surfaces

Figure 6. Material evaluation sample configuration

Figure 7. Material evaluation surface to groundable test 

point

Отзывы: