To Replace the Evaporator:
(Assuming all the steps for removal of the
thrust bearing, breaker, auger, and water seal
have been performed.)
1. Shut the hand valves in the liquid and
suction lines to the evaporator being serviced;
then discharge the refrigerant.
2. Unsweat the refrigerant connections:
 a) At the thermostatic expansion valve outlet.
//////////////////////////////CAUTION///////////////////////////
Heat sink the TXV body when unsweating
or
 resweating the adjacent tubing.
//////////////////////////////////////////////////////////////////////////
 b) At the suction line
at the joint about 3"
from the evaporator.
3. Remove the
evaporator.
4. Unsweat the drier
from the liquid line.
5. After installing a
new water seal in the
new evaporator (see
"To Replace the Water
Seal") sweat in the
new evaporator at the
old  connections.
6. Install an new drier
in the liquid line.
7. Evacuate the
system until
dehydrated, then
weigh in the
nameplate charge.
Check for leaks.
8. Install auger,
breaker, breaker
bearing assembly, and
ice discharge chute in
reverse order of
disassembly.  See "To
Reassemble
Evaporator and Auger"

To Reassemble the Evaporator and Auger
1. After the gearmotor has been inspected,
fasten the evaporator to the gear motor, be
sure that the number of shims indicated on the
gear case cover is in place between the
gearcase cover and the drip pan gasket.
Torque the bolts to 110 inch pounds.
2. Lower the auger into the evaporator barrel,
slightly turning it to match up with the drive
end. Do Not Drop Into the Evaporator.
3. Complete the reassembly by reversing the
disassembly for the breaker & thrust bearing
assembly.

ICE SWEEP

BEARING

AUGER

EVAPORATOR

DRIP PAN

DIVDER/BREAKER

REMOVAL AND REPLACEMENT: Evaporator

NM1850RH

May, 1989

Page 24

Содержание NM1850RH

Страница 1: ...o liquid line valves two control boxes two thermostatic expansion valves and an EPR valve TABLE OF CONTENTS For the Installer Page 2 For the Electrician Page 4 For the Plumber Page 5 Final Check List...

Страница 2: ...e highest regard for safety and performance They meet or exceed the standards of U L N S F and C S A Scotsman assumes no liability or responsibility of any kind for products manufactured by Scotsman t...

Страница 3: ...p edge and using a mechanical lift install the NM1850RH onto the top of the storage bin assembly Fasten the ice machine to the bin using 4 5 15 18 2 5 cap screws Level the assembly by a Turning the le...

Страница 4: ...diagram The ice machine should be connected to it s own electrical circuit and be individually fused Voltage when the unit is under full load must remain within the limitations listed on page 2 LOW V...

Страница 5: ...etween the ice maker and the water supply Drain System All drains are of the gravity type and must have a minimum of 1 4 fall per foot of horizontal run The drains must be installed to conform to loca...

Страница 6: ...en removed from inside the cabinet 6 Have the electrical connections been made 7 Have the drains been installed and checked for leaks 8 Has the refrigeration supply been installed and checked for leak...

Страница 7: ...o make ice Water flows from the water reservoir and the float drops letting in more water 7 Switch on the other master switch observe that The liquid line valve opens The gearmotor runs Within a short...

Страница 8: ...ing is 4 80 F Measure the temperature of the evaporator outlet at the TXV bulb and check the low side pressure at the EPR valve Convert the pressure to temperature using a temperature pressure chart a...

Страница 9: ...ice when the unit turns off and for the liquid line valve Transformer Supplies low voltage to the circuit board On Off Switch Manual control for that side of the machine Reset Switch Manual reset Glow...

Страница 10: ...being where the two seal faces meet Ice Sweep A plastic cap with fingers It revolves with the auger to sweep the ice into the ice chute Divider Where the ice is compressed and much of the extra water...

Страница 11: ...rs for more than 15 seconds bin full At that point the bin empty light goes out and the machine shuts down Shut Down consists of The liquid line relay opens The liquid line valve closes Ice making sto...

Страница 12: ...s through the float valve The water then goes out the bottom of the reservoir tank to the bottom of the evaporator Reservoir overflow or evaporator condensation is routed to the drain WATER INLET DRAI...

Страница 13: ...thermostatic expansion valve meters the liquid refrigerant into the evaporator where it boils off evaporates and absorbs heat It then moves through the ball valve and into the evaporator pressure reg...

Страница 14: ...ic and Hydroxyacetic acids These compounds are corrosive and may cause burns If swallowed DO NOT induce vomiting Give large amounts of water or milk Call Physician immediately In case of external cont...

Страница 15: ...he tip wiped clean of mineral buildup 3 The bearing in the breaker should also be checked at least two times per year Check the bearing by removing the ice chute cover unscrewing the ice sweep removin...

Страница 16: ...mation on removal of these parts see REMOVAL AND REPLACEMENT 1 To remove the auger remove front and top panel If top panel cannot be removed or if there is less than 6 clearance over the top of the ma...

Страница 17: ...k the spout switch D Check the spout switch It opens from excess pressure of ice inside the ice chute this should only happen when the machine does not shut off when the ice storage bin is full This s...

Страница 18: ...on the tester to the full position The bin full light on the tester should be ON if not replace the circuit board If the bin full light on the tester is ON move the tester switch to bin empty the lig...

Страница 19: ...e at the liquid line valve coil Check for an open wire between the relay and the valve 2 Check the valve coil If the coil is open replace the liquid line valve 3 Check the auger drive motor centrifuga...

Страница 20: ...eservoir from icemaker 8 Reverse to reassemble BIN CONTROLS Ice Level Sensors 1 Disconnect electrical power 2 Remove front panel 3 Remove control box cover 4 Locate ice chute at the base of the chute...

Страница 21: ...reaker to evaporator d Lift up and remove breaker bearing assembly from auger evaporator 6 Service the bearing Check for rust rough spots and damage a The bearing is pressed into the breaker to remove...

Страница 22: ...crews holding breaker to evaporator d Lift up and remove breaker from evaporator e If the auger is stuck use a slide hammer type puller to pull on the auger at the threaded hole The size of that hole...

Страница 23: ...tly past the grove for the snap ring 2 Replace the snap ring and pull the water seal down against it 3 The part of the water seal that rotates with the auger must also be replaced Remove the old part...

Страница 24: ...n new drier in the liquid line 7 Evacuate the system until dehydrated then weigh in the nameplate charge Check for leaks 8 Install auger breaker breaker bearing assembly and ice discharge chute in rev...

Страница 25: ...ickly check the gears and bearings They are likely to be fine if the oil is If there is evidence of water in the oil rusty bearings and gears the oil having a creamy white appearance oil level too hig...

Страница 26: ...that the ice level sensors are properly aligned clean and not obstructed use the tester as follows Bin Control Note All testing is done with the electrical power on the master switch on and all reset...

Страница 27: ...ot replace the circuit board b Move the water switch on the tester to the Water position The No Water light on the board should go OFF If not replace the circuit board If the light does go off replace...

Отзывы: