SERVICE DIAGNOSIS: Condition - No Ice Being Produced

STATUS: 

NOTHING OPERATES

H. Check: The gear motor, if it will not run, the compressor will not run. If no power to it:
Check: The indicator lights on the circuit board, the bin empty light should be ON, the no water
light should be OFF .

1. If the  bin empty and no water lights are off, check the  transformer

a. Transformer "load" side should have 12 to 15 volts.  If not, check the "line" side. The line

 

side should have between 208-230 volts.  If the line side has the correct voltage and the 
load side does not, replace the transformer.

2. If the transformer is good, and the bin empty light is OFF, check the ice level sensors.

a. Remove sensors by sliding them sideways out of the ice chute.  Visually inspect them, 
clean if needed.
b. Look through the ice chute "eye" hole for something blocking the ice chute.
c. If the unit still does not run, replace the ice level sensors.
d. If the bin empty light is still OFF, check the circuit board.

1. Unplug "opto trans" and "LED" connectors from the circuit board.
2. Plug "opto trans" and "LED" connectors from the Scotsman Electronic Control

 

Testor Model NM1 into the circiut board.

a.Move the "bin full" switch on the tester to the full position.  The bin full light
 on the tester should be ON, if not, replace the circuit board.
If the bin full light on the tester is ON, move the tester switch to "bin empty"
the light on the tester should go OFF and the bin empty light on the circuit 
board  should go ON.  If not, replace the circuit board. If it does as above, 
and the machine still does not run, replace the ice level sensors. 

3. If the transformer is fine, and the "no water" light is ON, check the water level sensor.

a. Check the water level in the reservoir, restore if low. If the water level is ok:
b. Remove the water level sensor from the reservoir and clean the tip if dirty.
CAUTION:  THE TIP IS MADE OF GLASS
c.  Replace the water level sensor.  If the no water light is still on, check that the 
"water sen" plug is firmly plugged into the circuit board. 
d.  If the no water light is still on, 

1. Unplug the "water sen" connector from the circuit board.
2. Plug "water sen" connector from the Scotsman Electronic Control tester into 
the  circuit board.

a. Move the water switch on the tester to "no water" and the no water light 
on the circuit board should go on.  If not, replace the board.
b. Move the water switch to the "water" position, the no water light should 
go off, if not, replace the circuit board.
c. If after the above, the machine still will not run, replace the water level
sensor

MORE INFORMATION ON THE TESTOR MAY BE FOUND ON THE LAST PAGES OF THE
MANUAL.

NM1250

February, 1989

Page 20

Содержание NM1250

Страница 1: ...of kit KSTACK30 electronic circuitry for monitoring ice and water level a thermostatic expansion valve and R502 as the refrigerant TABLE OF CONTENTS For the Installer Specifications 2 Location 3 Stac...

Страница 2: ...orrect Bin Correct Ice Machine Correct Bin Top if required All kits legs and information required for the specific job SPECIFICATIONS ICEMAKER Minimum Circuit Ampacity is used to determine wire size a...

Страница 3: ...ne that filters out suspended solids to a dimension of 5 microns or smaller The finer the filter the better but finer filters will clog sooner than course ones It may be necessary to add a course filt...

Страница 4: ...s in the bottom of the bin Turn the leg levelers all the way in preparation for leveling later Return the bin to the upright position remove paper covering the bin gasket Install bin top if required N...

Страница 5: ...pin plug onto the ice machine circuit board socket marked LED CX2 B Plug the 3 pin plug onto the ice machine circuit board socket marked Photo Trans CX4 12 Unplug the wire harness connecting the trans...

Страница 6: ...back of the cabinet the drain line is of the gravity type and 1 4 inch per foot fall is an acceptable pitch for the drain tubing There should be a vent at the highest point of the drain line and the...

Страница 7: ...es a solid chassis to earth ground wire The ice maker should be connected to its own electrical circuit so it would be individually fused Voltage variation must remain within design limitations even u...

Страница 8: ...r leaks 4 Has the machine and bin been leveled 5 Is there a minimum of 6 clearance at the rear left and right of the machine for proper service access and air circulation 6 Is the water pressure a min...

Страница 9: ...rain 5 The unit should soon be making ice if desired the low side pressure can be checked it should be 30 psig or 4 psig The suction line temperature at the compressor is normally very cold nearly to...

Страница 10: ...Senses if there is water in the reservoir to make ice out of Will shut the machine off it there is none Ice Discharge Chute Directs the ice made by the evaporator into the storage bin Ice Level Senso...

Страница 11: ...to the circuit board Low Pressure Control Cut Out A manual reset control to shut off the ice machine when the low side pressure drops below a preset point 0 4 psig Potential Relay The compressor start...

Страница 12: ...faces meet Ice Sweep A plastic cap with fingers It revolves with the auger to sweep the ice into the ice chute Breaker Where the ice is compressed and much of the extra water is squeezed out of it be...

Страница 13: ...e evaporator and then The auger motor relay opens and the auger motor stops If the ice level sensor is clear bin empty for more than 15 seconds the machine will start up again Another purpose of the c...

Страница 14: ...of the evaporator Reservoir overflow or evaporator condensation is routed to the drain Water cooled models have a separate water circuit for the cooling water it enters the fitting at the rear goes t...

Страница 15: ...depending upon the temperature of the evaporator warmer evaporators get more refrigerant and colder evaporators get less At the evaporator the refrigerant enters an area of relatively low pressure whe...

Страница 16: ...and Hydroxyacetic acids These compounds are corrosive and may cause burns If swallowed DO NOT induce vomiting Give large amounts of water or milk Call Physician immediately In case of external contac...

Страница 17: ...should also be checked at least two times per year Check the bearing by removing the ice chute cover unscrewing the ice sweep removing the water shed using a spanner wrench and unscrewing the breaker...

Страница 18: ...top panel If top panel cannot be removed or if there is less than 6 clearance over the top of the machine the gearmotor evaporator may be slid out for service access See Removal And Replacement 2 Remo...

Страница 19: ...ge E Check the high pressure cut out if closed go to F if open check 1 The pressure control opens at 450 psig Check the high side pressure reset the control and observe on water cooled that water soon...

Страница 20: ...full light on the tester should be ON if not replace the circuit board If the bin full light on the tester is ON move the tester switch to bin empty the light on the tester should go OFF and the bin e...

Страница 21: ...s open replace the contactor 3 Check the auger drive motor centrifugal switch If when the drive motor is running contact 4 black wire removed has no power and all of the above switches have been check...

Страница 22: ...er leaks replace the water seal if found to be leaking 3 Check the low side pressure normal is about 30 psig If low assume a refrigerant leak locate repair and recharge If no leak the TXV may be restr...

Страница 23: ...from icemaker 8 Reverse to reassemble BIN CONTROLS Ice Level Sensors 1 Disconnect electrical power 2 Remove front panel 3 Remove control box cover 4 Locate ice chute at the base of the chute in front...

Страница 24: ...olding breaker to evaporator d Lift up and remove breaker bearing assembly from auger evaporator 6 Service the bearing Check for rust rough spots and damage a The bearing is pressed into the breaker t...

Страница 25: ...en head cap screws holding breaker to evaporator d Lift up and remove breaker from evaporator e If the auger is stuck use a slide hammer type puller to pull on the auger at the threaded hole The size...

Страница 26: ...ast the grove for the snap ring 2 Replace the snap ring and pull the water seal down against it 3 The part of the water seal that rotates with the auger must also be replaced Remove the old part from...

Страница 27: ...ntil dehydrated then weigh in the nameplate charge Check for leaks 8 Install auger breaker breaker bearing assembly and ice discharge chute in reverse order of disassembly See To Reassemble Evaporator...

Страница 28: ...usty bearings and gears the oil having a creamy white appearance oil level too high carefully inspect the bearings and gears If in doubt about the condition of a part replace it The oil quantity is 14...

Страница 29: ...ACEMENT Gearmotor WATER SHED SEAL CENTRIFUGAL SWITCH DRIVE MOTOR BEARING SEAL 1ST GEAR AND BEARINGS GASKET GEARCASE 2ND GEAR AND BEARINGS GEARCASE COVER BEARINGS OUTPUT GEAR OUTPUT SHAFT NM1250 Februa...

Страница 30: ...at the ice level sensors are properly aligned clean and not obstructed use the tester as follows Bin Control Note All testing is done with the electrical power on the master switch on and all reset sw...

Страница 31: ...t replace the circuit board b Move the water switch on the tester to the Water position The No Water light on the board should go OFF If not replace the circuit board If the light does go off replace...

Отзывы: