Operational Characteristics 1400 lb system
Cycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F
System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.
Headmaster maintains a minimum discharge
pressure during freeze of:
·
217 PSIG + 25, -15 PSIG
CPR Valve Setting: 55 - 60 PSIG.
Note: CPR allows a maximum low side pressure at
the CP unit’s compressor. Maximum only occurs
during harvest.
Refrigerant Charge
·
272 oz
Compressor Amps
·
Single Phase - 8 to 12
·
Three Phase - 6 to 10
Batch Weight
·
14 to 15 lb (small cube
·
13 to 14 lb (medium cube)
Discharge Pressure Cut Out Switch
·
Cuts Out at: 450 PSIG
·
Resets at: 350 PSIG
Compressor:
·
CS14K6E
Expansion Valves: 2
Prodigy Eclipse
ä
1400,1800, 2000
April 2006
Page 43
70/70/50
90/90/70
120/110/100
Freeze (minutes)
10 to 14
13 to 17
21 to 25
Harvest (minutes)
1 to 1.5
1 to 1.5
1/2 to 1
70/70/50
90/90/70
120/110/100
Suction at Ice Making Section, end of Freeze
35 to 45 PSIG
35 to 45 PSIG
40 to 50 PSIG
Suction at Ice Making Section, Harvest
85 to 105 PSIG
100 to 120 PSIG
120 to 150 PSIG
Discharge at Condensing Unit: Freeze
220 to 260 PSIG
250 to 270 PSIG
370 to 380 PSIG