Scotsman DB-101 Скачать руководство пользователя страница 5

SCOTSMAN WOOD FURNACE – INSTRUCTION MANUAL 

 

Scotsman

 

 

Jun

-10

 

4

CREOSOTE

 

Wood combustion is never 100% complete.  Wood smoke always contains some unburned 
gases and a mixture of unburned tar-like liquids.  A percentage of these materials will 
condense out on any cool surface, leaving a dark brown or black substance with an unpleasant 
acrid odor.  This substance is commonly called creosote. 

 

If these wood gases condense out on cool surfaces such as a cold chimney or a long smoke 
pipe, they retain large amounts of water and will be very fluid.  At higher temperatures the 
condensed creosote will resemble tar (thick and tacky). 

 

Creosote generation is highest during low heat outputs common with long smoldering burns.  
Creosote generation is lowest during high heat outputs common with intense fires.  It is 
recommended that a small intense fire be used for best results against creosote build up even 
though the wood furnace will require refueling more often. 

 

Creosote generation is also higher when burning green wood.  The moisture in the green wood 
absorbs the heat from the fire, cooling the fire below the point at which the creosote can be 
consumed.  The low temperature smoke is then further cooled in the upper furnace chambers; 
smoke pipe and chimney allowing large amounts of creosote to form. 

 

To reduce creosote build-up during periods of low heat requirements (i.e. Spring and Fall) it is 
recommended to fuel the wood furnace with smaller quantities of smaller diameter logs.  
Matching fuel loads and heat requirements will result in cleaner combustion and higher 
efficiency. 

 

IN CASE A SERIOUS CREOSOTE FIRE BEGINS: 

o

  Close the damper door by disconnecting chain. 

o

  Close all draft regulators. 

o

  Throw 1/2 lb. of coarse or table salt on the fire and close door immediately. 

o

  Call the FIRE DEPARTMENT at once! 

 

Have a firmly established Emergency Procedure in place for the handling of a flue fire. 

 

1.3 STORAGE 

OF 

WOOD 

 

Once cut, green wood dries (or seasons), quickly at first and then at a slower and slower rate.  
When the wood has been cut to the proper length and split, it should be piled outside during 
the summer months.  Place two poles on the ground to serve as rails to keep the firewood off 
the moist ground.  Stack the wood so that both ends of the logs are exposed to the air if space 
is available, since more drying occurs through the cut ends than through the sides.  This is true 
even with wood that has been split.  The woodpile should be under cover so that it will not 
absorb moisture from the rain and snow before it is used, but still open on the sides and ends 
to the drying effect of the wind and sun.  Store wood in neat well supported piles. 

 
 
 
 
 
 
 
 
 

Содержание DB-101

Страница 1: ...RE INSTALLING FURNACE OR LIGHTING FIRE CONSULT LOCAL AUTHORITIES IF IN DOUBT ABOUT YOUR LOCAL FIRE SAFETY REGULATIONS ALL INSTALLATIONS MUST BE MADE IN ACCORDANCE WITH LOCAL AND STATE OR PROVINCIAL CO...

Страница 2: ...t 17 Appendices APPENDIX A Warranty DIAGRAMS S101 1 Add On to Oil Clearances S101 2 Add On to Oil S type duct S101 3 Gravity Return Air Kit S101 4 Base for use on Combustible Floor S101 5 Controls Pla...

Страница 3: ...h 36 Diameter 23 Secondary Heat Exchanger 14 gauge steel Fire Box Door Cast Iron 13 x 13 Warm Air Plenum 32 x 25 3 8 Return Air Plenum N A Air Filter Size 16 x 20 x 1 Blower Size G10 10 Blower Motor 1...

Страница 4: ...anufactured logs compressed wood Before adding fuel to an existing fire turn up the thermostat for about five minutes or lift damper chain to hold damper fully open for about one minute before opening...

Страница 5: ...s smoke pipe and chimney allowing large amounts of creosote to form To reduce creosote build up during periods of low heat requirements i e Spring and Fall it is recommended to fuel the wood furnace w...

Страница 6: ...Cleaning should be done whenever there is more than 1 4 inch of build up on the heat exchanger or 3 inches of ash in the base If the wood furnace is to be left unused for an extended period of time m...

Страница 7: ...the following precautions should be taken DO NOT shut off power The blower must be kept running to disperse excessive heat Manually close the damper door by unhooking the chain Check controls for pro...

Страница 8: ...he cover is an option available from your Kerr dealer The kit must be installed on the cabinet side directly opposite to the entry of the blower or oil furnace S connection ductwork Manually open the...

Страница 9: ...fuel within the above clearances or within the space required for charging and ash removal o Establish a routine for storage of fuel care of the appliance and firing techniques 2 0 INSTALLATION INSTRU...

Страница 10: ...ig S101 4 The location of the furnace must be as close as possible to the tile lined brick chimney or factory built solid fuel approved chimney ULC S629 Keep in mind also the day to day operation and...

Страница 11: ...e flue gases are forced to fully heat the secondary heat exchanger which will maintain higher furnace efficiency The furnace must be located to meet a minimum venting distance needed between the furna...

Страница 12: ...lue key pipe dampers and check draft controls located on or in the flue pipe 4 The flue pipes of the appliances are connected to a manifold as close to the chimney as practicable or directly to the ch...

Страница 13: ...duct a 2 51 mm minimum clearance must be maintained between the warm air supply ducts and all joists or combustible material See Fig S101 1 Return air ducts including main ducts and branch ducts on s...

Страница 14: ...m the yellow wire leading to the blower compartment and both red and yellow wires marretted off then there would be no need for the switching relay Honeywell R4222D 1013 or equiv In that case the two...

Страница 15: ...end of the wire on to the other side of the normally open contacts relay spade 3 8 Remove the yellow low speed wire from the blower motor this should be the selected low speed in the furnace wiring bo...

Страница 16: ...a reverse flow is possible Before attempting installation determine if there is suitable space available in the furnace area for the furnace connection outlined herein The external static pressure in...

Страница 17: ...h technicians shall be licensed to perform this service The installation shall comply with the applicable requirements of CSA standard B365 Installation Code for Solid Fuel Burning Appliances and Equi...

Страница 18: ...s main disconnect switch within view 2 Wiring cables protected from heat and not touching hot surfaces FLUE AND SMOKE PIPE INSPECTION 1 Flue inner size equivalent to 7 round or larger 2 Separate entry...

Страница 19: ...ON CAPABILITY Add on furnaces such as the Kerr Scotsman and Scotty SS can be installed with oil fired warm air furnaces such as the Kerr Gemini that have continuous blower circulation capability A rel...

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ......

Отзывы: