background image

1.  Control Panel Installation

  

The Control Panel is fixed using the two M5 slots in the rear of the box.

 

  

Cabling for the Control Panel can either be run inside a cavity 

    

wall with an exit hole directly behind the Control Panel, or 

    

can be run in conduit on the outside of the wall. If using 

    

conduit, the optional mounting box must be used to allow 

    

cable access to the sides of the panel (Fig. 1).  

  

Undo the two small screws at the top of 

    

the panel and carefully remove the front 

    

face, taking care not to pull the cable 

    

between the two parts (Fig. 2). 

  

Connect the cable for each Head Unit to 

    

the appropriate screw terminals (marked 

    

CH1 to CH8) on either side of the rear 

    

entry slot. Note which colour wires have been 

    

used for each terminal (marked A, B, C, and D). 

    

These will connect to the corresponding terminals 

    

in the Head Unit. If using 3-core cable, connect to 

    

terminals A, B, and C only (Fig. 3).

NOTE:

 Incorrect wiring may lead to damage to 

either the Control Panel or the Head Unit. 

Cabling

  

Scorpion can be connected using the following cables to give up to 100m distance 

    between the Control Panel and each Head Unit:

2

    

a. Fire resistant cables such as FP200 1.5mm (Lapp J-Y(ST)Y 0.5mm ), 

 

       or equivalent recommended

2

2

    

b. Maximum conductor size is 1.5mm , minimum is 0.5mm

    

c. Screened cable is not required 

  

The connector used in the Head Unit is intended for solid-core conductors for ease 

    of installation in difficult areas. Stranded cable may be used but would need to be 
    tinned (soldered) or terminated with a suitable terminal (ferrule) with an external 
    diameter no greater than 1.5mm.

  

Each Head Unit requires three (3) conductors (A, B & C). 4-core cable is 

    recommended.

 

Cabling must be installed in accordance with local wiring regulations. Scorpion uses 

 

    battery power (nominal 7.2V, 2.2Ah).

  

Tighten the terminal screws. 

Mounting

Slots

2.  Control Panel Interface

TEST

CLEAR

TEST

CLEAR

R E M O T E   D E T E C T O R        

scorpion

T E S T  T E C H N O L O G Y 

®

0 0 0 

Time Indicator

Battery Low Indicator

RUN Button

STOP Button

Clearing Indicator

UP Button

DOWN Button

Smoke Test Indicator

Display

Clearing Time Button
(recessed)

Smoke Time Button
(recessed)

Display

Indicates: 
- Head Unit number (1 - 8)
- Timer (counting up in seconds when the green LED is on)

Display

- Three flashing dots indicates the internal fuse has blown (see Section 8)

UP

 

Button 

- Used to select Scorpion Head Unit or adjust timer
- When TEST or CLEAR recessed button is pressed, the UP button increases 
  the time

DOWN

 

Button

 

- Used to select Scorpion Head Unit or adjust timer
- When TEST or CLEAR recessed button is pressed, the DOWN button
  decreases the time

RUN

 

Button

 

- Used to start test (smoke generation and/or clearing)

STOP

 

Button

 

- Used to stop test (smoke generation and start clearing, or to stop clearing, 
  or to stop timer)
- Press for 3 seconds to activate or deactivate timer

Timer

 

Indicator 

- Lights up when timer is active
- The display then indicates the time since smoke generation and/or clearing
  cycle started

TEST

 

Indicator 

- Test cycle in progress (smoke generated and /or clearing functions)
- Recessed Button: Press with small pointed tool to change smoke duration

CLEAR Indicator 

- Clearing (detector purging) in progress 
- Recessed Button: Press with small pointed tool to change clearing time

Battery Low Indicator 

- Lights up when battery power is low

CAUTION

This product may be used at height.

Exercise great care and wear appropriate PPE (personal 
protective equipment) when operating above head height in 
order to avoid the risk of injury.

Fig. 2

Fig. 3

Fig. 1

Scorpion Control Panel
Installation & Operation Guide

(Point and ASD Systems)

Scorpion Control Panel

SCORP 8000

(including mounting box)

www.

scorpion-tester

.com/support

[email protected]

Care of Scorpion Products



Low Battery Indicator 

- illuminates when battery power 

   gets low. Tests cannot be made when the low battery indicator 
   is on and the battery will need to be recharged. 



Error

 - Three (3) flashing dots on the display indicate that 

   a fault has occurred causing the internal fuse to blow. 

TEST

R E M O T E   D E T E C T O R        

scorpion

T E S T  T E C H N O L O G Y 

0 0

. . .

0

Flashing dots on the display

indicate a fault

CLEAR

®

There are no user serviceable parts in the Scorpion Head Unit which is permanently sealed. 



 

Opening the Head Unit other than as shown in the Installation Guide will invalidate any 



   warranty. 

NOTE:

 The Head Unit is designed to be permanently installed providing in excess of 240 tests

The Control Panel contains a 500mA fuse which can be replaced if necessary (Littlefuse Surface



   Mount NANO2 SLO-BLO 500mA fuse, Manufacturer Part No. 0454.500, or equivalent).



There are no other user serviceable components in the Control Panel.

In the event of failure, any liability for No Climb Products Ltd. shall be limited to 



    

replacement of Scorpion components only.

LI37209-3

Please read the Scorpion Manual

Warnings and Errors

Service / Maintenance

Head Unit

Control Panel

R E M O T E   D E T E C T O R        

scorpion

®

T E S T  T E C H N O L O G Y 

Spare Fuse

www.acornfiresecurity.com

www.acornfiresecurity.com

Отзывы: