![SCM CUBO2 SMART Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/scm/cubo2-smart/cubo2-smart_oem-manual_1217973035.webp)
OEM Manual – CUBO
2
SMART
Pag. 35
15
HECU Controller layout
Analog Inputs
Digital Inputs
Analog Ouput
Digital Ouput
U1 -
DI1 ON/OFF remote
Y1 Modulating
fans
NO1-C1 Serious alarm
U2 Ambient temperature DI2 High pressostat
alarm
Y2 -
NO2-C2 -
U3 Suction temp. MT
DI3 Evaporator Request Y3 -
NO3-C3 -
U4 Discharge temp. MT
DI4 Change Setpoint
NO4-C4 -
U5 Gas Cooler Outlet
temp.
DI5 -
NO5-C5 -
U6 Suction pres. MT
NO6-C6 By-pass solenoid valve MT
U7 Discharge pres. Trans.
MT /GC pressure)
NO7-C7 Compressor Ready
U8 -
NO8-C8 Cabinet washing
U9 -
U1
0
Receiver pres.